7
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide poisoning
that could result in personal injury or death.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the floor or platform.
Circulating air ductwork must not be connected
to any other heat producing device such as a
fireplace insert, stove, etc. This may result in fire,
explosion, carbon monoxide poisoning, personal
injury, or property damage.
Return Air
U.S.A. home manufacturers shall comply with all of the
following conditions to have acceptable return air systems
for closet installed forced air heating appliances:
• The return air opening into the closet shall not be less
than specified in the appliance’s listing.
• The cross-sectional area of the return duct system
leading into the closet, when located in the floor or
ceiling shall not be less than 235 in
2
.
CAUTION:
HAZARD OF ASPHYXIATION: Do not cover or
restrict return air opening.
• Means shall be provided that prevent inadvertent closure
of flat objects placed over the return air opening located
in the floor of the closet (versus the vertical front or side
wall).
• The total free area of openings in the floor or ceiling
registers serving the return air duct system must be at
least 235 in
2
. At least one register should be located
where it is not likely to be covered by carpeting, boxes
and other objects.
• Materials located in the return duct system must have a
flame spread classification of 200 or less. This includes
a closet door if the furnace is in a closet.
• Noncombustible pans having 1” upturned flanges are
located beneath openings in a floor duct system.
• Wiring materials located in the return duct system shall
conform to Articles 300-22 of the National Electrical
Code (ANSI C1/NFPA-70).
• Gas piping is not run in or through the return duct system.
CAUTION:
HAZARD OF ASPHYXIATION: Negative pressure
inside the closet, with closet door closed and
the furnace blower operating on high speed,
shall be no more negative than minus 0.05 inch
water column.
• Test the negative pressure in the closet with the air-
circulating fan operating at high speed and the closet
closed. The negative pressure is to be no more negative
than minus 0.05 inch water column.
• Air conditioning systems may require more duct register
and open louver area to obtain necessary airflow.
Supply Air
For proper air distribution, the supply duct system must be
designed so that the static pressure measured external
to the furnace does not exceed the listed static pressure
rating shown on the furnace rating plate.
Location, size, and number of registers should be selected
on the basis of best air distribution and floor plan of
the home.
The supply air must be delivered to the
conditioned space by duct(s) secured to the furnace
casing, running full size and without interruption.
Three typical distribution systems are shown in
FURNACE INSTALLATION
NOTE:
These Installation procedures are suggested for
typical furnace installations. Since each installation is
different, the sequence of instructions may differ from
the actual installation. Only qualified HVAC technicians
should install this furnace.
The installer must be familiar with and comply with all
codes and regulations applicable to the installation of
these heating appliances and related equipment. In
the absence of local codes, the installation must be in
accordance with the current provisions of one or more of
the following standards.
• Federal Manufactured Home Constructions & Safety
Standard (H.U.D. Title 24, Part 3280.707[a][2])
• American National Standard (ANSI-119.2/NFPA-501C)
for all recreational vehicle installations.
• American National Standard (ANSI-Z223.1/NFPA-54)
and/or CAN/CSA B149 for all gas-fired furnace models.
• American National Standard (ANSI-Z95.1/NFPA-31)
and/or CSA B139 for all oil-fired furnace models.
Figure 5. Typical Supply Duct System
A Single trunk duct
B Dual trunk duct
w/crossover connector
C
Transition duct
w/branches
Summary of Contents for MG1 Series
Page 31: ...31...