Novatek NACF75 Operating Instructions Manual Download Page 3

2

Installation Instructions

CAUTION:

If the ground from the electrical panel or breaker
box  to  the  water  meter  or  underground  copper
pipe  is  tied  to  the  copper  water  lines  and  these
lines  are  cut  during  installation  of  the  Noryl
bypass  valve  and/or  poly  pipe,  an  approved
grounding  strap  must  be  used  between  the  two
lines  that  have  been  cut  in  order  to  maintain
continuity.  The  length  of  the  grounding  strap  will
depend  upon  the  number  of  units  being  installed
and/or  the  amount  of  copper  pipe  being  replaced
with poly. See Figure 1.

In all cases where metal pipe was originally used
and  is  later  interrupted  by  poly  pipe  or  the  Noryl
bypass  valve,  as  in  Figure  1  or  by  physical
separation  as  in  Figure  2,  to  maintain  proper
metallic pipe bonding, an approved ground clamp
c/w  not  less  than  #6  copper  conductor  must  be
used for continuity.

Check  your  local  electrical  code  for  the  correct
clamp and cable size.

NOTE:

This timer’s programs will be out of sync if

you turn the knob too far or do not allow the drive
motor to stop completely before continuing to the
next step. If this happens while doing any
procedure, rotate the knob clockwise until the
white dot lines up with the time of day arrow and
the unit will return to the service position. You can
then start again.

1.

Place filter on a flat surface in desired location, near a drain and 115 volt AC outlet. Subjecting your filter to freezing or to
water temperatures above 120°F (49°C) will void the warranty. Remove the valve from the carton. Be sure the distributor
tube is in place. Carefully position the valve over it and turn securely on to the fiberglass tank.

Note: 

All multi media and some larger units are supplied with the media separate. Please refer to page 5 Installations &

Replacement of Filter Media Pak.

2. Attach  the  installation  kit  or  bypass  to  the  control  valve.  Make  inlet  and  outlet  water  connections  to  meet  applicable

plumbing codes. A 3/4” inlet line is recommended. When sweat fittings are used, solder the adapters for the inlet and outlet
to the copper pipe first. This procedure is necessary because the controls 

must not

be subjected to temperatures above

160°F (71°C). Then, using teflon tape, screw the adapters for the inlet, outlet and drain into the valve. CAUTION: do not
use pipe thread compound as it may attack the materials in the valve body.

3. On the drain, use 1/2” hose barb supplied and full 1/2” hose (not supplied) for the drain line and make the shortest run to a

suitable  drain.  The  drain  line  must  be  secured  in  position  at  the  end  which  discharges  into  the  drain  so  it  cannot  be
inadvertently moved from the drain.

4. Loosen the two screws on the timer cover to remove it from the timer.

5. Automatic water filters are supplied from the factory in the backwash position, ready for start up. Turn on the water supply

to the unit. Open the supply line slowly and allow the air to escape from the filter before turning the supply water on all the
way. Allow the unit to backwash until all the air and media fines are no longer showing at the drain. This may take up to 15
minutes so you need to unplug the timer until you are ready to continue.

6.  Plug the timer in, set the time and frequency of regeneration following instruction on page 4. Allow the unit to complete the

cycle on its own from this point.

7. Make sure the bypass valve is in the service position.

Installation and Start-up Procedure

ALL GOVERNMENT CODES GOVERNING INSTALLATIONS OF THESE DEVICES MUST BE OBSERVED.

Electrical Panel

Ground Strap

Poly Pipe

Ground From Panel

Poly Pipe

Filter
c/w Plastic Bypass

Copper Pipe

Water Meter

Outside Water Line For Outside & 3rd Tap Comes From Meter

Filtered Water Line in Home

Unfiltered Water Bypass
Loop Cut & Capped

Ground Strap Required Because
of Break in Continuity

Figure 2

Figure 1

Summary of Contents for NACF75

Page 1: ...Carbon Filter MMF Multimedia Filter NF Neutralizing Filter Page 5 of this manual contains important maintenance procedures required for the continued proper operation of this unit These MUST be perfor...

Page 2: ...ckwash Inches W x D x H Size Inches Weight Lbs NNF75 75 2 3 5 3 5 10 x 10 x 57 8 x 47 75 NNF10 1 0 3 5 4 11 x 11 x 58 9 x 48 115 NNF15 1 5 5 8 5 12 x 12 x 64 10 x 54 165 NNF20 2 0 6 10 7 14 x 14 x 62...

Page 3: ...nstallation kit or bypass to the control valve Make inlet and outlet water connections to meet applicable plumbing codes A 3 4 inlet line is recommended When sweat fittings are used solder the adapter...

Page 4: ...being used regeneration should be staggered by 15 minute intervals from 1 a m Manual Bypass Figure 3A In case of an emergency you can isolate your water filter from the water supply using the bypass...

Page 5: ...s tab out Moving clockwise round the skipper wheel adjust the remaining tabs using the following table as a guide Manual Regeneration Turn the manual regeneration knob clockwise This slight movement o...

Page 6: ...rge drum or pail The tank must be rinsed out completely and have no media or gravel left in it at all Loading the Media Pak Place the distributor tube Item B back down the center of the tank The top o...

Page 7: ...sure permanent electrical service check fuse interrupted plug or switch Timer is defective Replace timer Power failure Reset time of day Broken cogs on the 24 hour gear Replace 24 hour gear Timer moto...

Page 8: ...od shall be from the date thereof Lifetime Guarantee on Mineral Tanks and Brine Tanks Novatek will provide a replacement mineral tank or brine tank to any original equipment purchaser in possession of...

Reviews: