Northern Stoker 30-30 Owner'S Manual Download Page 5

 

 

 

 

LOCATION: 

It is important to consider the prevailing wind directions in the heating season. The Northern Stoker should be placed so that the smoke 
exiting the unit will not create problems for you or your neighbours. Consult your Northern Stoker Dealer for suggestions where to 
locate the unit. 
 

PAD TO SUPPORT YOUR NORTHERN STOKER:  

First, remove the top soil, build a form, and fill it with concrete.  The pad should be 5” – 6” (127 – 152 mm) thick and have some wire 
mesh or rebar in it.  It should be a least 16” (400 mm) in front and 8” (200 mm) on either side of the fuel loading and ash removal doors.  
Consult your Northern Stoker Dealer for the local code requirements in your area.  

CAUTION! Check before you dig! 

Telephone Lines – Hydro Lines – Gas Lines – Water Lines – Sewer Lines – Drainage Tiles 

 
LIFTING TECHNIQUES  
 
 
 
 
 
 
TRENCH FOR INSULATED WATER LINES AND ELECTRICAL WIRE: 

The trench should be approximately 3’ (914 mm) deep and 18” (457 mm) wide.  It can be dug with a shovel or a backhoe.  Place all the 
dirt to one side of the trench to allow room for working on the other side.  Rake the bottom of the trench so it is smooth, no large bumps 
or sharp stones.  

 
WATER LINES: 
Water line to use

: 1” (25 mm) water line with a minimum rating of 100 psi (689.5 kPa) at 180ºF / 82ºC rating.  

Water line insulation

: Must be rated for at least R-8. Cover the insulated pipes with 3” (76 mm) of clean sand to avoid stone punctures. 

Contact you Northern Stoker dealer for approved water line insulation.  

Burying tip

: When burying your water lines in a low lying and wet area, be sure to insulate and install inside PVC piping.  

Burying tip

: When burying your water lines, be sure to sure to label the water lines at each end for ease of installation.   

Burying tip:

  If installing the water lines underneath a driveway, they should be buried approximately 4’-5’ (1219 – 1524 mm) below 

grade. If lines travel through a low or wet area, they should be insulated and installed in a water tight piping. 

Burying Tip:

  It is easiest to hook up your Northern Stoker when it is mounted on a concrete pad before the trench is dug.  If this is not 

possible, be sure to leave adequate pipe above the pad to complete the hook-up.  
Installation Tip: Be sure to install a furnace fill valve inside your home in the cold water return line preferably close to domestic water 
supply. This will aid when filling water into your system (see page 4). 

WIRING: 

The electrical wire used must be rated for underground and at least12 AWG copper, two wire plus a ground (12/2).  Place the electrical 
wire in the bottom of the trench and cover with 3” (76 mm) of sand along with the water lines from the Northern Stoker.  The electrical 
wire must maintain a minimum 24” (610 mm) depth. As with any buried electrical wires you must install a “Caution Buried Electrical 
Cable Below” tape over top of the wire. 

Always follow the applicable local Provincial and Municipal laws, regulations and codes. 

CHIMNEY SPECIFICATIONS: 

 
MODEL 30-30 

 

 

 

 

 

MODELS 36-42, 48-54 

Oliver Macleod – H.T. 6103 

 

 

 

 

Oliver Macleod – H.T. 6103

 

6” (152 mm) I.D.   

 

 

 

 

8” (203 mm) I.D. 

8” (203 mm) O.D.    

 

 

 

 

10” (254 mm) O.D. 

24” (610 mm) Long 

 

 

 

 

24” (610 mm) Long 

Tested to ULC – S610 

 

 

 

 

Tested to ULC – S610 

 

 

Use only a chimney suitable for solid fuel.  Do not connect to a chimney flue serving another appliance.  Place only on non 
combustible flooring with adequate support.  

 

 

 

Furnace Installation 

 
 
 

CAUTION! Lift between the legs from the side or from the lift hook on the top only! Do NOT lift 
from under the “control house” at the rear of the furnace. Ensure that the lifting device is rated 
for weight of the furnace and can safely lift and maneuver the Northern Stoker into position. 

Maintain the following clearances to combustibles: 

Sides – 8’ (2438 mm)    Front – 8’ (2438 mm)    Back - 8’ (2438 mm) 

 

Summary of Contents for 30-30

Page 1: ...SEDNOVEMBER1 2013 Note In an effort to provide our customers with the best product and experience available Northern Stoker reserves the right to update and modify the contents of this Owners Manual a...

Page 2: ...Starting a Fire 7 Refueling 8 Cleaning your Northern Stoker 9 Electronic Control System 10 14 Maintenance Schedule and Approved Fuels 15 16 Troubleshooting Guide 17 Furnace Diagram 18 Specifications...

Page 3: ...burn 30 50 less fuel This would represent a very high return on your labour Your Northern Stoker will give you the best results if you burn the best possible fuel which is Dry Wood If you cut your own...

Page 4: ...oor clean and free from combustible materials CAUTION It is important to regularly clean the flue pipes and chimney and is especially important to thoroughly clean at the end of the heating season to...

Page 5: ...erneath a driveway they should be buried approximately 4 5 1219 1524 mm below grade If lines travel through a low or wet area they should be insulated and installed in a water tight piping Burying Tip...

Page 6: ...ys and various system setups to add your Northern Stoker Water Treatment fluid Please contact your Northern Stoker Dealer for the best way to do so as per your system design Model 30 30 requires appro...

Page 7: ...C BOILER PERIODICALLY TO ENSURE THAT IT WILL OPERATE SATISFACTORILY WHEN NEEDED 2 DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS IN THE ORIGINAL GAS OIL ELECTRIC BOILER INSTALLATION 3 CAUTION TH...

Page 8: ...ater to water heat exchanger Forced Air Furnaces Forced air furnaces are the most common type of primary heat systems in residences today With the addition of a water to air heat exchanger installed i...

Page 9: ...fire 10 When you need to add this additional fuel turn OFF the combustion chamber blower fan follow instructions on page 8 for Refueling the Northern Stoker Wait a minimum of one minute or until smok...

Page 10: ...l into your Northern Stoker When placing the fuel in your furnace it should be placed in the firebox combustion chamber and not in the loading door frame area Wood can be loaded to the top of the open...

Page 11: ...en bottom auger This will clean the heat exchanger tubes and deposit the fly ash back into the combustion chamber Every two 2 weeks or there about it is advisable to remove the augers and clean the au...

Page 12: ...LOW WATER ALARM INDICATOR C START PUSH BUTTON D SYSTEM OFF ON ILLUMINATED SWITCH G INTERIOR LIGHT OFF ON SWITCH H CONTROLLER I TEMPERATURE FARRENHEIT J OUT1 INDICATES BLOWER IS ON M PV INDICATES ACTU...

Page 13: ...roller system to function correctly The switch will illuminate red if left in the OFF position This is a reminder to the operator to turn the switch ON for normal operation Note The auxiliary receptac...

Page 14: ...GLE DEGREE INCREMENTS TO 10 DEGREE INCREMENTS This button changes the set temperature UP Down buttons O from single degree increments to 10 Degree increment adjustments M PV INDICATES ACTUAL MANIFOLD...

Page 15: ...e UP arrow and DOWN arrow buttons O on the CONTROLLER H The range of adjustable temperature is 150 F to 185 F 65 6 C to 85 C Simply press up or down to the desired temperature shown at M Now the furna...

Page 16: ...chamber loading door and turn ON the blower fan Toggle switch located on the upper right side of structure Flip combustion chamber blower fan toggle switch ON D When you want to shutdown the furnace f...

Page 17: ...ean out augers Page 9 Observe light layer of soot fly ash or creosote on the combustion chamber walls chimney flue chimney connector or chimney and remove Page 9 Top up with water to ensure there is n...

Page 18: ...cian or Northern Stoker Dealer APPROVED FUEL NON APPROVED FUELS Dry split wood up to 25 moisture content Fire starter fluids of any kind Gas Diesel Fuel Oil Tires Naphtha YOUR INVESTMENT You have inve...

Page 19: ...le Fan Forced Furnace make sure that existing primary heat source is operating correctly If the temperature reading is inaccurate check that the temperature probe has a loose connection come out of th...

Page 20: ...TDOOR 120V LIGHT 11 EXPANSION TANK AND WATER LEVEL INDICATOR 4 CHIMNEY AND RAINCAP 12 HEAT EXCHANGER DOORS HOUSES AUGERS FOR ASH CLEANOUT 5 INTERIOR LIGHT SWITCH LOCATED ON 6 WATER LEVEL FLOAT SWITCH...

Page 21: ...OUSE AND FLOOR WEIGHT AND OUTSIDE DIMENSIONS EMPTY 3175 lbs 1440 kg 84 2134 mm L x 56 11 16 1440 mm W x 105 5 8 2383 mm H WATER CAPACITY 167 IMP GALLONS 758 L ELECTRICAL RATING 120V 60HZ 15A HEAT OUTP...

Page 22: ...Follow instructions in owner s manual OPERATE THE OIL GAS ELECTRIC BOILER PERIODICALLY TO ENSURE IT WILL OPERATE SATISFACTORILY WHEN NEEDED DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS IN THE...

Page 23: ...21 Notes...

Page 24: ...N INFORMATION INSTALLED BY DEALER CUSTOMER INSTALLED FOR HOUSE COMMERCIAL AGRICULTURAL GARAGE SHOP GREENHOUSE OTHER ____________________________________________________________________________________...

Page 25: ...GES INCURRED TO PROPERTY BY DISTRIBUTORS DEALERS AND SUB TRADES DAMAGE CAUSED BY CORROSIVE WATER WATER TREATMENT PURCHASED FROM A NORTHERN STOKER DEALER MUST BE ADDED TO HELP WITH CORROSION LUBRICATIO...

Page 26: ...N INFORMATION INSTALLED BY DEALER CUSTOMER INSTALLED FOR HOUSE COMMERCIAL AGRICULTURAL GARAGE SHOP GREENHOUSE OTHER ____________________________________________________________________________________...

Page 27: ...GES INCURRED TO PROPERTY BY DISTRIBUTORS DEALERS AND SUB TRADES DAMAGE CAUSED BY CORROSIVE WATER WATER TREATMENT PURCHASED FROM A NORTHERN STOKER DEALER MUST BE ADDED TO HELP WITH CORROSION LUBRICATIO...

Page 28: ...GES INCURRED TO PROPERTY BY DISTRIBUTORS DEALERS AND SUB TRADES DAMAGE CAUSED BY CORROSIVE WATER WATER TREATMENT PURCHASED FROM A NORTHERN STOKER DEALER MUST BE ADDED TO HELP WITH CORROSION LUBRICATIO...

Reviews: