Novus 81500FT020 Instruction Manual Download Page 3

N1500FT Flow Indicator 

NOVUS AUTOMATION 

3/9 

AUXILIARY DIGITAL INPUT AND 

 KEY 

Similarly to a digital input, the 

  key can be set to zero the 

totalizer, freeze the main screen, zero minimum and maximum 

readings or control the feeder function. 

FEEDER 

The feeder function is used to control the volume of fluids based on 

its flow rate.  It is typically used for storage applications, where there 

is a start signal that triggers a relay and the flow rate begins to be 

measured. When reaching a given setpoint, this relay is deactivated 

to stop flow. 
Its use depends on correct configuration of the related alarm. 
During the feeder  process,  it is not possible to change the alarm 

setpoint. Process should be reset first to allow it. 

Functions  of 

  key and/or  digital  input,  when assigned to the 

feeder function: 

 

When the 

  key or digital  input is activated,  the feeder 

process is started, activating all relays related to the feeder alarm; 

 

In case the 

 key or digital input is activated once again, the 

process is frozen and all relays related to the feeder alarm are 

deactivated; 

 

To restart the feeder process, 

 key or digital input must be 

activated for 3 seconds, until the process is restarted, zeroing all 

existing feeder indication.  This can be done with the process 

stopped or running; 

 

At the end of the feeder process, when alarm setpoint is reached, 

process values are frozen and all related relays are deactivated. 

To restart a new process, just activate the 

 key or digital 

input for all counters to be reset and process will start running; 

 

In case of a power shortage, if the feeder batch reset parameter 

(

Bat.rst

)  is configured as 

no

,

  whenever the equipment 

powers up again the process will restore from where it stopped. 

This means that, if it was in the middle of a feeder process, all 

relays assigned to the feeder alarm will be activated.  If the 

process was stopped, all counters will keep their values and the 

process will remain stopped until it is activated either by the 

 key or the digital input.

 

MANUAL OPERATION MODE 

In the hardware cycle, outputs can be set manually. This can be 

extremely useful for tests and simulations. After exiting the cycle, 

outputs go back to their regular status. 

24 VDC AUXILIARY POWER SUPPLY 

DC power supply models provide a 24 Vdc output for field transmitters. 

INSTALLATION 

The indicator must be installed on a panel. To do so, remove the two 

plastic clamps, introduce the device in the panel cutout and put the 

clamps back from the rear side of the indicator. 

INSTALLATION RECOMMENDATIONS 

 

Input signal conductors  should be disposed in the system 

separately from output conductors  and power conductors, 

preferably in grounded electrodes. 

 

Instruments should be powered through a dedicated network. 

 

For control and monitoring applications it is vital to consider what 

might happen if any part of the system fails.  The alarm internal 

relay does not ensure total protection. 

 

It is recommended to use RC FILTERS (47 

 and 100 nF, series) 

in contactor coils, solenoid coils, etc. 

ELECTRICAL CONNECTIONS 

All the inside can be removed without the need to undo the electrical 

connections. Disposition of signals in the rear panel of the indicator is 

shown in 

Fig. 1

 

Fig. 1

 – Rear panel connections 

POWER SUPPLY CONNECTION 

 

 

Fig. 2

 – Power supply terminals 

CONNECTIONS FOR INPUT AND OUTPUT SIGNALS 

It is important that these connections are well made, with signal or 

sensor wires securely attached to rear panel terminals. Check the 

“Specifications” section for the range of the input signals. 
 
The images below show connections for different input types: 

 

 

 

Fig. 3

 – Auxiliary digital input 

connection 

Fig. 4

 - Flow pulse input – 

Voltage signals 

 

 

Fig. 5

 -

 

Flow pulse input – 

NPN signals 

Fig. 6

 - Flow pulse input – 

PNP signals 

 

 

Fig. 7

 - Flow pulse input – Dry 

contact signals 

Fig. 8

 – Coil Signal connection 

(magnetic pickup) 

Summary of Contents for 81500FT020

Page 1: ...ization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seconds without input variation In...

Page 2: ...utput frequency has hardware limitation See Specifications Check the Specifications ALARMS The indicator s basic version has 2 alarm outputs with the option of up to 4 alarms Whenever an alarm is on a...

Page 3: ...feeder alarm will be activated If the process was stopped all counters will keep their values and the process will remain stopped until it is activated either by the key or the digital input MANUAL OP...

Page 4: ...value being modified Press while holding Available only for some parameters Change a parameter Press or to select the next option or in the case of a numerical value to increase or decrease the value...

Page 5: ...Table 5 Key f Key Function Selection of key function See Table 6 d 1n F Digital Input Function Selection of digital input function See Table 6 reset Reset Resets totalizer Bat rst Feeder Batch Reset...

Page 6: ...f the 4 20 mA input is enabled The YES option applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys SELECTION OF FLOW INPUT TYPE S...

Page 7: ...nt close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Protection leve...

Page 8: ...control and sends a response to the master The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledg...

Page 9: ...Isolation 250 Vrms Pulse Maximum frequency 100 Hz Voltage 0 to 30 Vdc Maximum current 15 mA Isolation 250 Vrms OUTPUT RELAYS ALM1 and ALM2 SPDT 3 A 240 Vac 3 A 30 Vdc resisitive ALM3 and ALM4 SPST NA...

Reviews: