Approved H9HK heater kits are shipped ready to install using 

single or dual circuit electrical supply and existing factory 

installed terminal blocks. If dual circuit supply is desired, 

follow instructions included under Multiple Branch Circuit 

Electrical Connections section.
NOTE: Use of the 3 pole terminal block found in the main 

control panel is for the unit's refrigerant cooling circuit only. 

This circuit includes:

• Compressors

•  Blower motors

•  OD fan motors

•  Low Voltage transformer (all unit electrical loads)

Circuit Options

P7TQ units installed with electric heat may be wired for single 

or multiple circuit supply connections.

Single Branch Circuit Electrical Connection

Units are factory ready for addition of H9HK heater kits. See 

unit rating label or 

Table 4 (page 7)

 for single point power 

circuit Minimum Circuit Ampacity (MCA) and Maximum Over-

Current Protection of branch circuit wiring.
Field wiring will be routed from the branch circuit disconnect 

to this 3 pole terminal block for both heating and cooling 

operation.

Multiple Branch Circuit Electrical Connection

For Dual Point Power Circuit connections see the unit rating 

plate or electrical data in 

Table 5 (page 8)

 for proper high 

voltage branch circuit requirements. Both 3 pole terminal 

blocks provided in the unit will be used for converting to dual 

supply connections.
The 3 pole terminal block located in the electric heat vestibule 

is for connection of the electric heater kit branch circuit wiring. 

Field wiring will be routed from the electric heat branch circuit 

disconnect to this 3 pole terminal block for heating operation.
The factory supplied red, yellow, and black wires connected 

to the electric heat terminal block from the main unit 3 pole 

terminal block must be removed. These 3 wires (if long enough) 

may be used for connection between the unit main control 

panel 3 pole terminal block and the second branch circuit 

power supply disconnect for cooling and blower operation. 

See 

Figure 13 (page 9)

.

Circuit Breakers

If circuit breakers are used for any circuit, they must be 

used for all electric heat circuits. Use one breaker for each 

circuit. See 

Table 3, (page 6)

. If circuit breakers are not 

being used, proceed to the Heat Kit Installation section on 

page 4

.

IMPORTANT NOTE:

Circuit breakers (if installed) in the unit with the addition 

of heater kits are for short circuit protection of the internal 

heater element circuit wiring and DO NOT serve as a 

unit disconnect. The circuit breakers DO NOT provide 

over-current protection of the supply wiring.
•  Whether or not circuit breakers are used in the units, 

protection and disconnect requirements. 

NOTE:  If any of 

the original wiring supplied with the unit must be replaced, 

it must be replaced with material of the same gauge and 

temperature rating.

Clearances to Combustibles

All units are approved for zero clearance to combustibles when 

installed according to these instructions and other instructions 

included with the unit and other approved accessories.

Wiring Diagrams

Wiring Diagrams are shipped with each H9HK heater kit 

assembly. Attach the heater kit wiring diagram label over the 

bottom half of Sheet #2 of the unit wiring diagram label on 

the control panel access door. For proper adherence, make 

sure the surface is clean and free of oil before applying.

Clearances

All H9HK electric heater kits are approved for use in 

installations with zero-clearance to combustibles at any blower 

speed allowed on the units blower performance charts for 

both Horizontal and Downflow applications when installed 

according to these instructions and other instructions included 

with the unit and other approved accessories. See note (in 

bold type) for vertical duct applications in Heat Kit Installation 

section on 

page 4

.

ELECTRICAL SUPPLY

All wiring must comply with the current revision of the National 

Electric Code and must be sized for the minimum ampacities 

as listed on the unit data label or in 

Table 1

. Refer to the 

detailed wiring diagrams for proper connections:

 

Figure 13

Figure 14

Figure 15

,

 

Figure 16

,

 

Figure 17

Figure 18

, and 

Figure 19

.

If the unit was previously installed without electric heat, the 

existing supply wiring may not be sufficient to handle the 

increased load. See the unit rating label or 

Table 4 (page 

7)

 or 

Table 5 (page 8)

 for minimum circuit ampacities 

and maximum overcurrent protection ratings.

Installation Preparations

Before proceeding with the electrical connections, make sure 

that the voltage, frequency, and phase of the supply source 

are the same as those specified on the unit rating label. Also 

verify that the service provided by the utility is sufficient to 

handle the additional load imposed by this equipment.

Terminal Blocks

Table 1. Heater Kits and Part Numbers

HEATER

KITS

DESCRIPTION

PART

NUMBER

3 PHASE

208/240V

H9HK009Q-01 (9kw)

1011669

H9HK018Q-11 (18kw)

1011672

H9HK030Q-21 (30kw)

1011675

H9HK035Q-21 (35kw)

1011678

3 PHASE

480V

H9HK009S-01 (9kw)

1011670

H9HK018S-01 (18kw)

1011673

H9HK030S-01 (30kw)

1011676

H9HK035S-01 (35kw)

1011679

3

CP-H9HK (05-20) 1012566-B

Summary of Contents for 1011669

Page 1: ...with these instructions and with all applicable national and local codes and standards Please read all instructions carefully before starting the installation Return these instructions to the customer...

Page 2: ...ons are primarily intended to assist qualified individuals experienced in the properinstallationofthesecomponents Somelocalcodes may require licensed installation service personnel for this type of eq...

Page 3: ...and DO NOT serve as a unit disconnect The circuit breakers DO NOT provide over current protection of the supply wiring Whether or not circuit breakers are used in the units protection and disconnect...

Page 4: ...supply grille 1 Remove Compressor Access panel See Figure 2 foam wire guards for later use See 4 Install the DIN rail mounting bracket inside of the unit and tightly secure it with two screws See NOT...

Page 5: ...m flange of the element mounting plate to the bottom pan and then one in the rear of the element assembly support bracket as shown in and 11 Route all wiring out the two wire passage holes and foam wi...

Page 6: ...0Q 21 1011675 2 Figure 18 210 F 35 H9HK035Q 21 1011678 2 Figure 18 210 F 6 7 5 10 and 12 5 ton 460V 3PH P7TQ 072 090 120 150 D 9 H9HK009S 01 1011670 NONE Figure 15 155 F 18 H9HK018S 01 1011673 NONE Fi...

Page 7: ...49 4 58 5 30 35 50 60 UNIT EQUIPPED WITH 3 HP 2 SPEED MOTOR HEATER KIT 3 HP 2 SPEED MOTOR HEATER KIT POWER EXHAUST COOLING TONNAGE UNIT VOLTAGE MCA MOP MCA MOP 9 KW 18 KW 30 KW 35 KW 9 KW 18 KW 30 KW...

Page 8: ...7 40 31 7 40 31 7 40 31 7 40 14 9 15 27 1 30 43 3 45 52 3 60 HIGH STATIC DRIVE OPTIONAL 3 HP ECM MOTOR 6 208 240 33 7 50 33 7 50 33 7 50 33 7 50 23 5 27 1 30 30 45 4 52 3 50 60 75 0 86 6 80 90 90 7 1...

Page 9: ...POWER SUPPLY L1 L2 L3 To Cooling Circuit Power Supply Disconnect Main Control Panel 3 Pole Terminal Block To Cooling Components and Control L1 L2 L3 L1 L2 L3 Electric Heat 3 Pole Terminal Block Elect...

Page 10: ...BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1...

Page 11: ...T BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS...

Page 12: ...OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012105A Replaces 10121050 05 17 18 kW 1 Stage 20...

Page 13: ...RING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012106A Replaces 10...

Page 14: ...HE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012108A Replaces 10121080 05 17 30 35 kW 1 Stage 208...

Page 15: ...THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012109A Replaces 10121090 05 17 30 35 kW 1 Stage 48...

Page 16: ...HESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER Specifications and illustrations subject to change without notice or incurring obligations 2020 Nortek Global HVAC LLC O Fallon MO All rights reserved...

Reviews: