- 4 -
RN-16TМ
NOVATEK-ELECTRO
Voltage measurement accuracy, V (doesn’t exceed)
1
Voltage hysteresis (returning ratio), V
+ 5
Illumination level hysteresis (returning ratio), %
12
Adjustable reaction time delay to Max/Min voltage interruptions, sec
0– 9,9
Autoreclosing time delay (the RN-16TM will automatically close the
contacts (turn ON the power load) as soon as the tripping parameters
return to normal values), sec
0– 9,9
Fixed reaction time to changes in illumination level, sec
12
Accuracy of the time clocks, seconds per day (not exceed)
3
Accuracy to adjust schedule time setting, min (not exceed)
1
Maximal number of events per day,
Include : - switching ON…………………………………………………..
- switching OFF.…………………………………………………
Events per week…………………………………………………………………
60
30
30
60
х7=420
Endurance to the voltage absence (retention of settings when supply
voltage is absent, no less than)
1 month
Protection degree: - relay
- terminal
ІР40
ІР20
Commutation life for the output contacts:
-- under load
16А,
no less than, operations
-- under load 5A, no less than, operations
100 000
1 000 000
Power consumption (under load), VA, not more than
3,0
Weight, not more than, kg
0,150
Dimensions, mm
50
х
88
х
65
Operating temperature,
°
С
from -10 to +55
Storage temperature,
°
С
from -20 to +70
3 GENERAL DESCRIPTION
The mains power supply 240V 50Hz should be connected to
«(1-1) – (2-2)»
terminals of
the
RN-16TM
. For wiring convenience terminals
1-1
are the one connection point and
2-2
terminals - another connection point. Output contacts have changeover relay
3 – 4
.
In a time of exploitation of relay a strap is set 5-6.This strap is connect the internal
accumulator of reserve clock motion. For warehousing of device it is recommended to take
off this strap that will substantially increase lifetime of accumulator.
Power load is being connected using terminals
3-4
.
Output contacts characteristics (terminals 3-4-4-5)
Max. current
under U~250V
A.C.
Max. power when
contacts are
closed
Max.
switch.
power
Max. long-term
safe voltage
A.C./D.C.
Max. current
under U=30V
D.C.
Cos
φ
=0.4
5A
5000VA
4000VA
380/150 V
5A
Cos
φ
=1.0
16A