background image

13

After refrigerant line connections are completed, it is 
required that you leak check and evacuate the indoor 
section and all line connections (using proper methods) 
before fi nalizing the full system refrigerant charge. For 
fi nal charges based on matched systems and specifi ed 
line lengths, see physical and electrical specifi cations 
(Table 4, page 15).
•  To achieve rated capacity and effi ciency, the compressor 

must be exposed to refrigerant for at least 24 hours 
prior to running and then the compressor must be run 
for a minimum of 12 hours.

•  Cooling mode charging charts are applicable only to 

matched assemblies of NORDYNE equipment and 
listed airfl ows for the indoor coil. T5BP outdoor units 
with indoor coils not listed are not recommended 
and deviations from rated airfl ows or non-listed 
combinations may require modifi cation to the expansion 
device and refrigerant charging procedures for proper 
and effi cient system operation. Refer to Figure 8 for 
7.5 ton units or Figure 9 for 10 ton units (page 19).

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the 
outdoor unit. Use only gage line sets which have 
a “Schrader” depression device present to actuate 
the valve. A common suction port for heating mode 
charging is included and located on the compressor 
access panel above the outdoor unit service valves.

•  Heat mode verifi cation charts are provided for quick 

reference when the unit is in heating mode and for the 
inspection of the liquid line pressures and temperatures. 
Refer to Figure 10 for 7.5 ton units or Figure 11 for 10 
ton units (page 21).

Charging an R410A system in AC mode at outdoor 
temperatures above 55° F for optimized sub-cooling of 
10° F to 12° F.
1.  With the system operating at steady-state, measure 

the liquid refrigerant pressure (in PSIG) at the outdoor 
unit service valve.

2.  Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3.  Determine the required liquid refrigerant pressure 

from the appropriate charging chart (Figures 8 or 9).

• If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined in 
Step 3, then there is too much charge in the system. 
Remove refrigerant and repeat Steps 1 through 3 
until the system is correctly charged.

• If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 
Step 3, there is too little charge in the system. Add 
refrigerant and repeat Steps 1 through 3 until the 
system is correctly charged.

HEAT PUMP MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 
death, disconnect all electrical power to the unit 
before performing any maintenance or service. 
The unit may have more than one electrical 
supply.

Proper maintenance is important to achieve optimum 
performance from the heat pump. The ability to properly 
perform maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess these 
skills, contact your dealer for maintenance. Consult your 
local dealer about the availability of maintenance contracts. 
Routine maintenance should include the following:
•  Inspect and clean or replace air fi lters at the beginning 

of each heating and cooling season, or more frequently 
if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 
Clean the outdoor coil and louvers as necessary using 
a mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 
as necessary.

 CAUTION:

The unit should never be operated without a 
fi lter in the return air system. Replace disposable 
fi lters with the same type and size.

•  Do not attempt to add additional oil to motors 

unequipped with oil tubes. The compressor is 
hermetically sealed at the factory and does not require 
lubrication.

REPLACEMENT PARTS

Replacement parts are available through all Nordyne distributors. 
Please have the complete model and serial number of the unit 
when ordering replacement parts.

ELECTRICAL:

Capacitors

Temperature Limit Switches

Compressors

Thermostats

Contactors

Time Delay Relays

Pressure Switches

Transformers

Relays

MOTORS:

Blower Motor

Fan Motor

COMPONENTS:

Blower Assembly

Fan Grille

Cabinet Panels

Filter/Driers

Expansion Valves

Summary of Contents for T5BP 090C

Page 1: ...nate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes req...

Page 2: ...2...

Page 3: ...enance 13 Replacement Parts 13 Component Functions 14 Figures Tables 14 Figure 5 T5BP Heat Pump Dimensions 14 Table 3 Unit Dimensions Shipping Weights 14 Electrical Information 15 Table 4 Electrical S...

Page 4: ...de to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Set the temperature selector to the desired temperature level The outdoor fan compressor and blower motor will all cycle on and off to...

Page 5: ...al power to the unit is turned on WARRANTY INFORMATION A warranty certificate with full details is included with the heat pump Carefully review these responsibilities with your dealer or service compa...

Page 6: ...refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified in...

Page 7: ...econsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine th...

Page 8: ...required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces A filter dryer is provided with the unit and must be installedintheliquidlineo...

Page 9: ...sk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Label all wir...

Page 10: ...mostats can be used withthisequipmentdependingonoptionalaccessories i e economizer installed with the unit Select a thermostatthatoperatesinconjunctionwiththeinstalled accessories A typical commercial...

Page 11: ...ch from delay to no delay remove the pin from the delay pin location and move it to the no delay pin location Scroll compressors that have noise issues while going into or coming out of defrost should...

Page 12: ...outdoor unit remains de energized 3 After approximately 5 minutes verify the compressor andfanenergizeandthetemperatureofthedischarge air is cooler than the room temperature System Cooling 1 Set the...

Page 13: ...d in Step 1 is greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is corr...

Page 14: ...low 6 Minimum Clearance FIGURES TABLES Model Number T5BP Unit Weights Lbs Height H Width W Depth D Shipping Height Without Packaging Shipping Weight All dimensions in inches 090C 390 424 44 1 4 37 1 2...

Page 15: ...1 7 Fan Blade Diameter Pitch Blades 30 22 3 30 22 3 30 26 3 30 26 3 RPM CFM Max Total 850 7 200 850 7 200 850 8 000 850 8 000 PHYSICAL DATA REFRIGERANT SPECS Outdoor Coil Assembly 1 ea 1 ea 1 ea 1 ea...

Page 16: ...r run time is accumulated Opening of DFT during defrost or interval period resets the interval to 0 5 Ground on location provided inside compressor terminal box CC Contactor Coil CCH Crankcase Heat DF...

Page 17: ...ED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT SEE NOTE 1 SEE NOTE 2 SEE NOTE 4 SEE NOTE 5 SEE NOTE 3 G Y E R O B W...

Page 18: ...or a variety of indoor return air conditions and are most influenced by the outdoor ambient temperature outdoor fan operation and the unit operating voltage Before using these charts make sure the uni...

Page 19: ...efrigerant when above curve Add refrigerant when below curve Figure 8 Charging Chart for 7 5 Ton Units Figure 9 Charging Chart for 10 Ton Units Liquid Temperature F Liquid Pressure psig 175 200 225 25...

Page 20: ...n the charge to the amount shown on the rating label However if an inspection with these verification charts does not line up with the values shown and the ambient temperature is above 50 F then a mor...

Page 21: ...e psig T5BP 120 Heat Mode Verification Chart 80 ID Rtn 70 ID Rtn 60 ID Rtn 62 OD Amb 47 OD Amb 17 OD Amb Figure 10 Verification Chart for 7 1 2 ton units Liquid Temperature F Liquid Pressure psig T5BP...

Page 22: ...22...

Page 23: ...23...

Page 24: ...___________________________ UnitInstalledMinimumclearancesper Figure 2 page 7 YES NO INSTALLER NAME CITY _______________________ STATE ________________ ELECTRICAL SYSTEM Electrical connections tight Y...

Reviews: