- 8 -
RN-16TМ
NOVATEK-ELECTRO
2. TO SET MIN/MAX VOLTAGE THRESHOLDS AND TIME DELAY SETTINGS
Perform steps 1-4 from the previous table section “1” (choose the operation mode).
Ste
p
s
Action
B
u
tto
n
Indication
B
u
tto
n
Action
Indication
1
Press end enter the
menu
2
By scrolling buttons find
U-PA
mode
◄►
3
Press and choose upper
voltage threshold
4
Press and while keeping
button pressed set the
required upper voltage
threshold, then release
the button when the
setting is done
(blinking dot)
◄►
Set upper voltage
threshold value in
the range 230-320
(blinking dot)
5
Press and save the
selected value in the
device memory (Save
and Exit)
6
Select LOWER voltage
threshold
◄►
7
Press and while keeping
button pressed set the
required lower voltage
threshold, then release
the button when the
setting is done
(blinking dot)
◄►
Set lower voltage
threshold value in
the range 150-210
(blinking dot)
8
Press and save the
selected value in the
device memory (Save
and Exit)
◄►
Press (calibration of
the present voltage)
NOT
RECOMMENDED
TO MAKE ANY
CHANGES ON
THIS STEP!
This function allows to perform precise calibration to the curtain power supply circuit.
If there is strong requirement it’s possible to change calibration voltage when having
voltmeter connected in parallel and setting the value shown on the voltmeter.
9
Press and while keeping
button pressed set the
required value, then
release the button when
the setting is done
(blinking dot)
◄►
Set the voltage
shown on voltmeter
L_ _ _
L._ _ _
L.205
L205
221.5
221.5
Н240
SP 1
U – PA
Н._ _
_
Н.240
Н_ _ _