Configuring the ACPS-2406
Addressing
18
ACPS-2406 PN 51304:B 09/02/2003
The DIP Switch configurations chosen determine the ACPS-2406 address consumption. Refer to
Table 3.2 through Table 3.7 for illustrations of the DIP Switch/address consumption relationship.
3.2 Addressing
The installer must set aside sequential SLC addresses (an address block) equal to the number of
addresses that will be consumed by the ACPS-2406. Determing the size of the address block and
setting the SLC base address is described in this section.
Determining Address Consumption
An ACPS-2406 can occupy an address block of 5, 6, 8, 9, 12, or 13 addresses on an SLC, depending on the
configuration of ACPS-2406 DIP Switches. Table 3.2 through Table 3.7 below detail the DIP Switch/
address consumption relationship. Compare the actual DIP Switch settings with the tables: a match will
give the total number of SLC addresses necessary for the address block.
Refer to “Setting the Base Address” for information on the SLC Base Address.
Table 3.2 DIP Switch Settings Resulting in 5 Addresses Consumed
Table 3.3 DIP Switch Settings Resulting in 6 Addresses Consumed
DIP
Switch
DIP Switch Setting
ACPS-2406 Addresses Selected
by DIP Switch Settings at Left
ACPS-2406 Addresses
SLC
Address
SW3.1 ON or OFF
✔
1.Monitor General
B*
SW3.2 ON or OFF
✔
2. ACPS-2406 Output #1
B + 1
SW3.3 ON or OFF
✔
3. ACPS-2406 Output #2
B + 2
SW3.4 ON or OFF
✔
4. ACPS-2406 Output #3
B + 3
SW3.5 Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
✔
5. ACPS-2406 Output #4
B + 4
SW3.6
Not selected.
6. Signal Silence Address
SW3.7 Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
7. Monitor AC Fail (Canada only)
SW3.8
8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
SW2.1 ON or OFF
10. Dual Stage Output #1
SW2.2 ON or OFF
11. Dual Stage Output #2
SW2.3 ON or OFF
12. Dual Stage Output #3
SW2.4 ON or OFF
13. Dual Stage Output #4
SW2.5 OFF
Total: 5 Addresses
Assign 5 sequential SLC
addresses for this DIP Switch
configuration.
*B =SLC
Base
Address
SW2.6 ON or OFF
SW2.7 ON or OFF
SW2.8 ON or OFF
DIP
Switch
DIP Switch Setting
ACPS-2406 Addresses Selected
by DIP Switch Settings at Left
ACPS-2406 Addresses
SLC
Address
SW3.1
ON or OFF
✔
1.Monitor General
B*
SW3.2
ON or OFF
✔
2. ACPS-2406 Output #1
B + 1
SW3.3
ON or OFF
✔
3. ACPS-2406 Output #2
B + 2
SW3.4
ON or OFF
✔
4. ACPS-2406 Output #3
B + 3
SW3.5
Any combination except 3.5 ON, 3.6 ON
(Canadian Trouble Reporting)
✔
5. ACPS-2406 Output #4
B + 4
SW3.6
✔
6. Signal Silence Address
B + 5
SW3.7
Any combination except 3.7 ON, 3.8 OFF
(Dual Stage)
Not selected.
7. Monitor AC Fail (Canada only)
SW3.8
8. Monitor Battery (Canada only)
9. Monitor Earth Fault (Canada only)
SW2.1
ON or OFF
10. Dual Stage Output #1
SW2.2
ON or OFF
11. Dual Stage Output #2
SW2.3
ON or OFF
12. Dual Stage Output #3
SW2.4
ON or OFF
13. Dual Stage Output #4
SW2.5
ON
Total: 6 Addresses
Assign 6 sequential SLC
addresses for this DIP Switch
configuration.
*B = SLC
Base
Address
SW2.6
ON or OFF
SW2.7
ON or OFF
SW2.8
ON or OFF