background image

5

AIR CONDITIONER INSTALLATION

Unpacking the Unit

It is recommended that the unit be unpacked at the installation 

site to minimize damage due to handling.

 CAUTION:

Do not tip the unit on its side. Oil may enter the 

compressor and cause damage.

1. Remove the bands from around the unit.

2. Unfold the top and bottom cap flanges.

3. Carefully remove the top cap and tube.

Installing Return & Supply Air Collars (Optional)

Supply and return collars are not supplied with the unit but 

are offered as accessory item. Check with your distributor for 

pricing and availability. They can be easily positioned over the 

unit openings and secured with sheet metal screws. See 

Figure 

Table 2, (page 10)

.

•  The diameter of the return duct collar is 14”.

•  The diameter of the supply duct collar is 12”.

•  Before permanently installing the collars, it is recommended 

you pre-fit them over the openings first to determine best fit 

and alignment.

Supply Duct

1. Assemble the collar by overlapping the two ends. 

NOTE:

 One end of the collar is slotted and the opposite end 

has two small holes. Position the end with small screw holes 

underneath the slotted end.

2. Fasten the collar ends with two self drilling sheet metal screws.

3. Position the collar over the opening and align the 4 holes in 

the collar with the 4 holes (or dimples depending on model) 

in the rear panel.

4. Using self-drilling screws (10-16x.5), secure the collar to the 

rear panel.

Return Duct

1. Assemble the collar by overlapping the two ends.  

NOTE: 

One end of the collar is slotted and the opposite end 

has two small holes. Position the end with small screw holes 

underneath the slotted end.

2. Fasten the collar ends with two self drilling sheet metal screws.

3. Position the collar over the opening. Align the four holes in 

the collar with the four dimples or holes (depending on unit 

model) in the panel.

4. Secure the collar to the rear panel using self tapping screws 

(10-16x.5).

Locating & Installing the Return Air Assembly

To simplify installation, locate and install the return air assembly 

first. If desired, the return opening can be located inside a closet 

with louvered doors that has an open area equal to or greater 

than a 12” x 20” grille. The return air grille can be placed in the 

wall of a closet and the air ducted into the filter box through a 

boxed-in area at the closet floor level (

Figure 4

). 

Verify the filter 

is readily accessible.
NOTE:

 The return air box with grille and filter should not be 

located in heavy traffic areas like hallways or center of rooms. 

A good spot is in a corner or under a table, if a minimum two 

inch clearance is available.
1. Start the installation from under the home by cutting a small 

hole in the subfloor. Determine how the floor joist location 

will affect cutting the opening needed for the return air box. 

NOTE: 

Floor joists are generally located on 16” centers, 

leaving 14-3/8” between joists.

2. After measuring the return air box (approximately 12-1/4” x 

20-1/4”), cut the hole through the floor so that the box will fit 

between the floor joists. Care should be taken when cutting 

through carpeting to avoid snags. 

NOTE:

 In most installations 

it will be necessary to cut a similar hole in the fiberboard 

directly under the hole in the floor. However, if the floor is 

more than ten inches deep, it will only be necessary to cut 

a hole for the collar on the return air box or for the insulated 

duct.

3. Set the box into the opening and fasten with screws or nails.

4. Install the filter and return air grille in the air box.

Connecting the Return & Supply Air Flexible Ducts

•  Flexible ducts may be cut to the required length and spliced 

with sheet metal sleeves and clamps. 

Keep all ducts as short 

and straight as possible. Avoid sharp bends. 

Please follow 

all instructions packed with duct.

•  Flexible ducts can be secured to the corresponding fittings 

with the clamps provided with the ducts. 

NOTE:

 To prevent a 

loss in cooling capacity, make sure all connections are tight.

•  Ducts may be spliced with sheet metal sleeves and clamps.

•  After the inner duct is connected to the proper fitting, the 

insulation and plastic sleeve should be pulled over the 

connection and clamped.

•  Homes with multiple supply ducts (or special applications), 

a Y fitting is available to divide the supply air so it can be 

ducted to different areas of the home for more efficient cooling. 

NOTE: 

For maximum performance, insulate the Y fitting.

Transition

Duct Screws

Supply Air

Return Air

Duct

Dimples

Figure 3. Return & Supply Air Collars

Figure 4. Return Air Box

Summary of Contents for VP7RE Series

Page 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Page 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Page 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Page 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Page 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Page 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Page 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Page 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Page 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Page 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Page 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Page 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Page 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...

Reviews: