Novatek-electro PEF-320 Operating Manual Download Page 4

~ 4 ~ 

 

PEF-320 

                                  

                                                                          

NOVATEK-ELECTRO

 

 

If the temperature of the device after transportation or storage differs from the ambient temperature at which it is

 

supposed  to  be  operated,  then  before  connecting  to  the  mains  keep  the  device  under  the  operating  conditions 
within two hours (because of condensation may be on the device elements). 

 

ATTENTION! The device is not intended for operation in the following conditions: 

 

Significant vibration and shocks; 

 

High humidity; 

 

Aggressive environment with content in the air of acids, alkalis, etc., as well as severe contaminations  

          (grease, oil, dust, etc.). 

 

2. TECHNICAL SPECIFICATIONS

 

The basic technical specifications are given in Table 1. 

 

Table 1.

     

    

Designation 

Value 

Nominal phase voltage, V 

230 

Operating capability voltage, on single phase, V

 

120 

Mains frequency, Hz 

45 

– 55 

Trip threshold for Umin,  V  

160 

– 210 

Trip threshold for Umax, V 

230 

– 280 

Time delay range for return to the priority phase (Tr), sec *  

– 200 

Time delay range of reclosing (Ton), sec 

– 600 

Fixed time delay of switching over (switching off) for Umin, sec 

12 

Time of switching over to reserve phases, sec, not more 

 

0.2 

Hysteresis (reset coefficient) on voltage, V 

– 6 

Accuracy of threshold trip, V 

±3 

Maximum switched current (cos 

φ=1) of additional relay output contacts, A 

16 

Maximum switched current (cos 

φ=0.4) of additional relay output contacts, A 

Device operating capability phase voltage, V 

400 

Short time allowable operating capability maximal phase voltage, V 

450 

Power consumption (under load), W, not more than 

1.2 

Protection degree of the front panel 

IP 40 

Protection degree of terminals block 

IP 20 

Climatic version 

NF 3.1 

Electric shock protection class 

II 

Pollution rate

 

II 

Category of overload 

II 

Device scope 

Control and distribution device 

Construction type (installation) 

On standard DIN-rail, 35 mm 

Cross-section of connection terminal wires, mm

2

 

0.5 

– 1.5 

Screw torque of terminal clams, N*m 

0.4 

Service life of output contacts: 

-

 

under load 16 A, operations, not less than 

-

 

under load 5 A, operations, not less than 

 

50 000 

100 000 

Overall dimensions H*B*L, mm 

90.2*36*64.5 

Weight, kg, not more than 

0.15 

The device remains operational capability in any position in space 
Housing material - self-extinguishing plastic 
 

– If knob 

Тr

 is in position "

" there is no return to the priority phase 

 

3. DESIGN AND PRINCIPLE OF OPERATION

 

The electronic phase switch PEF-320 is a microprocessor-based digital device. 
The  user  should  make  settings  of  the  trip  threshold  limits  of  the  PEF-320  -  the  minimum  and  maximum 

voltage values at which the device trips and switches over to the backup phase (switches off the load).   

The glow of one of the green LEDs L1, L2, L3 on the front panel indicates the phase to which the load is 

connected. 

PEF-320 has three independent inputs, terminal L1 (priority phase) and L2, L3 (backup phases). 

Summary of Contents for PEF-320

Page 1: ...he development and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product aft...

Page 2: ...CHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met nam...

Page 3: ...and protect them against unallowable voltage variations in the mains According to the voltage presence and voltage quality on the phases the PEF 320 will automatically select the optimum phase in lim...

Page 4: ...ional relay output contacts A 5 Device operating capability phase voltage V 400 Short time allowable operating capability maximal phase voltage V 450 Power consumption under load W not more than 1 2 P...

Page 5: ...ters at one of the phases within acceptable limits the PEF 320 will switch the load to this phase during the time of AR 4 THE INTENDED USE 4 1 Preparation for operation 4 1 1 Preparation for connectio...

Page 6: ...time of return to the priority phase After the setting the threshold values the device is ready for operation with the load It is allowed to change the thresholds values Umax Umin Tr and Ton during th...

Page 7: ...helf life is 3 years 6 3 Warranty period of the device operation is 5 years from the date of sale During the warranty period of operation in the case of failure of the device the manufacturer is respo...

Page 8: ...______________________________________________ _______________________________________________________________________________ The Company is grateful to you for the information about the quality of t...

Reviews: