background image

2

General Requirements and Specifications

CAUTION

This unit must be installed in a dry place, in a non-corrosive, well-ventilated environment, without excessive dust.
The ambient temperatue must be over 10°C and under 27°C. If the ambient temperatue is 10°C or less, the plenum
must be insulated on 10 ft linear minimum length.

1. LOCATION – The furnace should be centrally located to the heating area.

2. POSITIONS – It can be installed for vertical, horizontal or downflow operation. When installed horizontally, the

furnace should be positioned such as the door will not end up being on the top. The door should be on the side of
the furnace, to ensure that the motor bearings are in their designed position. In vertical downflow installations, use
only “L”- or “T”-shaped plenum with no openings or registers directly below furnace.

3. INSTALLATION CLEARANCES – As shipped from the factory, each unit is approved for “zero inch” clearance. If

additional clearance is required, it will be indicated on the data label attached to the furnace.

4. TEMPERATURE RISE – Furnaces are shipped to operate at 0.20” W.C. (50 Pa) external static pressure. They are

certified for operation up to 0.50” W.C. (125 Pa). Check below for temperature rise table on specification chart and,
if necessary, adjust the unit to match.

5. SERVICE CLEARANCE – Units are serviced from the FRONT. Leave at least 24” (610 mm) clearance in front of

the door.

240 VOLTS - SINGLE PHASE

TEMPERATURE RISE

@ 0.20" W.C.

MODEL NO.

KW

BTUH

AMPS INCL. MOTOR

HP

°C

°F

SPEED*

21D10

10

34121

46

1/3

18

32

LOW

21D15

15

51182

67

1/3

21

38

MED

21D18**

18

61419

77

1/3

25

46

MED

21D20**

20

68243

86

1/3

28

51

MED

21D23**

23

78479

97

1/3

33

59

MED

21D25**

25

85304

107

1/3

35

64

MED

STATIC PRESSURE

FLOW

(INCHES OF WATER COLUMN)

SPEED

RATE

0.2

0.3

0.4

0.5

0.6

LOW

CFM

980

950

925

905

880

L/s

462

448

436

427

415

MED

CFM

1240

1220

1190

1165

1135

L/s

585

576

562

550

536

HIGH

CFM

1420

1395

1360

1330

1280

L/s

670

658

642

628

604

WARNING:

* FACTORY SETTINGS.

** These models must NOT be setup to run continuously at LOW speed as it will cause overheating conditions. These
models are certified to run only at HIGH and MED speeds.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

4

Summary of Contents for 21D10

Page 1: ...ON AND USER MANUAL D SERIES ELECTRIC FURNACE MODELS 21D10 21D15 21D18 21D20 21D23 AND 21D25 IMPORTANT READ AND SAVE THESE INSTRUCTIONS NORTRON Sherbrooke Quebec www dettson ca 1 800 567 2733 2019 11 2...

Page 2: ...not block the combustion air openings in the furnace Any blockage will result in improper overheat situation and may result in a fire hazard and or cause bodily harm The unit must have an uninterrupte...

Page 3: ...Supply 6 5 3 Connecting and Adjusting the Low Voltage Thermostat 6 6 Use in Mobile Homes 7 7 Using Optional Equipment 7 7 1 Two Stage or Outdoor Thermostat 7 7 2 Air Conditioning 7 7 3 Electronic Air...

Page 4: ...he data label attached to the furnace 4 TEMPERATURE RISE Furnaces are shipped to operate at 0 20 W C 50 Pa external static pressure They are certified for operation up to 0 50 W C 125 Pa Check below f...

Page 5: ...ation can be controlled by the thermostat the fan speed is determined by this switch HIGH The blower motor will operate at low speed LOW The blower motor will operate at a higher speed During spring o...

Page 6: ...the electrician s responsibility to ensure that the wiring and connections are compliant to the latest editions of the Canadian Electrical Code and local codes 5 3 Connecting and Adjusting the Low Vo...

Page 7: ...nction with the furnace wiring diagram 7 2 Air Conditioning Your furnace is equipped with all the controls required for the addition of air conditioning except the heat cool thermostat The evaporator...

Page 8: ...on When the electric furnace is used in combination with another device as for example a wood burning furnace it is recommended to perform the connection by referring to the wiring diagram at right Th...

Page 9: ...RNING Risk of electric shock Disconnect power before installation servicing maintenance or field wiring Replace all panels before operating Failure to do so can result in electric shock causing severe...

Page 10: ...iling Also Nortron recommends to contact a certified service depot for all replacement parts and repairs No Part No Description 1 30274131 24VDC Relay SPDT 2 L01H030 24VDC Relay DPST 3 30300022 Transf...

Page 11: ...mostat or its connecting wiring After the fault area is isolated by use of the thermostat a check of the following components can be made more efficiently Problem Possible defective parts or component...

Page 12: ...tation of repaired part or replaced product mentioned above and for reinstallation costs The duration of any implied warranty is limited to the sixty month period as specified for the express warranty...

Reviews: