background image

~ 8 ~ 

NOVATEK-ELECTRO

    

                                                                                                                

PEF-

321АВР

 

Detailed description of Figure 5: 

– normal voltages are present at inputs 1, 2. Device 321АВР connected the load to 

input 1

 by contactor 

K1

– at 

input  1

,  the  voltage  went  beyond  the  limits  set  by  the  user  (a  failure  occurred).  The  device 

disconnects  the  load  from 

input 

1  by  contactor 

K1

  and  counts  the  transition  time  to 

input  2

 



», 

table 5).

 

– 

after the completion of the

 

«



», 

countdown, the device connects the load to 

input 2

 by contactor 

K2

– 

Some voltage appeared at 

input 1

. Device 321АВР counts the time of return to the priority input

 



», 

table 5).

 

– 

the device disconnects the load from 

input 2

 by contactor K2 and counts the transition time to another 

input

 



», 

table 5).

 

– 

the device connects the load to 

input 1

 by contactor 

K1

 

6.2.1.3 

To work with a three-phase generator, it must be connected to 

input 2

 (terminals 

30

33

) and select 

the appropriate mode of operation with a three-phase generator 

– «

» («



», table 5). The trigger signal for the 

generator is generated by the device in the event that a failure occurs at 

input 1

. The start and stop signal of the 

generator is shaped by the internal relay of the device, the contacts of which go to terminals 

20, 21, 22 (20 - 21

 - 

normally open contact, 

21 - 22

 normally closed contact). 

 

 
 
 

 
 
 
 
 
 
Fig.  6

 

–  Diagrams  of  works 

with a generator at 

input 2

 

 
 

 

A detailed description of work with a generator, in accordance with Fig. 6: 

– 

Input 1

 has a normal voltage. Device 321

 

АВР

 connected the load to 

input 1

 by Contactor K1. The LED

 

« 

 

» 

does not light

– 

At input 1, voltage went beyond the limits set by the user (a failure occurred). The device disconnects 

the  load  from 

input  1

  by  contactor 

K1

  and  counts  the  transition  time  to  the  secondary  input

 



», 

table 5). 

– 

After completion of the

 

«



», 

321

АВР time countdown, device 321АВР closes terminals 

20 - 21

 (sends 

a  signal  to  start  the  generator).  The  time  for  starting  and  warming  up  of  the  generator  is  counted 



», table 5). A test check is made for absence of voltage at the load (terminals 

34  -  36

)  and  for 

absence of failures at 

input 2

. The LED

 

« 

 

» 

flashes.

 

– 

The device connects the load to 

input 2

 by contactor 

K2

. The LED

 

« 

 

» 

lights up. 

– 

Some  voltage  appeared  at 

input  1

.  The  device  counts  the  time  of  return  to  the  priority  input

 



», 

table 5). 

– 

After completion of the

 

«



» 

countdown, the device disconnects the load from 

input 2 

by the contactor 

K2

. A test check is made for absence of voltage at the load (terminals 

34 36

) and absence of failures at 

input 1

. The device will count the time

 

«



» 

and

 

«



» (

table 5). The LED

 

« 

 

» 

flashes. 

– 

After completion of time

 

«



» 

countdown, the device will connect the load to

 input 1

 by contactor 

K1

– 

After completion of the

 

«



» 

countdown, the device will open terminals 

20 - 21

 (it sends a signal to turn 

off the generator). The LED

 

« 

 

» 

goes off. 

 

6.2.1.4

 

Battery connection

 

The battery is connected to terminals 39 and 40, as shown in Figure 3. 
The battery is charged in the buffer mode with current of not more than 60 mA. It is not recommended to use 

a battery with a capacity of more than 2 Ah because of the low charge current. 

Attention! Devices connected in parallel to the battery affect its charge. 

If there is voltage of 100 V, at least at one of the phases of any input, the device is powered by this voltage. 

Otherwise, 321 

АВР is powered by a battery with current of not more than 100 mA. If the battery is discharged to 

11.5 V, then 321АВР will disconnect the battery from the circuit and it will stop working. The next time the device 

Summary of Contents for PEF-321ABP

Page 1: ...m on the development and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the produ...

Page 2: ...AL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met namely Regulations for Operation of Consumer Electrical Installations Safety Rules for Oper...

Page 3: ...vervoltage category III Rated insulation voltage V 450 Rated impulse withstand voltage kV 4 0 Wire cross section for connecting to terminals mm2 0 5 2 Tightening torque of terminal screws N m 0 4 Tabl...

Page 4: ...frame self extinguishing plastic No harmful substances in amount that exceeds permissible exposure limits Table 3 Characteristics of output contacts Used terminals Max current at U 250 V A Number of...

Page 5: ...to power the device or connect the generator 7 8 9 10 11 not involved 31 the second phase of input 2 to power the device or connect the generator 12 13 the state of voltage at input 1 32 the third pha...

Page 6: ...ECTIONS MUST BE PERFORMED WITH THE DEVICE BEING DEENERGIZED An error in installation work may result in damage of the device and instruments connected to it To ensure reliability of electrical connect...

Page 7: ...f operation 321 supports 6 operating modes two equivalent three phase inputs two three phase inputs with priority input 1 two three phase inputs with priority input 2 three phase input 1 and a three p...

Page 8: ...input 1 by contactor K1 and counts the transition time to the secondary input table 5 3 After completion of the 321 time countdown device 321 closes terminals 20 21 sends a signal to start the generat...

Page 9: ...d configure other menu items In order to exit the menu press and hold the OK button for 3 s If no button is pressed within 30 s the menu will exit automatically Table 5 Menu Menu Value Name Descriptio...

Page 10: ...SCII 1 RTU MODBUS modes 134 Parity check parity check is off even parity check odd parity check 135 Number of stop bits or 136 Transfer rate transfer rate 2400 baud transfer rate 4800 baud transfer ra...

Page 11: ...d order dot is lighting 13 14 Phase voltage of phase 3 Low order dot is lighting 15 16 Linear voltage of phases 1 2 High order dot is flashing 17 18 Linear voltage of phases 2 3 Mid order dot is flash...

Page 12: ...s not lighting no voltage 400 AC 16 17 Optotransistor Availability of the battery Is not lighting the battery is disconnected Is lighting the battery is connected 280 AC 400 DC 18 19 Optotransistor Th...

Page 13: ...ite the value to 321 The coefficient of reduction to an integer value is determined by a number of decimal places 1 0 10 1 00 100 1 000 1000 Table 13 Error codes for the MODBUS protocol Error code Nam...

Page 14: ...s Addresses of the slave devices are in the range from 1 to 247 Figure 10 shows the ASCII frame format 1 byte Address Function code Data CRC checksum CRLF 2 bytes 2 bytes 2 bytes Up to 504 bytes 2 byt...

Page 15: ...tion 0x06 provides writing to one 321ABP register The master s request contains the address of the register and data for entering The answer of the device coincides with the request of the master unit...

Page 16: ...ored at the temperature from minus 45 to 60 C and relative humidity of no more than 80 10 ACCEPTANCE CERTIFICATE PEF 321 has been manufactured and accepted in accordance with the requirements of valid...

Reviews: