CUSTOMIZED LINEARIZATION CYCLE 

Lin.enbl 

Lin

earization 

En

a

bl

Enables linearization. Applicable only when 

flow input is 4-20 mA. 

1np.01 

Inp

ut 

01

 

First input point for linearization. 

0vT.01 

Out

put 

01

 

First output point for linearization. 

1np.02 

Inp

ut 

02

 

Second input point for linearization. 

0vT.02 

Out

put 

02

 

Second output point for linearization. 

 

27 input and output points for linearization. 

1np.30 

Inp

ut 

30

 

Last input point for linearization. 

0vT.30 

Out

put 

30

 

Last output point for linearization. 

Table 11

 – Customized linearization cycle keys 

HARDWARE CYCLE (MANUAL MODE) 

manual

 

Manual

 mode

 

Enables manual mode of operation. 

(ur.0ut

 

Cur

rent 

Out

 

Current output status in manual mode. 

PUl.0ut

 

Pul

se 

Out

 

Pulse output status in manual mode. 

Rl1.0ut

 

R

e

l

ay 

1 Out

 

Relay 1 output status in manual mode. 

Rl2.0ut

 

R

e

l

ay 

2 Out

 

Relay 2 output status in manual mode. 

Rl3.0ut

 

R

elay 

3 Out

 

Relay 3 output status in manual mode. Visible 

only for the 4 relays model. 

Rl4.0ut

 

R

e

l

ay 

4 Out

 

Relay 4 output status in manual mode. Visible 

only for the 4 relays model. 

Table 12

 – Hardware cycle keys 

CALIBRATION CYCLE 

All input and output types are factory calibrated. If recalibration is 

required, it must be performed by a specialist. If this cycle is 

accidentally accessed, go through all parameters without changing 

values. 

PASS 

Pass

word

 

Access Password entry. 
This parameter is shown before protected 

cycles. See item Configuration Protection. 

(alib 

Calib

ration 

Enables calibration. 

inL( 

In

put 

L

ow 

C

alibration 

Entry of value close to the beginning of scale 

in 4-20 mA input, within scale specified in 

InLL

 and 

InKL

inx( 

In

put 

H

igh 

C

alibration 

Entry of value close to the end of scale in 4-20 

mA input, within scale specified in 

InLL

 and 

InKL

ovL( 

Ou

tput 

L

ow 

C

alibration 

On this screen, whenever you press 

 or 

, a standard current close to 4 mA will 

be applied. Measure current, in mA, and enter 

it on this screen. 

ovx( 

Ou

tput 

H

igh 

C

alibration 

On this screen, whenever you press 

 or 

, a standard current close to 20 mA will 

be applied. Measure current, in mA, and enter 

it on this screen. 

rstr 

R

e

st

o

r

Restores factory calibration. 

Pa.(x 

Pa

ssword 

Ch

ange 

Changes user password. 

Prot 

Prot

ection 

Protection level. 

Table 13

 – Calibration cycle keys 

CONFIGURATION PROTECTION 

The indicator allows configuration protection as determined by user, 

preventing unauthorized changes. The Protection (

PROt

) parameter, 

in the Calibration cycle, determines the protection level to be 

adopted, limiting Access to cycles, as shown in the table below. 

PROTECTION 

LEVEL 

PROTECTED CYCLE 

Calibration 

Calib Hardware 

Calib Ha Linearization 

Calib Ha Lineari Relays 

Calib Ha Lineari Relays 

+ Output Config. + Input Config. 

Calib Ha Lineari Relays 

+ Output Config. + Input Config. + Functions 

Calib Ha Lineari Relays 

+ Output Config. + Input Config. + Fun 

Alarm 

Calib Ha Lineari Relays 

+ Output Config. + Input Config. + Fun 

Alarm + Main 

Table 14

 – Configuration Protection Levels 

Access Password 

To access the protected cycles, it is necessary to enter an 

Access 

Password

  that allows altering the configuration of parameters in 

these cycles. 
The access password is entered in the 

Pass

 parameter, which is 

shown in the first of protected cycles. 
Without a protection password, parameters of the protected cycles 

can be only viewed. 
The Access Password is defined by user in the Password Change 

(

PA.(k

) parameter, shown in the Calibration cycle. 

New indicators come from factory with access password “1111”. 

Master Password 

If you forget the access password, it is possible to use the Master 

Password feature. When this password is entered, users gain access 

to the Password Change (

PA.(k

)  parameter and are allowed to 

specify a new access password to the indicator. 
The Master Password consists of the last three digits of the indicator 

serial number 

added

 to the number 9000. 

For example, for a device with serial number “12154321”, master 

password is “9 3 2 1”. 

MAINTENANCE 

PROBLEMS WITH INDICATOR 

Connection errors and inadequate programming are the main 

problems when using the indicator. A final review should prevent 

losses and wasting time. 

Summary of Contents for 81500FT020

Page 1: ...ization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seconds without input variation In...

Page 2: ...utput frequency has hardware limitation See Specifications Check the Specifications ALARMS The indicator s basic version has 2 alarm outputs with the option of up to 4 alarms Whenever an alarm is on a...

Page 3: ...feeder alarm will be activated If the process was stopped all counters will keep their values and the process will remain stopped until it is activated either by the key or the digital input MANUAL OP...

Page 4: ...value being modified Press while holding Available only for some parameters Change a parameter Press or to select the next option or in the case of a numerical value to increase or decrease the value...

Page 5: ...Table 5 Key f Key Function Selection of key function See Table 6 d 1n F Digital Input Function Selection of digital input function See Table 6 reset Reset Resets totalizer Bat rst Feeder Batch Reset...

Page 6: ...f the 4 20 mA input is enabled The YES option applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys SELECTION OF FLOW INPUT TYPE S...

Page 7: ...nt close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Protection leve...

Page 8: ...control and sends a response to the master The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledg...

Page 9: ...Isolation 250 Vrms Pulse Maximum frequency 100 Hz Voltage 0 to 30 Vdc Maximum current 15 mA Isolation 250 Vrms OUTPUT RELAYS ALM1 and ALM2 SPDT 3 A 240 Vac 3 A 30 Vdc resisitive ALM3 and ALM4 SPST NA...

Reviews: