Use this chart to estimate the total load on  your

generator.

For Determining Generator Load Requirements

Dev ice

Running Watts

Air Conditioner (12,000 Btu)

1700 (a)

Battery Charger (20 Amp)

500

Belt Sander (3”)

1000

Chain Saw

1200

Circular Saw (6-1/2”)

900

Coffee Maker

1000

Compressor (1 HP)

2000 (a)

Compressor (3/4 HP)

1800 (a)

Compressor (1/2 HP)

1400 (a)

Curling Iron

700

Dishwasher

1200

Edge Trimmer

500

Electric Nail Gun

1200

Electric Range (one element)

1500

Electric Skillet

1250

Furnace Fan (1/3 HP)

1200 (a)

Freezer

800 (b)

Hair Dryer

1200

Hand Drill (1”)

1100

Hand Drill (1/2”)

875

Hand Drill (3/8”)

500

Hand Drill (1/4”)

250

Hedge Trimmer

450

Home Computer

150

Impact Wrench

500

Jet Pump

800

Lawn Mower

1200

Light Bulb

100

Microwave Oven

700

Milk Cooler

1100 (a)

Oil Burner on Furnace

300

Oil Fired Space Htr (140,000 Btu)

400

Oil Fired Space Htr (85,000 Btu)

225

Oil Fired Space Htr (30,000 Btu)

150

Oven

4500

Paint Sprayer, Airless (1/3 HP)

600 (a)

Paint Sprayer, Airless (handheld)

150

Radio

200

Refrigerator

600 (b)

Slow Cooker

200

Submersible Pump (1-1/2 HP)

2800 (a)

Submersible Pump (1 HP)

2000 (a)

Submersible Pump (1/2 HP)

1500 (a)

Table Saw  (10”)

2000 (a)

Television

500

Toaster

1000

Vacuum cleaner

250

VCR

70

Water Heater

3000

Weed Trimmer

500

(a) Hard-starting motors require 3 to 5 times the

rated running watts.

(b) These loads may require up to 15 minutes  to

restart due to their normal build up of  compressor
head pressure.

NOTE: For extremely hard to start  loads  such  as

air conditioners and air  compressors,  consult  the
equipment  dealer to determine the maximum wattage.

 PRE-START PREPARATIONS

Your generator has been thoroughly tested prior to

shipment from the factory.  A factory test report has
been included with this manual.   However,  damage
can occur during shipping, so be sure to check for
damaged parts or loose or missing nuts and bolts.  If
the aforementioned problems occur, call Customer
Service at 1-800-270-0810.

GROUNDING - 

All units must be grounded.  Drive

a 3/4” or 1” copper pipe or rod into the  ground  close  to
the generator.   The pipe/rod must  penetrate  moist
earth.  Connect an approved ground clamp to the pipe.
Run a no. 12 Ga. wire from the clamp  to  the generator
grounding screw located on the generator  head.    Do
not connect to a water pipe or a ground used by a
radio system.

CAUTION: 

The engine has been shipped without

oil.  Fill the crankcase with oil before trying to start.
Low oil shut-down prevents your generator from
starting without sufficient oil.

OPERATING SPEED

The generator must be run at  the  correct  speed  in

order to produce the proper  electrical  voltage and
frequency. The speed of the engine was carefully
adjusted at the factory so that the generator produces
the proper voltage and frequency.

The output voltage should be checked with a

voltmeter to ensure the generator is working properly
before connecting a load to the generator.  Failure to
do so  could  result in damage to equipment  plugged
into the unit and possible injury to the individual.

All engines have a tendency to  slow down  when  a

load is applied.  When the electrical load is  connected
to the generator,  the engine is  more  heavily loaded,
and as a result the speed  drops  slightly.   This  slight
decrease in speed, together with the  voltage  drop
within the generator itself, results in a slightly lower
voltage when the generator is loaded to its full capacity
than when it is running with no  load.   The  slight
variation has  no  appreciable effect in the  operation of
motors, lights and most appliances. Electronic
equipment and clocks will be affected if correct RPM is
not maintained. See Load vs. Output chart.

Load

Output

Percent of
Generator

Output

Speed
(RPM)

Frequency

(Hz)

Generator

Voltage at 120V

Receptacle

0 %

3750

62.5

120

50 %

3660

61.0

120

100 %

3600

60.0

120

Summary of Contents for 15000 PPG

Page 1: ...EL 15000 PPG ITEM 165925 Professional Portable Generator M165925A OWNER S MANUAL 00211 Shown with Wheel Kit Item 165919 Any Questions Comments or Problems Call Customer Service at 1 800 270 0810 Hours...

Page 2: ...r North Star Pro Series Generator IMPORTANT Make certain the operator Reads and understands the manuals pertaining to this machine Is instructed in safe and proper operation of this machine NOTICE K B...

Page 3: ...y 2 1 US quarts with filter Starting Method Electric start 120V Receptacles 2 20 Amp A duplex NEMA 5 20R 30 Amp A twistlock NEMA L5 30R 120 240V Receptacles 30 Amp A twistlock NEMA L14 30R 60 Amp A st...

Page 4: ...240V 60A Receptacle 13 Choke 4 120 240V 30A Twistlock Rec 14 Muffler Spark Arrestor 5 120V 30A Twistlock Rec 15 Oil Filter 6 120V 20A Duplex Rec 16 Battery Box Battery 7 Oil Drain Valve 17 Gas Line Va...

Page 5: ...g the generator Reference 13 Choke Lever Used during cold starts Refer to the starting stopping instructions and the Kohler Command 25 engine manual for usage Reference 14 Muffler and Spark Arrestor R...

Page 6: ...njury to people NEVER touch hot muffler hot exhaust manifold or engine cooling fins ALWAYS remove all oil or gasoline deposits and accumulated dirt from generator and immediate area Keep generator hea...

Page 7: ...Cap or Split Phase SP type The following chart shows the approximate current required to start and run various types and sizes of 120 volt 60 cycle electric motors under various conditions 120V 60 Hz...

Page 8: ...damaged parts or loose or missing nuts and bolts If the aforementioned problems occur call Customer Service at 1 800 270 0810 GROUNDING All units must be grounded Drive a 3 4 or 1 copper pipe or rod i...

Page 9: ...s revolving field and synchronous type with one sealed radial roller bearing The rotor of the generator head is directly connected to the engine crank shaft and the stator is rigidly coupled to the en...

Page 10: ...ine speed too high b Voltage regulator out of adjustment a Bring generator to a qualified technician for adjustment b Bring generator to a qualified technician for adjustment Generator overheating a G...

Reviews: