VS18/VS26
MAINTENANCE & INSTRUCTION BOOKLET
8.3.3 DeviceNet address and baud rate setting
The VS18/VS26 DeviceNet valve island address can be set within the range 0 to 63, set by
using the address selector switches accessible by removing the securing screw and lifting the
hinged cover of the address switches. The two rotary switches allow an address range of 0 to
63. The valve island needs a power reset to accept a new address. When position 64 is
selected the address may be set through software via a capable DeviceNet master.
Default address = 63
Following are VS18/VS26 DeviceNet baud rates, which are detected automatically:
125 kBit/s
250 kBit/s
500 kBit/s
8.3.4 DeviceNet output addressing
Data byte_0
Data byte_1
Data byte_2
Data byte_3
Valve no.
¨
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16
Solenoid
14
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Data bits
Solenoid
12
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Solenoids 14
Solenoids 12
Valve no.