Program
Panel Program
20
NFS-3030 Programming Manual P/N 51345:C 11/4/03
DISPLAY
ADDRESS:
Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER
MENU:
Press this soft key to bring up the Reminder Menu screen.
ACCEPT:
Press this soft key to save the information entered on this screen.
MORE:
Press this key to progress to the second Panel Settings screen.
Figure 3.5 Panel Settings (2) Screen
Soft Keys
LCM
LOCAL
MODE:
Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, the LCM will operate in a limited fashion when
communication is lost with the NFS-3030/E CPU. Inputs on the LCM loop (and associated LEM
loop, if installed) will activate outputs on the same loop(s)
• when the inputs and outputs have been set with point programming to participate in local mode
• when the type codes are of the same type: that is, an input with a fire alarm type code will
activate an output with a fire alarm type code
Default:
NO
PANEL
CIRCUIT
BELL
CODING:
Press to toggle between
MARCH
and
TEMPORAL
. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 104 for more
information. Default:
MARCH
DCC
PARTICIPATION:
Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default:
NO
CAUTION: On systems utilizing the DCC function, all locations that can participate in DCC
should be set to YES.
DEFAULT
SETTINGS:
Press this soft key to activate default settings for the following:
Program setting for:
Default:
Local Control
Yes
Piezo
On
Proprietary Supervising Station
No
Event Ordering
USA
Display Address
Yes
LCM Local Mode
No
Panel Circuit Bell Coding
March
DCC Participation
No
P A N E L S E T T I N G S
L C M L O C A L M O D E : Y E S
P A N E L C I R C U I T B E L L C O D I N G : M A R C H
D C C P A R T I C I P A T I O N : N O
D E F A U L T S E T T I N G S
A C C E P T
B A C K
!
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...