background image

- 7 - 

NOVATEK-ELECTRO

                                                                                                    

 RNPP

-302

 

  

                                                                                                                      

 

Adjustable and measures 

parameters 

P

ar

amet

er

 

cod

es

 

Minimal 

va

lue

 

Ma

xim

al 

V

alue

 

F

ac

to

ry 

se

tt

ing

 

Description 

 

 

 

 

2 - MAXIMAL VOLTAGE RELAY, RNPP-302turns 
OFF the power load if the voltage gets higher 
than preset 

 value; 

3 - MINIMAL/MAXIMAL VOLTAGE RELAY, 
RNPP-302 turns OFF the power load if the 

voltage gets lower than 

 value or higher 

than 

 value 

Method to set Voltage 
deviation  



0 - voltage values are set up in absolute values 
1 - voltage values are set up in % of rated power 
parameters  

Phase imbalance control 

  0 

0 - not enabled 
1 - enabled 

Phase sequence control 

  0 

0 - not enabled 
1 - enabled 

Control of the voltage 
presence on the output 
contacts of the contactor 

  0 

0 - not enabled 
1 - enabled  
2 - enabled, and full-phase TURN OFF or TURN 
ON of the contactor is allowed (for example for 
the cases where manual stop/start function is 
required)  

Voltage setting

 

Voltage measurement 



0 - phase voltage (phase-to-neutral) 220V 
1 - phase voltage (phase-to-neutral) 230V 
2 - phase voltage (phase-to-neutral) 240V 
3 - line voltage (phase-to-phase) 380V 
4 - line voltage (phase-to-phase) 400V 
5 - line voltage (phase-to-phase) 415V 

Minimal voltage setting, 
V: 

              

In % values 

 

85 
147 

 

-60 

230 
398 

 

+10 

180 
311 

 

-30 

If 



 =0 and 



=0, 



=1,



=2; 

If 



 =0 and  



=3, 



=4,



=5; 

 

If 



 =1 and any values of 



 

parameter. 

Maximal voltage setting, 
V: 

              

In % values 

  235 

407 

 

-10 

295 
510 

 

+20 

245 
424 

 

10 

If 



 =0 and 



=0, 



=1,

 



=2; 

If

 



 =0 and



=3, 



=4, 



=5; 

 

If 



=1 and any values of 



  

parameter. 

Phase imbalance, V: 
              
 
In % values 

  10 

17 
 
 5 

80 
138 
 
35 

15 
25 
 

If 





=0, 



=1,



=2; 

If 



 =0 and  



=3, 



=4, 



=5; 

 
If 



 =1 and any values of 



 

parameter. 

Time setting

  

Autoreclosing time delay, 
sec 



0,5 
 

600 
 

10 
 

 

Time delay to TURN OFF 
the power load in case of 

minimal voltage

 

interruption detected, sec 

  0,1 

30 

10 

 

Time delay to TURN OFF 
the power load in case of 

maximal voltage

 

interruption detected, sec 

  0,1  

30  

1  

 

Time delay to TURN OFF 
the power load in case 
the phase imbalance is 
detected, s 

  0,1 

30 

3,0 

 

Summary of Contents for RNPP-302

Page 1: ...for 2 hours before switching to the mains Do not use abrasives or organic compounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components m...

Page 2: ...MS of the phase voltage or alternatively line voltage depending on mode of operation Voltage fault in mains power supply and the type of the interruption State of output relay contacts OPEN CLOSE NOTI...

Page 3: ...phase to neutral voltage on each phase L1 L2 L3 if the parameter 0 or alternatively phase to phase voltage L1 L2 L2 L3 L3 L1 if parameter 1 Phase Indicator indicator of the currently measured phase L...

Page 4: ...esting of the RNPP 302 4 2 2 Minimal voltage monitoring mode 1 If the RNPP 302 was initially in turned OFF state then in case the correct voltage is applied to the device it will automatically turn ON...

Page 5: ...load after the time and turn OFF the signalization RNPP 302 performs the control over following parameters 1 Phase imbalance If the parameter 1 the RNPP 302 performs the control over phase imbalance...

Page 6: ...ignalization relay for the operation by the contactor also So the main output relay could be used as a signalization relay with normally closed contacts contacts are closed when there is no alarm situ...

Page 7: ...manual stop start function is required Voltage setting Voltage measurement 0 3 0 0 phase voltage phase to neutral 220V 1 phase voltage phase to neutral 230V 2 phase voltage phase to neutral 240V 3 lin...

Page 8: ...iance with the operating manual by the user within the warranty period RNPP 302 is not subject to the warranty service in the following cases expiry of the warranty period availability of mechanical d...

Page 9: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Reviews: