4. Read Status Operation
Viewing and Printing a Read Status
46
NFS-640 Operations Manual P/N 51334:B 10/03/2003
How to View Read Status for a NAC or Panel Circuit
From the “Read Status” screen, press
0
, then press the
ENTER
key.
You can now view Read Status for a NAC or Panel Circuit as
follows: press
OUTPUT
, enter the device address, then press the
ENTER
key. For example, to read the status of NAC 0-2: press
OUTPUT
, enter 02, then press the
ENTER
key. The control panel now
displays information for a NAC as shown in Figure 23.
The display and descriptions of the fields are shown below:
Figure 23 Sample NAC & Panel Circuit Read Status Display
•
Device Status
The status of the device: ON (device active) OFF (device not active).
•
Type Code
The software Type Code that identifies the type of NAC or Panel Circuit. Refer to
“Appendix F - Type Codes” in
NFS-640 Programming Manual.
•
CBE List
Only the first zone in the NAC or Panel circuit’s CBE list will be displayed here.
•
Device Address
The address of the NAC (01-04) or Panel Circuit (1-1 - 8-8)
•
Switch Inhibit
A selection for disabling the switch function for the panel circuit, control/relay,
or transponder output circuit. (I=on; *=off).
•
Silenceable
A selection that specifies if the device can be silenced during an alarm by pressing
the
SIGNAL
SILENCE
key.
•
Walk Test
A selection that specifies if the device will activate during a Walk Test.
Device address
next device
previous device
Type Code (CONTROL)
Walk Test selection:
W
selected for Walk Test
*
not selected
Label for the NAC or Panel Circuit
Default zone selection
Address (01-04)
B
= NAC
P
= Panel Circuit
Switch Inhibit:
I
selected,
*
not selected
Device status
Silenceable:
S
selected (default),
*
not selected
OFF
CONTROL
PANEL CIRUIT NO. 2
Z000
*SW
B02
Technical Manuals Online! - http://www.tech-man.com