- 6 -
RN-16TМ
NOVATEK-ELECTRO
- illumination level threshold setting.
Important notes:
Quality of the mains voltage power supply doesn’t influence on the preprogrammed
operation schedule of the RN-16TM. So after the normalization of the voltage parameters
power load will be turned ON again, but according to the time schedule preset by the user.
If mains voltage was absent not more than 1 month (device was disconnected for 30
days) all the parameters and settings will be safely kept in the RN-16TM memory. Output
contacts of the relay will be kept in a cold initial state.
For example RN-16TM was preprogrammed such a way that every day of a week it
turn ON the power load at 22:00 and then at 8:00 in the morning of next day it turns the
power load OFF. Let’s assume that at 22:30 on Monday mains voltage disappeared and
then recovered back only on Wednesday at 6:00 in the morning. So when voltage
disappeared contacts 3-4 opened.
As soon as the power load restore and return back to normal values RN-16TM will turn
ON the power load again but according to the preprogrammed schedule of operation. So at
6:00 when the power return – it will turn ON the power load and at 8:00 in the morning that
will turn it OFF according the schedule.
4 FIRST STARTUP PROCEDURES AND OPERATION ALGORHYTM
For preservation of working capacity of an inner clock when disappearance of
voltage
, it is necessary to establish a strap 5-6
(Figure
1).
Preliminary start up procedures include the following steps:
•
setting of the current time and the day of a week;
•
setting the schedule of events (exact time values and days of a week when
the power load should be turned
ON
and turned
OFF
as per users requirements);
•
setting the voltage tripping thresholds for MIN/MAX allowed voltage values
•
setting the delay times to turn
ON
for UPPER/LOWER voltage thresholds
•
setting the autoreclosing time delay
•
setting the level of illumination (if necessary)
If in the menu some parameter or event is seen blank (“_”) then the event or parameter
in not set.
When setting the time event schedule it’s possible to adjust the following parameters:
- turn
ON
time; - turn
OFF
time; - current time
where: “01” – is number of event (
ON/OFF
);
x – days of a week, it’s possible to set 1-7 values (Monday – 1; Tuesday – 2;
Wednesday – 3; Thursday – 4; Friday – 5; Saturday – 6; Sunday – 7);
A – equal time-schedule for all days of a week;
B – equal time-schedule for working days (Monday-Friday);
C – equal time-schedule events for weekend days (Saturday-Sunday);
To give the power supply to the RN-16TM it’s necessary to connect mains voltage
wires to 1-1 and 2-2 input contact terminals.
ATTENTION! All connections of terminals should be performed strictly according
to safety regulations and in the absence of voltage in the mains. So before wiring
make sure that the wire terminals are not under voltage.
Н_ _ _
Е01.х
d
01.х
L_ _
CLOC