- 4 - 

RNPP-302

 

  

                                                                                                                            

NOVATEK-ELECTRO

 

 

 

Figure 2

. Wiring diagram of the 

RNPP-302

 to the 4 wires power circuits (with neutral phase present). 

 

NOTES

. In case the RNPP-302 is installed in 3 wires power circuit (without neutral) the connection of the 

Neutral Phase (Terminal #4) is optional (neutral may not be connected). 
On the wiring diagram 220V contactor is shown like the example, if the connection of 380V contactor is 
necessary contactor coil “K” should be connected to L1 or L2 phases. 

 

4. 

RNPP-302 OPERATION

 

4.1. Modes of RNPP-302 operation. 

Depending on the 



 

parameter value the RNPP-302 can work in following modes:  

1)  Phase  loss  relay  (the  relay  monitors  only  the  presence  of  voltage  (not  the  voltage  level)  on  every 

phase) 

 



 

=0; 

2)  Minimal voltage monitoring relay 

 



=1; 

3)  Maximal voltage monitoring relay 

 



 

=2; 

4)  Over/Under voltage monitoring (min/max) mode 

 



 

=3 ; 

Modes of operation, adjustable parameters, time delays and other controls are shown in 

Table 2

.  

 

4.2. Voltage monitoring modes 

 

4.2.1 First start up instructions 

In case of first start up during the installation or if the RNPP-302 was deenergized on first turning ON it is 

necessary  to  add  0,3  -  0,4  seconds  to  the  automatic  reclosing  time  delay  (



 

parameter).  This  time  is 

necessary for preparation to work and for self-testing of the RNPP-302. 

4.2.2. Minimal voltage monitoring mode 

(



 

=1)

 

If the 

RNPP-302

 was initially in turned OFF state then in case the correct voltage is applied to the device it 

will  automatically  turn  ON  within  the  delay  time  defined  by

 



 

parameter:  the  “

REL

”  LED  will  light  up  and 

terminals 23, 24 will open while 22, 24 and 20, 21 will close. 

If the input voltage get lower than the minimal tripping threshold (parameter

 

) within the curtain time 

defined  by  user  (parameter 

– then the RNPP-302 will turn OFF the power load: terminals 23, 24 will 

close while 22, 24 and 20, 21 will open. 

RNPP-302  has  the  operative  acceleration  in  turn 

OFF

  time.  If  the  voltage  decrease  is  more  than  80  V 

regardless of the preset voltage tripping threshold the RNPP-302 will cut OFF the power load within 0,1 second. 

After the recovery of the voltage parameters 

– when controlled voltage becomes 5-6 V higher than minimal 

tripping threshold (voltage hysteresis is 5-6 V) the relay will automatically turn ON the power load with delay 
time defined by

 



 

parameter. 

4.2.3. Maximal voltage monitoring mode 

(



 

=2)

 

In this mode power load should necessarily be connected to terminals 23,24. 

When giving correct power  supply to the input of the RNPP-

302 the position of the output contacts don’t 

change and co

rrespond to “cold state”: terminals 23, 24 are closed while 22, 24 and 20, 21 are open. 

If the increase in input voltage is more than the maximal tripping threshold (parameter 

) within the 

 

Summary of Contents for RNPP-302

Page 1: ...for 2 hours before switching to the mains Do not use abrasives or organic compounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components m...

Page 2: ...MS of the phase voltage or alternatively line voltage depending on mode of operation Voltage fault in mains power supply and the type of the interruption State of output relay contacts OPEN CLOSE NOTI...

Page 3: ...phase to neutral voltage on each phase L1 L2 L3 if the parameter 0 or alternatively phase to phase voltage L1 L2 L2 L3 L3 L1 if parameter 1 Phase Indicator indicator of the currently measured phase L...

Page 4: ...esting of the RNPP 302 4 2 2 Minimal voltage monitoring mode 1 If the RNPP 302 was initially in turned OFF state then in case the correct voltage is applied to the device it will automatically turn ON...

Page 5: ...load after the time and turn OFF the signalization RNPP 302 performs the control over following parameters 1 Phase imbalance If the parameter 1 the RNPP 302 performs the control over phase imbalance...

Page 6: ...ignalization relay for the operation by the contactor also So the main output relay could be used as a signalization relay with normally closed contacts contacts are closed when there is no alarm situ...

Page 7: ...manual stop start function is required Voltage setting Voltage measurement 0 3 0 0 phase voltage phase to neutral 220V 1 phase voltage phase to neutral 230V 2 phase voltage phase to neutral 240V 3 lin...

Page 8: ...iance with the operating manual by the user within the warranty period RNPP 302 is not subject to the warranty service in the following cases expiry of the warranty period availability of mechanical d...

Page 9: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Reviews: