background image

- 5 - 

NOVATEK-ELECTRO

                                                                                                      RN-111M

 

  

                                                                                                                            

 

2.3 PARAMETERS OF THE INTEGRATED RELAY OUTPUT TERMINALS 
The parameters of the integrated relay output terminals are shown in Table 3.

 

 

Table 3  

 

 

Maximal current 

at ~ 250V AC 

Maximal power when 

contacts are closed 

Maximal 

commutation power 

Maximal allowed  

AC/DC Voltage  

Maximal current  

at 30V DC 

Cos 

  = 0,4 

Cos 

  = 1 

А 

16A 

5000 VA 

4000 VA 

380/150 V 

5 А 

 

 

3. START-UP PROCEDURE AND CONNECTION  

 

3.1

.Using toggle switches on the front panel set necessary mode of operation ;  

3.2.

 In case of using RN-111M as Minimal/Maximal protection relay, Minimal protection relay or time relay 

connect  wires according Figure 2,vers.a.  

If  RN-111M  is  being  used  as  a  maximal  voltage  protection  relay  power  load  should  be  connected

 

according Figure 2,vers.b

.  

If power load is less than 16A (3,5 kW) then it could be commutated directly by the output contacts of the  

RN-111M; if the power load is more than 16A 

– then it should be commutated using contactor of appropriate 

rated parameters and the RN-111M should operate with the magnetic coil of the contactor.  

3.3.

 Connect RN-111M (contacts 

5, 8) 

to the power circuit.  

3.4.

  By  spinning  the  knobs  on  the  front  panel  set  the  required  Minimal  and  Maximal  voltage  tripping 

thresholds (

U

min

 and 

U

max

) and set necessary turn 

ON

 time delay (

T

on

). Please pay attention that the 

T

on

 

time  should  be  adjusted  taking  into  consideration  the  technical  documentation  and  requirements  of  the 
protected  power  load 

–  for  example  –  air-conditioners,  refrigerators  and  other  compressor  containing 

equipment usually need 3-4 minutes pause before turn 

ON

 again after they were disconnected.  

3.5

. Give the power supply to RN-111M and by spinning the adjustment knobs set precisely the required 

values for the 

U

min

U

max

 and 

T

on

. When spinning the knobs on the LED digital display it is shown the exact 

value of the adjusted parameter.  

 

4. GENERAL DESCRIPTION  AND OPERATION  

 

4.1.

 RN-111M has several functional states:  

– Normal operation mode: 

Power load is 

ON

, Green LED indicator 

– 

ON

. Digital LED display shows 

measured voltage value;  

– Alarm mode:

 Power load is 

OFF

, Green LED indicator 

– 

OFF

. Digital LED display shows blinking value 

of the measured voltage;  

– Indication of the remaining time to turn ON the power load (Ton):

 Power load is 

OFF

, Green LED 

indicator 

– 

OFF

. Digital LED display shows the remaining time to turn 

ON

 the power load (in seconds) and dot 

is being displayed in the lower digit. After the 

Ton

 time elapse RN-111M will return to 

Normal operation 

mode 

if voltage parameters on the input terminals are within the permitted range adjusted by the user.  

 

4.2

. MINIMAL/MAXIMAL VOLTAGE PROTECTION RELAY  

Power load (contactor coil) should be connected to the output terminals 2(3), 4 (Figure2).  
If RN-111M was initially deenergized or the power load was 

OFF

 due to the wrong voltage parameters 

– then 

after correct voltage appear on the input terminals and after the time delay 

T

on

 contacts 

1

, 2(3) will open and 

contacts 2(3), 4 will close.   

If input voltage get lower than minimal voltage threshold for more than 12 seconds RN-111M becomes to 

Alarm mode

 

– contacts 

1

, 2(3) close and contacts 2(3), 4 open. 

If input voltage gets 60V lower than the minimal voltage tripping threshold 

– RN-111M comes to Alarm mode in  

0,2 sec. After the recovery of the voltage parameters to the value of hysteresis (4-5V) 

– cycle is repeated relays.  

If input voltage gets higher than the maximal tripping voltage threshold for more than 1 sec. or the voltage is 

30V higher than the maximal tripping threshold during a period exceeding  

– then the RN-111M comes to 

Alarm 

mode

 

– contacts 2(3), 4 open and contacts 

1

,  2(3) close. When voltage  level  decrease  lower than the maximal 

tripping voltage threshold to the hysteresis value (4-5V) 

– RN-111M turns 

ON

 the power load with the user adjusted 

time delay 

T

on

.  

 

4.3. 

MINIMAL VOLTAGE PROTECTION RELAY  

Power load should be connected to the output terminals 2(3), 4 (Figure2).  
If 

RN-111M

 was initially deenergized or the power load was 

OFF

 due to the wrong voltage parameters 

– then 

after  correct  voltage  appear  on  the  input  terminals  and  after  the  time  delay 

T

on

  contacts 

1

2

(3)  will  open  and 

contacts 2(3), 4 will close.   

If  input  voltage  get  lower  than  minimal  voltage  threshold  for  more  than  12  seconds

 

RN-111M  becomes  to 

Summary of Contents for RN-111M

Page 1: ...ELECTRO LTD intellectual commercial electronics RN 111M SINGLE PHASE VOLTAGE PROTECTION RELAY OPERATING MANUAL Review the Operating manual before using the unit www novatek electro com www novatek ele...

Page 2: ...EMPT TO OPEN AND REPAIR THE PROTECTED EQUIPMENT IF SWITCHED TO THE UNIT SOCKET The electrical contact between the plug and the socket remains even in case of deactivated unit NEVER ATTEMPT TO OPERATE...

Page 3: ...he power load when necessary Kindly note that contactors of appropriate power rating should be chosen by User and not supplied along with RN 111M RN 111M has four independent modes of operation 1 Mini...

Page 4: ...ge frequency Hz 47 65 Harmonical configuration nonsinusoidality of power supply voltage EN 61000 3 2 IEC 1000 3 2 Adjustment ranges minimal voltage tripping range Umin V maximal voltage tripping range...

Page 5: ...ows measured voltage value Alarm mode Power load is OFF Green LED indicator OFF Digital LED display shows blinking value of the measured voltage Indication of the remaining time to turn ON the power l...

Page 6: ...ing time of 0 2 second is applied if the voltage is 30V higher than the maximal tripping threshold then the RN 111M comes to Alarm mode contacts 1 2 3 open and contacts 2 3 4 close When voltage level...