Section 5 - 8
www.notifierknowledge.com
997-670-000-2
Navigating the Panel Menus
Operating Manual
5.2 Start/End Testing
Various parts of the fire alarm system may be tested at user access
Level 2, as well as performing a function test of the panel’s visual
indicators and internal buzzer.
When a zone walk test is in progress, the TEST LED lights. When a
walk test is in progress the TEST tab is shown on the LCD display.
The following tests may be carried out from this menu:
-
Perform one or more zone walk tests (see
Section 5.2.1 Zones
)
-
Test alarm devices (see
Section 5.2.3 Alarm Devices
)
-
Perform a function test of the panel’s LEDs and function key
backlights (see
Section 5.2.4 LEDs
)
-
Test the function of the LCD (see
Section 5.2.5 LCD
)
-
Test the internal buzzer (see
Section 5.2.6
Internal Buzzer
).
5.2.1 Zones
To perform a zone walk test select option
1: Zones
from the Test
Menu; press the ‘1’ key on the alphanumeric keypad or, if highlighted,
press the or
key.
From the list of zones displayed, use numeric keypad to enter the
zone number or the
/
navigation buttons to highlight the
zone to be tested then press the key. The indicated status of the
zone changes from NORMAL to IN TEST and a TEST tab appears
behind the MENU tab.
Use the
key to bring the TEST screen to the top so that the
current test status of each device in the zone under test may be
viewed. Each device on the zone is listed with its status, NOT
TESTED/TESTED, displayed below the device icon. At the start of
testing all devices will show a status of NOT TESTED. Each time
a device is tested its status will change to TESTED on this screen.
OR