Circulation pump
1
Circulation pump
2
(if necessary
)
Relief valve
Hot water
supply points
Hot water supply line
Hot water return lin
e
Cold water supply pipe *1
When installing 2 pumps in parallel
Select the "pump rotation" is active (Refer to page 10 or page 23).
* Size the cold water supply piping to allow for maximum flow rates of the building.
* Be sure to connect the cold water supply pipe between the hot water storage tank and intake side of the storage tank circulation pump.
Thermostat
System Controller
Remote controller cord
Remote Controller
Remote Controller Cord
Unit
1
Unit
2
Unit
3
Unit 10
Unit 11
Unit 12
(copper or stainless steel pipe)
Hot water storage tank
(copper or stainless steel pipe)
Return line circulation pump
(Size for max. flow
)
(Size for max. flow
)
Storage tank supply line (copper or stainless steel pipe)
Storage tank return line (copper or stainless steel pipe)
Remote Controller
Cor
d
If "Pump error check" is active(Refer to page 12 or page 23),connecting these wires to system controller.
*
NWC-ADAPTER (NAW-1 US)
Pump Control Wires (use external relays)
Example of Installation with a Storage Tank and Recirculation System (Tank recirculation system)
The pump will push water through the Multi-unit System to heat up the tank.
When the temperature of the thermostat is high, the system controller will turn off the pump until
the temperature cools down.
*
For the set temperature of the remote controller
, use the temperature (of the thermostat) + about 10°F
.
*
To achieve the highest recovery
, size the storage tank circulation pump for maximum capacity
.
(9 GPM (each) @ 40 ft. of head (160°F setting or less) + piping losses through the system.)
Verify the supply pressure to the units is at least 30 PSI.