Precautions
Take the following precautions during installation:
§
Observe national and local electrical codes.
§
Connect 24-VAC power wiring to the terminals marked as 24 VAC only.
Connection to other terminals will damage them.
§
Do
not
use the Lingo as a final safety device.
§
Make sure that the 24-VAC power wiring is connected to a dedicated
transformer. No other devices should be powered by the transformer
connected to the Lingo.
§
Do
not
ground the transformer for this module on the secondary side.
§
Make sure that the Lingo power cannot be switched off accidentally. The
Lingo requires continuous power for proper operation.
Setting the Module
Address
Every Lingo module must have a unique address for it to be properly identified
on the local area network (LAN). Addresses are assigned in the software during
system programming.
NOTE!
The Lingo address must be set for one less than the Unit
number assigned to the Lingo in the ESS32 Unit Directory.
For example, Unit 1 will have an address of 00, Unit 5 will
have an address of 04, etc. When there is only one executive
module on the system, it must have an address of 00.
The address switches are located on the bottom edge, on the left side of the
Lingo. Set the switches to match the module address shown in Figure 1.
2
Doc. #569066000—B
7/30/04
Lingo Electronic Assembly Installation Instructions
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Figure 1.
Lingo address settings