Applications
Synchronization
30
ACPS-2406 PN 51304:B 09/02/2003
Figure 4.6 Supervised Daisy Chain Connection (Typical)
55 feet (16.76 m) of distance from each last
device when there is no wall or floor partition.
1, 3
ELR
ELR
ACPS-2406
ACPS-2406
ACPS-2406
ACPS-2406
ACPS-2406
ACPS-2406
SLC
SLC
SLC
SLC
SLC
SLC
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
2
W
A
L
L
W
A
L
L
2
1.
Refer To NFPA 72, 1999 Edition, Chapter 4-4, Visible Characteristics, Public Mode.
2.
The NAC output devices from one power supply must be partitioned with walls and/or floors from the next power supplies
and their NAC output devices.
3.
In an open area with no barriers, all strobe devices on the NAC outputs of one power supply must be at least 55 feet (16.76 m)
in distance from all strobe devices on the NAC outputs of another power supply.
4.
Use only devices from the same manufacturer in each system.
5.
A maximum of five slaves are allowable using this configuration.
Notes:
ELR
ELR
ELR
ELR
O
u
tput 4
O
u
tput 3
O
u
tput 2
O
u
tput 1
UZC-256 (
synch) Input
Output 4
Output 3
Output 2
Output 1
UZC-256 (synch)
Input
Output
4
Output
3
Output
2
Output
1
UZC-256 (
synch) Input
Output
1
Out
put 2
Out
put 3
Output
4
UZC-256 (
synch) Input
Output 1
Output 2
Output 3
Output 4
UZC-256 (synch)
In
p
u
t
Output 1
Output 2
Output 3
Output 4
UZC-256 (synch)
Input
From
FACP
or last
device
on
SLC
To next
floor
Line Drop to the last
device: 2.4VDC
Twisted Pair: Line Resistance
68.5 ohms per side max.