Novalynx 200-WS-01B User Manual Download Page 7

NovaLynx Corporation________________________________________________________________________________ 

 

 

 
200-WS-21-A 

Page 7 

November 2018 

 

4.2.3

 

CLEAR Button 

The CLEAR button performs the following actions: 

1.

 

If the user is in an editable field, the field will be set to the lowest possible value. 

2.

 

If the user is viewing the Max Wind Speed, the recorded value will be erased. 

3.

 

If the unit is alarming, all delay counters will be cleared.  

4.2.4

 

GO Button 

Press GO from any menu to return to 
operating mode. 
If the unit is already in operating mode, press GO to pause the system and disable all alarms.  

4.3

 

Programming 

Press the GO button until the display shows the operating mode screen (see GO Button, above). 

1.

 

Press MENU to enter programming mode. Use the UP or DOWN buttons to reach the Wind 
Alarms Menu (see illustration below, left side). 

Wind Alarms(mph)
1: 15      2: 15

MENU

Wind Alarms(mph)
1: 15      2: 15

MENU

Wind Alarms(mph)
1: 15      2: 15

MENU

MENU

  

       Wind Alarms Menu

                       

Program channel #1

 

 

Program channel #2

 

2.

 

Press MENU again. A blinking block cursor will be displayed on the channel #1 value. (see 
Program channel #1, above). Press the UP or DOWN buttons to change the wind speed 
threshold for channel #1. 

3.

 

Press MENU again. The blinking block cursor will move to channel #2 (see Program channel #2, 
above). Press the UP or DOWN buttons to change the value. 

4.

 

Press MENU again to get back to the Wind Alarms menu. 

5.

 

Press UP to switch to the Alarm Delays menu. 

6.

 

Program the alarm delays in the same manner as you did the wind alarms. 

7.

 

When you are done setting the alarm delays, press GO to return to operating mode. 

4.4

 

DIP Switch Settings 

The DIP switches are pre-set at the factory and should not need to be adjusted. However, sometimes 
during installation they get changed accidentally.  

1.

 

The Dual Set Point controller is designed to operate as either a Wind alarm or Temperature 
alarm. The DIP switch marked "Wt" determines which mode is selected. Set this switch to OFF 
for wind alarms. 

2.

 

Set the "Wu" switch to OFF for wind speed in miles per hour (MPH). Set the switch ON for 
kilometers per hour (KPH). 

3.

 

The "Tu" switch sets the temperature units. This is not relevant to the wind alarms, so it doesn't 
matter how this switch is set. 

Wind:  0.0 (mph)
1: 15      2: 15

GO

 System Paused
  GO to resume

Operating Mode

Paused Mode

Summary of Contents for 200-WS-01B

Page 1: ...200 WS 21 A User Manual Dual Set Point Wind Alarm Phone 530 823 7185 USA Toll Free 800 321 3577 Fax 530 823 8997 Email nova novalynx com Website www novalynx com...

Page 2: ...the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Plea...

Page 3: ...UP and DOWN Buttons 6 4 2 3 CLEAR Button 7 4 2 4 GO Button 7 4 3 Programming 7 4 4 DIP Switch Settings 7 5 ANEMOMETER INSTALLATION 8 5 1 Anemometer Siting Considerations 8 5 2 Anemometer Mounting 8 5...

Page 4: ...kph and enable disable the buzzer Each alarm channel has three programmable settings Delay before Alarm 0 99 seconds above threshold before alarm activation Default 15 sec Alarm Set Point Wind speed t...

Page 5: ...ock outs in back surface for screw mounting to a panel Dimensions 5 12 x 6 25 x 2 95 inch 13 0 x 15 9 x 7 5 cm Weight Shipping 1 lbs 0 45 kg 2 lbs 0 9 kg 200 WS 01B Anemometer Specification Measuremen...

Page 6: ...osition Refer to the DIP Switch Settings section of the manual to correct this situation 4 2 Menu Navigation Locate the programming buttons below the display 4 2 1 MENU Button Press the MENU button On...

Page 7: ...displayed on the channel 1 value see Program channel 1 above Press the UP or DOWN buttons to change the wind speed threshold for channel 1 3 Press MENU again The blinking block cursor will move to ch...

Page 8: ...he object Roof mounted sensors should be placed on the upwind side of the building and away from all exhaust vents If the sensor is located on top of a building the sensor height should be 1 5 x H whe...

Page 9: ...st direct manner Leave a drip loop of cable below the entry point to the equipment enclosure to help keep moisture out Fasten the cable to the mast with cable ties to prevent whipping during high velo...

Page 10: ...INSTALLATION 6 1 Controller Location To be effective the Wind Alarm controller must be in a location where one can view the display and hear the alarm At the same time it should not be accessible to...

Page 11: ...earth ground an electrical box with an earth connection or a metal cold water pipe that actually enters the ground Failure to provide a ground may cause erratic operation and make the system more vul...

Page 12: ...d the Wind Alarm to the settings you desire and the system is operating properly before you connect power to your external devices 8 ALARM FUNCTIONS The Wind Alarm controller must be in Operating Mode...

Page 13: ...Dn Clr Go PROGRAMMING BUTTONS MODE WIND UNITS TEMP UNITS BUZZER WIND MPH DEG F BUZZ TEMP KPH DEG C SILENT ON OFF Wt Wu Tu Si DIP SETTINGS DUAL SET POINT WINDALARM 200 WS 21A Alarms OFF Red Black Shiel...