7 |
Installation
Location
Mount on a suitable wall or vertical surface. Do not sit the on the floor to allow clearances
required for plumbing and electrical connections. Clearance dimensions shown are for
reference only and are the minimum required for maintenance of the humidifier. Consult local
and national codes before final location and installation. Nortec does not accept responsibility
for installation code violations.
•
Install only in areas with ambient temperature 41-104°F (5 – 40°C) relative humidity
5 - 95%.
•
When possible install below the steam distributor. If mounted above the steam distributor
take care to provide proper steam line routing and proper condensate traps.
•
DO NOT locate the humidifier any further then absolutely necessary from the steam
distributor location as net output will be reduced as a result of heat loss through the steam
line.
•
When possible, mount the RH humidifier at a height convenient for servicing.
Figure 4: Mounting Location / Clearance
Note:
Do not mount on hot surfaces, where freezing can occur, vibrating surface, or
floor.
Side clearance
for space models
only, see table
36 in. (92 cm)
in. ront learance
duct model
m
f
c
Additional front clearance
for space models,
see table
24 in.(61 cm)
Min Height
Mount Humidifier
Level
As Close as
Possible to Steam
Distributor
5-95%
Overhead clearance
for space models
only, see table
Humidifier Output lb (kg)
Side in. (cm)
<4 (1.8)
12 (30)
12 (30)
6 (2.7)
16 (40)
18 (46)
8 (3.6)
18 (46)
18 (46)
7 ft (2.1 m)
min. Height
for space
models only.
36 (92)
42 (107)
48 (120)
Additional Clearance for Space Models Only
Overhead in. (cm)
Front in. (cm)
Summary of Contents for RH
Page 7: ...Introduction 4 ...
Page 9: ...Installation 6 Typical RH Installation Figure 3 Typical Humidifier Installation ...
Page 20: ...17 Installation Modulating Control Wiring Figure 18 Modulating Controls ...
Page 21: ...Installation 18 Figure 19 Modulating Control Wiring Figure 20 Duct Sensor Wiring ...
Page 31: ...Start Up 28 ...
Page 36: ...33 Operation Humidifier Schematic Figure 28 Humidifier Schematic ...
Page 55: ...Spare Parts 52 Exploded View and Spare Parts List ...
Page 56: ...53 Spare Parts RH Spare Parts Figure 37 RH Spare parts ...
Page 58: ...55 Warranty ...