Novatek-electro PEF-320 Operating Manual Download Page 5

~ 5 ~ 

 

NOVATEK-ELECTRO

                                                                                                   

PEF-320                                                                                                           

 

With normal voltage on all phases, (L1, L2, L3), the load will be connected to phase L1. If the voltage value 

L1 goes beyond the thresholds,  the PEF-320 will check the L2  phase and connect the load through it. If the 
voltage value L2 is out of the trip thresholds, the PEF-320 will connect the load to phase L3. If the voltage on 
the backup phases does not correspond to the set thresholds, the load is switched off. 

 

Switching to the phase with unallowable parameters will not be performed. 

 

After the load had been switched to the backup phase and the voltage parameters  had been restored on 

the priority phase, the load will be switched to the priority phase after the return time set by the User. 

 

ATTENTION!  If  during  the  countdown  of  the  return  time,  the  voltage  in  the  priority  phase  goes 

beyond the thresholds, then the countertimer will be reset. 

 

If Tr is in the 

 position, then the return to the priority phase will be performed only when the voltage in 

the backup phase exceeds the specified thresholds. 

In the case when the voltage supplied to the load decreases below the threshold of the minimum allowable 

voltage, the switching over or disconnection of the load will be performed with a time delay of 12 seconds. If the 
voltage exceeds the threshold of the maximum allowable voltage or decreases by 30 V lower than the threshold 
of the minimum allowable voltage, the load switching over or disconnection will be performed with time delay of 
0.2 seconds.  

When the load is disconnected, the PEF-320 continues to perform the voltage control for all phases. 
After restoring the voltage parameters at one of the phases within acceptable limits, the PEF-320 will switch 

the load to this phase during the time of AR. 

 

 

     

4. THE INTENDED USE 

4.1. Preparation for operation 
4.1.1.

 Preparation for connection: 

  unpack  the  device  and  check  the  device  for  damage  absence  after  transportation;  in  case  of  such 

damages detection, contact the supplier or the manufacturer; 

  carefully study the Operation Manual (

pay special attention to the diagram of the device connection 

to power

). 

 

 

4.1.2.

 Device connection 

 

ATTENTION!  THE  DEVICE  IS  NOT  INTENDED  FOR  SWITCHING  A  LOAD  IN  CASE  OF  SHORT 

CIRCUITS. IN THE CIRCUIT OF OUTPUT CONTACTS OF THE DEVICE IT IS NECESSARY TO INSTALL 
THE CIRCUIT BREAKER (FUSE) WITH CUT-OFF CURRENT NOT OVER 16 A OF CLASS B. 

 

ATTENTION! ALL CONNECTIONS MUST BE PERFORMED WHEN THE DEVICE IS DE-ENERGIZED. 

 

Error when performing the installation works may damage the device and connected devices. 

 

To ensure the reliability of electrical connections the flexible (stranded) wires with insulation for voltage of at 

least  450 V  should  be  used,  the  ends  of  which  it  is  necessary  to  be  striped  of  insulati

on  for  5±0.5 mm  and 

tightened  with  bootlaces.  It  is  recommended  to  use  the  wire  with  cross-section  of  at  least  1 mm

2

.  Wires 

fastening should exclude mechanical damage, twisting and abrasion of the wire insulation. 

 

IT  IS  NOT  ALLOWED  TO  LEAVE  EXPOSED  PORTIONS  OF  WIRE  PROTRUDING  BEYOND  THE 

TERMINAL BLOCK. 

 

For a reliable contact, tighten the terminal screws with the force indicated in Table 1. 

 

When  reducing  the  tightening  torque,  the  junction  point  is  heated,  the  terminal  block  may  be  melted  and 

wire can burn. If you increase the tightening torque, it is possible to have thread failure of the terminal block 
screws or the compression of the connected wire. 

 

4.1.2.1.

 Connect the device according to the diagram shown in Fig. 2. 

 
 
 
                

                                               

Summary of Contents for PEF-320

Page 1: ...he development and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product aft...

Page 2: ...CHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met nam...

Page 3: ...and protect them against unallowable voltage variations in the mains According to the voltage presence and voltage quality on the phases the PEF 320 will automatically select the optimum phase in lim...

Page 4: ...ional relay output contacts A 5 Device operating capability phase voltage V 400 Short time allowable operating capability maximal phase voltage V 450 Power consumption under load W not more than 1 2 P...

Page 5: ...ters at one of the phases within acceptable limits the PEF 320 will switch the load to this phase during the time of AR 4 THE INTENDED USE 4 1 Preparation for operation 4 1 1 Preparation for connectio...

Page 6: ...time of return to the priority phase After the setting the threshold values the device is ready for operation with the load It is allowed to change the thresholds values Umax Umin Tr and Ton during th...

Page 7: ...helf life is 3 years 6 3 Warranty period of the device operation is 5 years from the date of sale During the warranty period of operation in the case of failure of the device the manufacturer is respo...

Page 8: ...______________________________________________ _______________________________________________________________________________ The Company is grateful to you for the information about the quality of t...

Reviews: