background image

6

“N”- 56"

23 3/4"

“C”- 76"

“A” Model 

w/o Coil 

Cabinet

“B/C” Model 

w/Coil 

Cabinet

19 3/4”

Figure 4. Overall Dimensions

Table 1. Minimum Clearances

ALL MODELS

CLOSET

ALCOVE

Front

6”

18”

Back

0”

0”

Sides

0”

0”

Roof Jack

0”

0”

Top

6”

6”

Top and Sides of Duct

0”

0”

Bottom of Duct

A Cabinet (w/ coil box)

0”

0”

A Cabinet (w/o coil box)

1/4”

1/4”

B Cabinet

0”

0”

GENERAL INFORMATION

 CAUTION:

•  Do Not alter or modify this furnace or any of 

its components.

•  Never attempt to repair damaged or inoperable 

components. This may cause unsafe operation, 

explosion, fire and/or asphyxiation.

•  If furnace malfunctions or does not operate 

properly, contact a qualified service agency 

or gas utility for assistance.

Minimum Clearances

This heating appliance must be installed with clearances 

not less than the minimums listed in 

Table 1, (page 6)

This furnace must be installed with ample clearance for 

easy access to the air filter, blower assembly, burner 

assembly, controls, and vent connections. See 

Figure 1

Figure 2

, and 

Figure 3

.

•  The dimensions of the room or alcove must be able to 

accommodate the overall size of the furnace and the 

installation clearances listed in 

Table 1

 and in 

Figure 4 

(page 6)

.

• Alcove installations: minimum 18” clearance at front 

of furnace shall be provided for future servicing. A 

removable access panel should be installed between 

top of the furnace door frame and the ceiling.

• Closet installations must use a louvered door having 

a minimum free area of 235 in

2

 when located 6” from 

furnace or 390 in

2

 for 5 ton MG1 furnaces. For special 

clearance between 1” - 6”, requirements are a louvered 

door with a minimum of 250 in

2

 free area, with the 

openings in the closet door in line with the louvered 

openings in the furnace door. A fully louvered closet 

door may be used. See Circulating Air Requirements 

section (

page 7

).

•  The furnace must be kept free and clear of insulating 

material. Examine the furnace area when the furnace is 

installed or when insulation is added. Insulating material 

may be combustible.

Applications

MG1 series gas furnaces are classified as a Category 
I (Catégorie I) appliance  and listed as a direct vent 

(sealed combustion), downflow heating appliance for 

manufactured (mobile) homes and recreational vehicles. 

The furnace must be located so that venting can be 

properly achieved.
Air conditioning may be added to structures with MG1 

series furnaces using air conditioning or conventional 

units. This Installation Instruction manual includes 

special requirements for incorporation of air conditioning 

equipment to the MG1 furnaces.

Unit Location

•  The furnace shall be appropriately located to the supply 

and return air distribution system (

page 7

). Sides and 

back of the furnace may be enclosed by wall framing. 

See Minimum Clearances section on 

page 6

.

•  The furnace installation is only intended for free air return 

through the furnace door louvers. DO NOT connect a 

ducted return air system directly to the furnace. Improper 

installation may create a hazard and damage equipment, 

as well as void all warranties.

•  Furnace may be installed on combustible flooring when 

using manufacturer approved duct connectors. See 

page 7

.

•  When installed in a residential garage, the furnace must 

be positioned so the burners and the source of the 

ignition are located no less than 18 inches above the 

floor and protected from physical damage by vehicles.

Summary of Contents for MG1 Series

Page 1: ...ier call the fire department QUE FAIRE S IL Y A UNE ODEUR DE GAZ N essayez d allumer aucun appareil Ne touchez aucun interrupteur lectrique n utilisez aucun t l phone dans le b timent vacuez l immeubl...

Page 2: ...nversion to Propane LP Gas 19 Atmospheric Direct Ignition Furnaces 19 Measuring the Supply Gas Pressure 19 Measuring the Manifold Pressure 19 STARTUP ADJUSTMENTS 20 Operating Instructions Direct Ignit...

Page 3: ...pendant l installation l entretien et le fonctionnement de cette fournaise Le non respect des recommandations de s curit peut causer des dommages l quipement ou des blessures graves voire mortelles A...

Page 4: ...ANSI NFPA 70 CANADA Canadian Electrical Code CSA C22 1 Gas Piping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes CANADA NSCNGPIC General Installation US Current edition of the NFGC and...

Page 5: ...sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide min 250 sq in 1613 cm open free area in front or side...

Page 6: ...e a louvered door with a minimum of 250 in2 free area with the openings in the closet door in line with the louvered openings in the furnace door A fully louvered closet door may be used See Circulati...

Page 7: ...ode ANSI C1 NFPA 70 Gaspipingisnotruninorthroughthereturnductsystem CAUTION HAZARDOFASPHYXIATION Negativepressure inside the closet with closet door closed and the furnace blower operating on high spe...

Page 8: ...1 7 8 2 7 8 C L Figure 7 Cut Out Dimensions for Round Duct Connectors Bend tabs up 90 Mounting Plate Duct Connector Connector Tabs Supply Air Duct Hole for Gas Line Wood Floor Figure 8 Standard Duct...

Page 9: ...to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 8 For round ducts see Figure 7 page 8 1 Measure 10 from the rear wall or alcove and mark the centerline...

Page 10: ...ector and the mounting plate to the wood floor with appropriate size screws 5 Connect the round supply duct to the underside of the duct connector and secure them with field supplied sheet metal screw...

Page 11: ...ING F S AW1523 0 2 4 A S 15 23 F S AW2135 0 2 4 A S 21 35 F S AW2747 0 2 4 A S 27 47 F S AW3563 0 2 4 A S 35 63 F S AW5195 0 2 4 A S 51 95 NOTE Not all models are available Check with your local distr...

Page 12: ...ough the opening cut on the roof 3 Connect inner flue pipe to vent collar of the furnace See Figure 22 4 Connectcombustionairpipetofurnacecollarwithsheet metal screw See Figure 22 NOTES Itisrecommende...

Page 13: ...stallations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes It is recommended that 115VAC line voltage be supplied to the f...

Page 14: ...unless the polarity and ground are properly connected as shown in Figure 25 and Figure 26 page 14 ForinstallationofA sizeCabinetfurnaces allowsufficient slack in the wiring if an optional cooling coi...

Page 15: ...Specifications Thermostat Wire Gauge FURNACE MODEL NUMBER FURNACE INPUT BTUH CABINET WIDTH IN NOMINAL ELECTRICAL SUPPLY MINIMUM OPERATING VOLTAGE MAXIMUM OPERATING VOLTAGE MAXIMUM FURNACE AMPERES MAXI...

Page 16: ...follow all safety warnings could result in serious injury death or property damage This furnace may be installed with left right or bottom gas entry Whenconnectingthegassupply provideclearance between...

Page 17: ...60HZ 30 vac Normal Anticipator Setting 0 4 Manifold Pressure for Natural Gas 3 5 w c Manifold Pressure for LP Gas 10 w c AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissement...

Page 18: ...e explosion carbon monoxide poisoning personal injury or death High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas The installation of this...

Page 19: ...Pressure To obtain an accurate pressure reading turn off all gas appliances i e Dryers water heaters stoves etc at their ON OFF control or individual gas valves 1 Remove the inlet pressure plug from t...

Page 20: ...ace in service it must be checkedtoensureitisequippedforthetypeofgas being used The burner flame must be observed andadjustedifnecessary Failuretoobservethis cautionmayresultinunsafeoperation explosio...

Page 21: ...supplier See page 19 Verifying Adjusting Temperature Rise Confirm the temperature rise through the furnace is within the limits specified on the furnace rating plate Any temperature rise outside the...

Page 22: ...to the furnace before shutting off the electrical supply 7 When call for heat is satisfied the thermostat contacts open thegasvalveshutsoffgasflowandthecombustion blower remains on for a 30 45 second...

Page 23: ...gnitortipforflamerectification Misalignedignitordoesnotallowflametocontactignitor tip for flame rectification Burner Short Cycling Thermostat Calls for Heat Limit Switches Closed Check for polarity Ch...

Page 24: ...h Inspect the combustion chamber blower compartment flue collar and Roof Jack Check the gas valve if applicable and fuel line connections for leaks Make any adjustments necessary for good operation WA...

Page 25: ...439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 16...

Page 26: ...27 24 Service Orifice Size Table 13 High Altitude Deration Chart for Natural Gas Low Heating Value Table 11 Natural Gas Heating Values LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE ABOVE SEA LEVEL BTU...

Page 27: ...115V N C L R GROUND SCREW GROUND SCREW GAS VALVE NEUTRAL L1 WIRE NUTS SUPPLIED BY INSTALLER 1 2 3 4 5 N L C G ECM BLOWER MOTOR G W Y R C CONTROL LIGHTS 1 2 1 2 BLACK BLACK 1 2 3 4 5 6 1 2 3 4 5 6 MOTO...

Page 28: ...Gas valve De energized when it should be Energized Rapid Flash Reverse Polarity Continuous On Normal Operation Flash codes stored in memory auto erased after 14 days Flash codes NOT stored in memory...

Page 29: ...79 53 2 Med Low 996 57 960 59 924 62 885 64 848 67 1 Low MG1E 090F1AAM1 MODEL NAME HEATING INPUT MOTOR SPEED EXTERNAL STATIC PRESSURE IN W C 0 1 0 2 0 3 0 4 0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM...

Page 30: ...6 0 7 0 8 CFM CFM CFM CFM CFM CFM CFM CFM MG1E 077F1AAM1 77 000 BTU Hr 5 High 1 573 1 541 1 511 1 479 1 452 1 419 1 388 1 358 4 Alternate 1 333 1 300 1 268 1 236 1 201 1 162 1 129 1 093 3 Med High 1 2...

Page 31: ...31...

Page 32: ...Literature Package been left with the unit YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict...

Reviews: