~ 9 ~
PEF-
321АВР
NOVATEK-ELECTRO
will be energized when voltage appears at one of the inputs or after replacing the battery with a charged one,
followed by a short pressing of an external button connected to the terminals (38 - 39).
If voltage appeared at any input when supply is from the battery, then after 12 s device 321
АВР will be
switched over to the mains supply, and the battery will be charging.
The measured battery voltage is available for reading at MODBUS and is converted to an integer value
(multiplied by 100), address 25. Also, the flag of battery connection to the terminals (38 - 39) is transmitted to
address 43, bit 4.
6.2.2
Menu setting and viewing
6.2.2.1
Menu settings
To enter the menu, press and hold the
«
OK
» button for 3 s. Display at
input 1
will show
«
», and at
display of
input 2
there will be
«
». Enter the password in accordance with clause 6.2.2.2. The factory default
password is
«
». If the
«
» value (table 5) is set to
«
» (password is not set), then after holding the «
OK
»
button for 3 seconds, you will immediately enter the menu.
To view and change menu values it is necessary:
–
after entering the menu to select the desired menu item by using
« » or « » buttons, it will be displayed
on the
input 1
display, and its value - on the input 2 display;
–
to change the value, press the
«
OK
» button, thereby the value on the input 2 display will flash;
–
change the flashing value with the buttons
« » and « »;
–
to save the data, briefly press the
«
OK
». The value on the input 2 display stops flashing, you can
proceed to view and configure other menu items.
In order to exit the menu, press and hold the
«
OK
» button for 3 s. If no button is pressed within 30 s, the
menu will exit automatically.
Table 5
- Menu
Menu
Value
Name
Description
Address
Basic items
Mode of operation
«
» – equivalent inputs;
«
» – priority input 1;
«
» – priority input 2;
«
» – work with a 3-phase generator;
«4» – work only with input 1;
«5» – work only with input 2.
100
Setting of the password
Described in clause 6.2.2.2
101
Voltage output
«
» – permanent display of one of the
voltages;
«
» – voltage display in turn, with interval of 5 s
102
Ratio of the minimum time of work
after load activation
Within 0 to 5 activations. If
«0» is selected, this
parameter is disabled
103
Full phase shutdown
«
» – full phase shutdown – a norm;
«
» – full phase shutdown – a failure
104
Reset to factory settings
If
«1» is written, there will be resetting of all
parameters of the menu
105
Voltages
Type of voltage measurement
«
» – phase voltages;
«
» – line voltages
106
Minimum phase voltage at input 1
From 140 to 230 V with interval of 5 V
107
Minimum phase voltage at input 2
108
¯
Maximum phase voltage at
input 1
From 235 to 260 V with interval of 5 V
109
¯
Maximum phase voltage at
input 2
110
Minimum line voltage at
input 1
From 240 to 395 V with interval of 5 V
111
Minimum line voltage at
input 2
112
¯
Maximum line voltage at
input 1
From 405 to 450 V with interval of 5 V
113
¯
Maximum line voltage at
input 2
114
Voltage imbalance at
input 1
From 15 to 140 V with interval of 5 V
115
Voltage imbalance at
input 2
From 15 to 140 V with interval of 5 V
116
Response time in case of failure
.
Minimum voltage
From 0.0 to 10.0 seconds with interval of 0.5 s.
If
«0.0» value is set, this item of the check is
not used
117