Novalynx 200-WS-01B User Manual Download Page 12

NovaLynx Corporation________________________________________________________________________________ 

 

 

 
200-WS-21-A 

Page 12 

November 2018 

 

7.3

 

Relay Connections 

There are two relays for connection of external alarms or to operate/disable pumps, etc. Please refer to 
the specifications to ensure the relays are rated for the load you intend to control. If the contact rating is 
less than required an external contactor may be required. Refer the installation to a qualified electrical 
contractor. 

WARNING: Turn off all power sources before connecting to the relays.

 Identify which relay(s) you will be 

using and which function is required. When there is no alarm, the N.O. contacts are OPEN. This contact is 
used to turn something ON when there is an alarm. The N.C. contact does the opposite, i.e. turns 
something OFF when there is an alarm. 

The contacts are "dry". Connect the hot lead to C1 for relay #1 or to C2 for relay #2. The N.O. or N.C. is 
then connected to the load, and the neutral of the load completes the circuit. 

Notice the unused spade lug (N.O. or N.C.) will be electrically HOT under some circumstances. Place a 
spare connector or insulating tape over the unused lug if there is any chance that someone might put their 
fingers on it accidentally. 

Be sure you have programmed the Wind Alarm to the settings you desire and the system is operating 
properly before you connect power to your external devices. 

8

 

ALARM FUNCTIONS 

The Wind Alarm controller must be in Operating Mode in order for the 
alarms to activate. Alarms are disabled while programming and when the 
unit is in Paused Mode. Be sure to return the unit to Operating Mode when 
the alarm function is required.

 (See GO button instructions). 

 

 

     Operating Mode Screen

 

Alarm Channel #1: 

The audible alarm will beep at 400 millisecond intervals (if enabled) and the relay will energize 
when the threshold and Delay-Before-ON timeout has occurred. A red LED on the circuit board will 
also flash. 

Alarm Channel #2: 

The audible alarm will beep at 200 millisecond intervals (if enabled) and the relay will energize 
when the threshold and Delay-Before-ON timeout has occurred. A red LED on the circuit board will 
also flash.  
When both alarms occur together, the beeping will be at 200 millisecond intervals. 

Paused Mode 

Press the GO button to place the controller in Paused Mode to turn off the alarms and relays. The 
controller will remain in this mode indefinitely unless the power to the controller is interrupted. 
Press GO again to return to operating mode.  

CLEAR Button 

(temporarily clears the alarm) 

The CLEAR button will stop the alarms by clearing the Delay Before ON timeout. If the wind speed is 
higher than the threshold the alarm will activate again when the timeout occurs. 

Wind:  0.0 (mph)
1: 15      2: 15

Summary of Contents for 200-WS-01B

Page 1: ...200 WS 21 A User Manual Dual Set Point Wind Alarm Phone 530 823 7185 USA Toll Free 800 321 3577 Fax 530 823 8997 Email nova novalynx com Website www novalynx com...

Page 2: ...the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Plea...

Page 3: ...UP and DOWN Buttons 6 4 2 3 CLEAR Button 7 4 2 4 GO Button 7 4 3 Programming 7 4 4 DIP Switch Settings 7 5 ANEMOMETER INSTALLATION 8 5 1 Anemometer Siting Considerations 8 5 2 Anemometer Mounting 8 5...

Page 4: ...kph and enable disable the buzzer Each alarm channel has three programmable settings Delay before Alarm 0 99 seconds above threshold before alarm activation Default 15 sec Alarm Set Point Wind speed t...

Page 5: ...ock outs in back surface for screw mounting to a panel Dimensions 5 12 x 6 25 x 2 95 inch 13 0 x 15 9 x 7 5 cm Weight Shipping 1 lbs 0 45 kg 2 lbs 0 9 kg 200 WS 01B Anemometer Specification Measuremen...

Page 6: ...osition Refer to the DIP Switch Settings section of the manual to correct this situation 4 2 Menu Navigation Locate the programming buttons below the display 4 2 1 MENU Button Press the MENU button On...

Page 7: ...displayed on the channel 1 value see Program channel 1 above Press the UP or DOWN buttons to change the wind speed threshold for channel 1 3 Press MENU again The blinking block cursor will move to ch...

Page 8: ...he object Roof mounted sensors should be placed on the upwind side of the building and away from all exhaust vents If the sensor is located on top of a building the sensor height should be 1 5 x H whe...

Page 9: ...st direct manner Leave a drip loop of cable below the entry point to the equipment enclosure to help keep moisture out Fasten the cable to the mast with cable ties to prevent whipping during high velo...

Page 10: ...INSTALLATION 6 1 Controller Location To be effective the Wind Alarm controller must be in a location where one can view the display and hear the alarm At the same time it should not be accessible to...

Page 11: ...earth ground an electrical box with an earth connection or a metal cold water pipe that actually enters the ground Failure to provide a ground may cause erratic operation and make the system more vul...

Page 12: ...d the Wind Alarm to the settings you desire and the system is operating properly before you connect power to your external devices 8 ALARM FUNCTIONS The Wind Alarm controller must be in Operating Mode...

Page 13: ...Dn Clr Go PROGRAMMING BUTTONS MODE WIND UNITS TEMP UNITS BUZZER WIND MPH DEG F BUZZ TEMP KPH DEG C SILENT ON OFF Wt Wu Tu Si DIP SETTINGS DUAL SET POINT WINDALARM 200 WS 21A Alarms OFF Red Black Shiel...

Reviews: