Start Up |
26
RH Pre-Start Up Checklist
Unit Serial #: _________________ No. of humidifiers: _______ Tag: _______________
Unit type: _______ __________
Voltage: ________V/_____ph
Cylinder type:
Customer/Job:
Address:
WATER QUALITY:
Well
water
F
City water
F
Softened water
F
HUMIDIFIER MOUNTING: (Clearances around the unit Acceptable Obstruction)
•
Level
Front Clearance 36 in.
F
STEAM LINE(S):
•
Material
F
Diameter / Size
F
•
Slope up (min 2 in/ft)
F
Slope down (min 0.500 in/ft)
F
•
Low point condensate traps
F
No hose kinks / Restrictions
F
•
Type of Insulation
CONDENSATE LINE(S):
•
P Trap min 6 in or duct press + 2in
F
P Trap min 12 in drop
F
WATER LINE:
•
1/2 in to within 4ft of unit
F
Water pressure: 30-80 psig
F
DRAIN LINE:
•
Air gap within 3 ft of the unit
F
Diameter / Size
F
CYLINDER:
•
Seated in drain valve and secured
yes
F
no
F
WIRING:
•
Wiring connections and connectors secured
yes
F
no
F
CONTROLS:
•
On / Off / Security loop devices working correctly
yes
F
no
F
•
Jumper J10 set to
Modulating (removed)
F
Or
On/Off (installed)
F
•
Control Location
•
High Limit Location
POWER:
•
Voltage, amp, fuse per Spec Label:
yes
F
no
F
•
Disconnect switch located close to humidifier
yes
F
no
F
•
Panel Number
Inspected by:
Date of inspection: ______/_______/______
Company:
Summary of Contents for RH
Page 7: ...Introduction 4 ...
Page 9: ...Installation 6 Typical RH Installation Figure 3 Typical Humidifier Installation ...
Page 20: ...17 Installation Modulating Control Wiring Figure 18 Modulating Controls ...
Page 21: ...Installation 18 Figure 19 Modulating Control Wiring Figure 20 Duct Sensor Wiring ...
Page 31: ...Start Up 28 ...
Page 36: ...33 Operation Humidifier Schematic Figure 28 Humidifier Schematic ...
Page 55: ...Spare Parts 52 Exploded View and Spare Parts List ...
Page 56: ...53 Spare Parts RH Spare Parts Figure 37 RH Spare parts ...
Page 58: ...55 Warranty ...