Navigating the Panel Menus
Operating Manual
5.2.2 Auto High Test
This is a maintenance facility only and is only available using an
access Level 3 passcode.
5.2.3 Alarm Devices
Alarm devices, such as sounders or control modules (set as type
SNDR, STRB but not as type CTRL), may be tested. Multiple devices
may be tested at the same time.
1
To test a device, or a selection of devices, first select the zone
which contains the device(s). If the panel is part of a network
you will be prompted for a node ID (number), even if the devices
that require testing are connected to the current panel.
2
Press the
/
navigation buttons to highlight the first device
in the list and then press the key to select for testing. For each
device selected for testing the IN TEST message is displayed in
the right-hand column. In the example provided at right module
81 on zone 26 is in test mode.
3
To stop testing of devices, select each device in test and press
the
key to cancel. The IN TEST message is removed to
reflect the status change. Alternatively, if a number of devices
are in test mode, press the key to cancel ALL alarm device
testing.
Note:
Unlike zone walk testing the TEST LED is not lit during alarm
device testing periods.