~ 4 ~
PEF-320
NOVATEK-ELECTRO
If the temperature of the device after transportation or storage differs from the ambient temperature at which it is
supposed to be operated, then before connecting to the mains keep the device under the operating conditions
within two hours (because of condensation may be on the device elements).
ATTENTION! The device is not intended for operation in the following conditions:
–
Significant vibration and shocks;
–
High humidity;
–
Aggressive environment with content in the air of acids, alkalis, etc., as well as severe contaminations
(grease, oil, dust, etc.).
2. TECHNICAL SPECIFICATIONS
The basic technical specifications are given in Table 1.
Table 1.
Designation
Value
Nominal phase voltage, V
230
Operating capability voltage, on single phase, V
120
Mains frequency, Hz
45
– 55
Trip threshold for Umin, V
160
– 210
Trip threshold for Umax, V
230
– 280
Time delay range for return to the priority phase (Tr), sec *
5
– 200
Time delay range of reclosing (Ton), sec
1
– 600
Fixed time delay of switching over (switching off) for Umin, sec
12
Time of switching over to reserve phases, sec, not more
0.2
Hysteresis (reset coefficient) on voltage, V
5
– 6
Accuracy of threshold trip, V
±3
Maximum switched current (cos
φ=1) of additional relay output contacts, A
16
Maximum switched current (cos
φ=0.4) of additional relay output contacts, A
5
Device operating capability phase voltage, V
400
Short time allowable operating capability maximal phase voltage, V
450
Power consumption (under load), W, not more than
1.2
Protection degree of the front panel
IP 40
Protection degree of terminals block
IP 20
Climatic version
NF 3.1
Electric shock protection class
II
Pollution rate
II
Category of overload
II
Device scope
Control and distribution device
Construction type (installation)
On standard DIN-rail, 35 mm
Cross-section of connection terminal wires, mm
2
0.5
– 1.5
Screw torque of terminal clams, N*m
0.4
Service life of output contacts:
-
under load 16 A, operations, not less than
-
under load 5 A, operations, not less than
50 000
100 000
Overall dimensions H*B*L, mm
90.2*36*64.5
Weight, kg, not more than
0.15
The device remains operational capability in any position in space
Housing material - self-extinguishing plastic
*
– If knob
Тr
is in position "
" there is no return to the priority phase
3. DESIGN AND PRINCIPLE OF OPERATION
The electronic phase switch PEF-320 is a microprocessor-based digital device.
The user should make settings of the trip threshold limits of the PEF-320 - the minimum and maximum
voltage values at which the device trips and switches over to the backup phase (switches off the load).
The glow of one of the green LEDs L1, L2, L3 on the front panel indicates the phase to which the load is
connected.
PEF-320 has three independent inputs, terminal L1 (priority phase) and L2, L3 (backup phases).