      TROUBLESHOOTING

Problem

Possible Causes

Possible Remedies

Engine will not start.

a)  Low oil level.
b)   Fouled spark plug.
c)   Out of fuel.
d)  Stop switch in OFF position.
e)  Battery has lost its charge.

f)  Engine fuse is blown.

a)   Fill crankcase to proper oil level.
b)   Clean or replace spark plug.
c)   Fill fuel tank.
d)   Place switch in ON position.
e)  Battery has low electrolyte and/or
needs to be charged or replaced.
f)  Replace fuse.  30A Buss type fuse,
located near starter motor.

Voltage too low.

a)   Engine speed too slow.

b)   Generator is overloaded.

c)   Voltage regulator out of adjustment.

a)  Bring generator to a qualified
technician for adjustment.
b)  Reduce the load. (See Load
Application section of this manual.)
c)  Bring generator to a qualified
technician for adjustment.

Circuit breaker trips.

a)   Defective load connected to generator.
b)   Defective receptacle.
c)   Generator overloaded.

a)   Disconnect load.
b)   Replace receptacle.
c)   Reduce the load. (See Load
Application section of this manual.)

Voltage too high.

a)   Engine speed too high.

b)   Voltage regulator out of adjustment.

a)  Bring generator to a qualified
technician for adjustment.
b)  Bring generator to a qualified
technician for adjustment.

Generator overheating.

a)    Generator is  overloaded.

b)   Insufficient ventilation.

a)   Reduce the load. (See Load
Application section of this manual.)
b)   Make sure there is at least 3 feet of
clearance on all sides of generator.

No output voltage.

a)   Defective load connected to generator.
b)   Broken or loose wire.

c)   Defective receptacle.
d)   Defective stator.

e)   Defective rotor.

f)   Defective capacitor.

g)   Voltage regulator fuse has blown.

a)   Disconnect load.
b)  Bring generator to a qualified
technician for repair.
c)   Replace receptacle.
d)  Bring generator to a qualified
technician for repair.
e)  Bring generator to a qualified
technician for repair.
f)   Bring generator to a qualified
technician for repair.
g)  Bring generator to a qualified
technician for repair.

Engine lacks power.

a)  Generator is overloaded.

b)  Dirty air filter.

a)   Reduce the load. (See Load
Application section of this manual.)
b)   Clean or replace air filter.

Engine shuts down
during operation.

a)   Out of fuel.
b)   Low oil level.

a)   Fill fuel tank.
b)   Fill crankcase to proper oil level.

Summary of Contents for 15000 PPG

Page 1: ...EL 15000 PPG ITEM 165925 Professional Portable Generator M165925A OWNER S MANUAL 00211 Shown with Wheel Kit Item 165919 Any Questions Comments or Problems Call Customer Service at 1 800 270 0810 Hours...

Page 2: ...r North Star Pro Series Generator IMPORTANT Make certain the operator Reads and understands the manuals pertaining to this machine Is instructed in safe and proper operation of this machine NOTICE K B...

Page 3: ...y 2 1 US quarts with filter Starting Method Electric start 120V Receptacles 2 20 Amp A duplex NEMA 5 20R 30 Amp A twistlock NEMA L5 30R 120 240V Receptacles 30 Amp A twistlock NEMA L14 30R 60 Amp A st...

Page 4: ...240V 60A Receptacle 13 Choke 4 120 240V 30A Twistlock Rec 14 Muffler Spark Arrestor 5 120V 30A Twistlock Rec 15 Oil Filter 6 120V 20A Duplex Rec 16 Battery Box Battery 7 Oil Drain Valve 17 Gas Line Va...

Page 5: ...g the generator Reference 13 Choke Lever Used during cold starts Refer to the starting stopping instructions and the Kohler Command 25 engine manual for usage Reference 14 Muffler and Spark Arrestor R...

Page 6: ...njury to people NEVER touch hot muffler hot exhaust manifold or engine cooling fins ALWAYS remove all oil or gasoline deposits and accumulated dirt from generator and immediate area Keep generator hea...

Page 7: ...Cap or Split Phase SP type The following chart shows the approximate current required to start and run various types and sizes of 120 volt 60 cycle electric motors under various conditions 120V 60 Hz...

Page 8: ...damaged parts or loose or missing nuts and bolts If the aforementioned problems occur call Customer Service at 1 800 270 0810 GROUNDING All units must be grounded Drive a 3 4 or 1 copper pipe or rod i...

Page 9: ...s revolving field and synchronous type with one sealed radial roller bearing The rotor of the generator head is directly connected to the engine crank shaft and the stator is rigidly coupled to the en...

Page 10: ...ine speed too high b Voltage regulator out of adjustment a Bring generator to a qualified technician for adjustment b Bring generator to a qualified technician for adjustment Generator overheating a G...

Reviews: