Locating & Installing the Supply Damper(s)

 CAUTION:

If installing this air conditioning system in 

conjunction with a furnace, a damper must be 

installed in the furnace base assembly to prevent 

cold air from being discharged around the heat 

exchanger. Damage to the heat exchanger 

and asphyxiation may occur if a damper is not 

installed.
Check with the furnace manufacturer for damper 

requirements. Failure to install the required 

furnace damper may invalidate code agency 

listing and limited warranty on the furnace.

When locating the supply damper(s), carefully check floor joists 

and frame members that could interfere with the installation of the 

damper or flexible duct. Ideally, the damper should be located 

in the bottom of the main duct, forward of center of the home, 

at least three feet from the nearest register. See 

Figure 5

. The 

round supply opening in the slanted side of the damper should 

face the side of the home where the air conditioner is located.
1. Locate the center of the heat duct by cutting a small hole in 

the fiberboard below the duct at the desired location.

2. Cut a hole approximately 3/4” larger than the damper opening 

in the fiberboard.

3. Cut a 9-1/8” x 13-1/8” hole in the duct and bend over all tabs 

flat on the inside of the heat duct.

4. Insert the damper into the duct and bend over all tabs flat on 

the inside of the heat duct.

5. Seal the opening between the fiberboard and damper or 

flexible duct.

Condensate Drainage

A 3/4” condensate fitting extends out of the side of the unit 

(

Figure 6

). The drain trap, shipped in the electrical compartment, 

must be installed to prevent water from collecting inside the unit.

1. Thread the elbow provided with the unit into the drain 

connection until hand tight.

2. Connect the condensate tubing onto the fitting, forming a trap 

near the drain connection.

3. Route the condensate tube from the trap to a suitable drain. 

NOTE:

 For proper drainage, make sure the trap is level to 

the ground and tubing outlet is below trap level.

ELECTRICAL CONNECTIONS

 WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury, death or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
•  Before servicing, disconnect all electrical power 

to the indoor blower.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

•  All electrical connections must be in compliance with all 

applicable local codes and ordinances, and with the current 

revision of the National Electric Code (ANSI/NFPA 70).

•  For Canadian installations the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

 Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

 Verify that the service provided by the utility is sufficient to 

handle the additional load imposed by this equipment. Refer 

to the unit wiring label for proper high and low voltage wiring.

 Verify factory wiring is in accordance with the unit wiring 

diagram 

Figure 10 (page 12)

 and 

Figure 11 (page 13)

Inspect for loose connections.

Line Voltage

•  A wiring diagram is located on the inside cover of the electrical 

box of the unit. The installer should become familiar with the 

wiring diagram before making any electrical connections to 

the unit.

• 

An electrical disconnect must be located within sight 

of and readily accessible to the unit. 

This switch shall be 

capable of electrically de-energizing the unit.

•  Line voltage to the unit should be supplied from a dedicated 

branch circuit containing the correct fuse or circuit breaker for 

the unit. Incoming field wiring and minimum size of electrical 

conductors and circuit protection must be in compliance with 

information listed on the unit data label. Any other wiring 

methods must be acceptable to authority having jurisdiction.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect the 

line-voltage leads to the terminals on the contactor inside 

the control compartment. Extend leads through power wiring 

hole (

Figure 7

). Connect L1 & L2 directly to the contactor.

Figure 5. Supply Damper

Figure 6. Drain Trap

Elbow

P-Trap

Summary of Contents for VP7RE Series

Page 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Page 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Page 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Page 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Page 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Page 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Page 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Page 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Page 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Page 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Page 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Page 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Page 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...