•  All gas piping must be installed in compliance with 

local codes and utility regulations. In the absence 
of local codes the gas line installation must comply 
with the latest edition of the National Fuel Gas Code 
(ANSI Z223.1) or (CAN/CGA B149.1 or .2) Installation 
Codes.

•  Some local regulations require the installation 

of a manual main shut-off valve and ground joint 
union external to the furnace as shown in Figure 13 
(page 17). The shut-off valve should be readily 
accessible for service and/or emergency use. 
Consult the local utility or gas supplier for 
additional requirements regarding placement of the 
manual main gas shut-off.

•  Gas piping must never run in or through air ducts, 

chimneys, gas vents, or elevator shafts.

•  Compounds used on threaded joints of gas piping 

must be resistant to the actions of LP propane gas.

•  The main gas valve and main power disconnect to 

the furnace must be properly labeled by the installer 
in case emergency shutdown is required.

•  Flexible gas connectors are not recommended for 

this type of furnace but may be used if allowed by 
local jurisdiction. Only new fl exible  connectors 
may be used. Do not use a connector which has 
previously serviced another gas appliance.

•  A drip leg should be installed in the vertical pipe 

run to the unit (Figure 13).

Table 7 (page 31) lists gas pipe capacities for standard 
pipe sizes as a function of length in typical applications 
based on nominal pressure drop in the line.

The furnace may be installed for either left or right side gas 
entry. When connecting the gas supply, provide clearance 
between the gas supply line and the entry hole in the 
furnace casing to avoid unwanted noise and/or damage to 
the furnace. Typical gas hookups are shown in Figure 13.

Leak Check

GAS SUPPLY & PIPING

FIRE OR EXPLOSION HAZARD

• Failure to follow safety warnings exactly 

could result in serious injury or property 
damage.

• Installation and service must be performed 

by a qualifi ed installer, service agency or 
the gas supplier.

• Do not store or use gasoline or other 

fl ammable vapors and liquids in the 
vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not 

use any phone in your building.

• Leave the building immediately.
• Immediately call your gas supplier from 

a neighbor’s phone. Follow the gas 
supplier’s instructions.

• If you cannot reach your gas supplier, call 

the fi re department.

 WARNING:

RISQUE D’INCENDIE OU D’ EXPLOSION

•  Le non-respect des avertissements de sécurité 

pourrait entraîner des blessures graves, la mort 
ou des dommages matériels.

•  L’installation et l’entretien doivent être effectués 

par un installateur qualifié, un organisme de 
service ou le fournisseur de gazstaller, service 
agency or the gas supplier.

•  Ne pas entreposer ni utiliser de l’essence ni 

d’autres vapeurs ou liquides infl ammables dans le 
voisinage de cet appareil, ni de tout autre appareil.

QUE FAIRE S’IL Y A UNE ODEUR DE GAZ

•  Ne pas tenter d’allumer aucun appareil.
•  Ne toucher à aucun interrupteur électrique; 

n’utiliser aucun téléphone dans le bâtiment.

•  Évacuer l’immeuble immédiatement.
•  Appeler immédiatement le fournisseur de gaz en 

employant le téléphone d’un voisin. Respecter à 
la lettre les instructions du fournisseur de gaz.

•  Si personne ne répond, appeler le service des 

incendies.

 AVERTISSEMENT:

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could 
result in serious injury or property damage.

Never test for gas leaks with an open fl ame. 
Use a commercially available soap solution 
made specifi cally for the detection of leaks 
to check all connections. A fi re or explosion 
may result causing property damage, personal 
injury or loss of life.

 WARNING:

Summary of Contents for *SA Upfl ow / Horizontal

Page 1: ...upplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des bless...

Page 2: ...r Connections 11 Upflow Horizontal Furnaces 11 Side Return Installations 11 Bottom Return Installations 12 Downflow Furnaces 12 Acoustical Treatments 12 FURNACE INSTALLATION 12 General Requirements 12...

Page 3: ...ry or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code NFPA54 ANSI Z223 1 or the Na...

Page 4: ...ermostat The installation must include a properly installed filter in the return air system with no by pass air The filter must be inspected frequently and replaced when necessary Combustion air must...

Page 5: ...opane Installation Codes NSCNGPIC Venting Systems and Air Supply for Appliances Duct Systems US and CANADA Air Conditioning Contractors Association ACCA Manual D Sheet Metal and Air Conditioning Contr...

Page 6: ...n vacuent correctement tel que prescrit ci dessus rouvrir les portes et les fen tres et remettre les ventilateurs d vacuation les registres de foyers et tout autre appareil fonctionnant au gaz leur ta...

Page 7: ...air from that space Furnaceclosets smallequipmentroomsandgaragesare confined spaces Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from...

Page 8: ...or Wall 12 Max 12 Max Furnace NOTE Each opening to outside must be at least 1 sq in per 4 000 Btuh of total input rating Vent or Chimney Water Heater See Note Total Input Rating Btuh Minimum Free Area...

Page 9: ...ve pressure draft and must be vented vertically or near vertical Additionally it is important to guard against excessive condensation WARNING Upon completion of the furnace installation carefully insp...

Page 10: ...xisting vent system should also be checked to make sure it remains in compliance with NFGC If it isn t the vent system must be brought into compliance before installing the furnace Horizontal Venting...

Page 11: ...e furnace is equal to the return air supply under normal indoor return air applications When a cooling system is installed which uses the furnace blower to provide airflow over the indoor coil the coi...

Page 12: ...ur knockouts to expose the blower assembly Position the return air duct over the opening in the side and secure together with sheet metal screws The screws must penetrate the duct and furnace casing W...

Page 13: ...hers Securethesupportframetothe rafters with lag bolts The furnace can also be suspended using steel straps around each end of the furnace The straps should be attached to the furnace with sheet metal...

Page 14: ...e the furnace in reverse order Bottom Panel Removal The steps listed below describe how to remove the bottom panel from the furnace See Figure 11 1 Remove the door 1 from the blower compartment 2 Disc...

Page 15: ...IPING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be performed by a qualified installer service a...

Page 16: ...2 000 feet the input needs to be reduced 8 at 3 000 feet 12 etc This deration is in reference to the input rate and gas heating value at sea level Toderatethefurnacerequiresknowingtheheatingvalueof t...

Page 17: ...TATUS FLAME 180 COOL HEAT 120 90 60 BLOWER OFF DELAY LOW ML MH HIGH EAC L1 XFMR HUM 24V L1A 5 NEUTRALS 2 6 3 4 1 7 8 9 5 2 6 3 4 1 FAN 8 3 5 See Note R C Y G W STATUS FLAME 180 COOL HEAT 120 90 60 BLO...

Page 18: ...erty damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing...

Page 19: ...is connected Furnace Model SA SK Furnace Input Btuh Cabinet Width in Nominal Electrical Supply Maximum Operating Voltage Minimum Operating Voltage Maximum Furnace Amperes Minimum Wire Gauge Maximum F...

Page 20: ...municate to a fixed speed or variable speed high efficiency motor that may be optionally installed Please contact your distributor for the proper upgrade motor kit Heat Anticipator Set the heat antici...

Page 21: ...cal power to the furnace 3 FollowtheOperatingInstructionsonthelabelattached to the furnace 4 Setthethermostataboveroomtemperatureandverify the Operating Sequence Page 22 5 After 5 minutes of operation...

Page 22: ...t switch should turn off the gas valve when the return is blocked time depends on how well the return air is blocked The circulating air and combustion blowers should continue to run when the limit sw...

Page 23: ...will close the gas valve and initiate the shutdown cycle GasValve Controls the flow of gas to the burners When the gas valve is energized it automatically opens and regulates the gas pressure in the...

Page 24: ...urnace 4 Turn the gas control switch to the OFF position 5 Disconnect the wires from the gas valve igniter flame sensor and flame rollout switch CAUTION To prevent damage to the unit or internal compo...

Page 25: ...ays however the flue vent system and burners should be inspected and cleaned if required by a qualified service technician annually to ensure continued safe operation Pay attention to any deterioratio...

Page 26: ...23A 072C 24B 17 1 2 11 3 4 15 7 8 16 1 8 090C 24B 072C 35C 21 14 19 3 8 19 7 8 090C 35C 108C 35C 126C 45D 24 1 2 15 1 4 22 7 8 23 1 8 NOTE Dimensions shown in Inches 18 5 8 C 7 34 1 2 22 1 2 28 25 3 8...

Page 27: ...685 32 1 645 32 1 590 34 1 550 34 1 485 36 1 415 38 Med High 1 400 38 1 360 39 1 340 40 1 310 41 1 275 42 1 245 43 1 190 45 1 125 47 Med Low 1 235 43 1 215 44 1 180 45 1 155 46 1 130 47 1 100 48 1 060...

Page 28: ...63 1 225 65 1 175 68 SA108C 35C Side Return 108 000 High 2 295 35 2 235 36 2 180 37 2 110 38 2 050 39 1 975 41 1 900 42 1 810 44 Med High 2 130 38 2 075 39 2 035 39 1 970 41 1 915 42 1 845 43 1 765 4...

Page 29: ...51 1 300 51 1 280 52 1 255 53 1 230 54 1 200 56 1 150 58 Med Low 1 180 56 1 165 57 1 150 58 1 135 59 1 115 60 1 090 61 1 060 63 1 010 66 Low 940 71 925 72 900 74 880 76 850 78 825 81 795 84 760 88 SK...

Page 30: ...n Yellow LED Continuous Flash On Alternating Flash IGNITOR INDUCER FLAME SENSOR C BLOWER LIMIT SWITCH DOOR SWITCH R 4 SPEED MOTOR WHITE RED BLUE ORANGE BLACK BLOWER LIMIT SWITCH GAS VALVE H MH ML L C...

Page 31: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Page 32: ...57 57 ORIFICE SIZE 9 0 9 0 9 0 9 0 9 0 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 59 57 57 57 57 57 ORIFICE SIZE 8 5 8 5 8 5 8 5 8 5 8 5 MANIFOLD PRESSURE LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE...

Page 33: ...LD PRESSURE 9 000 to 9 999 FT 51 49 49 49 49 49 ORIFICE SIZE 2 6 2 8 2 8 2 8 2 8 2 8 MANIFOLD PRESSURE Table 11 High Altitude Deration Chart for Natural Gas Low Heating Value NATURAL GAS with LOW HEAT...

Page 34: ...oll Out Switch Transformer Blower Assembly Control Board Main Air Limit Switch Figure 20 Furnace Components Combustion Tube Gas Manifold Gas Valve Inducer Assembly Control Board Pressure Switch Transf...

Page 35: ...35...

Page 36: ...tion of this appliance Some local codes require licensed installation service personnel for this type of equipment Please read all instructions carefully before starting the installation Return these...

Reviews: