Copyright
©
2017 Nortek Security & Control LLC
13
System Menu
The SYSTEM menu is used to setup the thermostat for the correct HVAC system type. The following
setup op ons will be displayed in the text line:
• HVAC System Type: Standard Gas/Electric or Heat Pump
• Fan Type: Gas Hea ng or Electric Hea ng
• Changeover Valve Type (for Heat Pump Systems): Changeover with Cooling or with Hea ng.
To select op ons:
• Use the
bu ons to scroll to the desired se ng.
• Press
SELECT
to change a se ng. The current se ng for that selec on will be
fl
ashing.
• Change the op on with the
bu ons.
• When the desired op on has been selected, Press
SELECT
again to save it.
• Then press
DONE
to exit.
System Type
• For Standard Gas/Electric systems, select
STANDARD
This is the default se ng.
• For Heat Pump systems, press the
bu ons to change to
HEAT PUMP
• Press
SELECT
to set.
• Press
DONE
to exit.
Fan Type (For Standard HVAC systems only)
Fan type depends on the hea ng system type.
• For Gas heat: select
GAS
. This is the default se ng.
• For Electric heat: press the
bu ons to change to
ELECTRIC
.
• Press
SELECT
to set.
• Press
DONE
to exit.
Changeover Type (For Heat Pump HVAC Systems Only)
The changeover (or reversing) valve is used to change from hea ng to cooling opera on. The HVAC
system is either a Changeover with Cooling type (O) or Changeover with Hea ng type (B). Most are
changeover with cooling, which is the default se ng.
• For Changeover with Cooling systems, select
WITH COOL
. This is the default se ng.
• For Changeover with Hea ng systems, use the
bu ons to change to
WITH HEAT
.
• Press
Select
to set.
• Press
Done
to exit.
Not sure what type Changeover system? Check the exis ng thermostat connec ons to help
determine this. If the original system had an orange wire connected to an “O” terminal, then this is a
“changeover with cool” system. If there was a brown wire connected to a “B” terminal, then this is a
“change over with heat” system. Set the Changeover se ng accordingly.
NOTE:
If heating comes on when cooling is expected or vice versa, switch the “Changeover
Type” to the opposite setting.