background image

8

table 1. thermostat Wire gauge

thermostat

Wire gauge

recommended t-Stat Wire

length (Unit to t-Stat)

2-Wire

cm (in.)

5-Wire

cm (in.)

24

140 (55)

64 (25)

22

229 (90)

114 (45)

20

356 (140)

178 (70)

18

572 (225)

279 (110)

optional electric Heater Kits

Optional field-installed electric heater kits may be 
available in multiple heating capabilities up to a maximum 
of 36kw. Split System Air conditioners are designed to 
allow optional auxiliary electric heat to be field installed 
as required by the building’s particular heating load. The 
options available for each unit are shown in the heater 
kit installation instructions or the air handlers Technical 
Service Literature.

Install the heater kits as directed by the instructions 
supplied with the heater kit. Follow all cautions and 
warnings as directed.

being pulled down to levels between 350-500 microns 
for 30 minutes.

•  To  achieve  rated  capacity  and  efficiency  the 

compressor must be exposed to refrigerant for at least 
24 hours prior to running and then the compressor 
must be run for a minimum of 12 hours.

•  Figures  6-14  (pages  14-18)  are  applicable  only 

to  matched  assemblies  of  NORDYNE  equipment 

and listed airflows for the indoor coil. Outdoor units 
with indoor coils not listed are not recommended 
and deviations from rated airflows or non-listed 
combinations may require modification to the 
expansion device and refrigerant charging 
procedures for proper and efficient system operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the 
outdoor unit. Use only gage line sets which have a 
“Schrader” depression device present to actuate the 
valve.

2. Indoor units are shipped with factory authorized orifices.  

One is installed in the distributor assembly.  Some 
models which cover multiple tonnage equipment will 
have additional orifices included.  Ensure the correct 
orifice size is installed in the distributor assembly for 
your specific matched system.  All R-22 export units 
must be charged with refrigerant as specified in the 
supplied addendum (709154).

3. Weigh-In the proper amount of new (or reclaimed) R-22 

refrigerant. Refer to the unit Rating Label or Table 2, 
Page 11 of this manual for the correct amount of charge 
that matches your specific system and connecting line 
lengths.

charging Units in ac mode when outdoor 
temperature is above 12.8° c (55° F) 
(optimized sub-cooling of 6.1° c - 7.8° c (11° 
F - 14° F)

1. With the system operating at steady-state, measure the 

liquid refrigerant pressure in kPa (PSIG) at the outdoor 
unit service valve.

2. Measure the liquid refrigerant temperature in Celsius ( 

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure from 

Figures 6-14 (pages 14-18).

•  If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined in 
Step 3, then there is too much charge in the system. 
Remove refrigerant and repeat Steps 1 through 3 
until the system is correctly charged.

•  If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 
Step 3, there is too little charge in the system. Add 
refrigerant and repeat Steps 1 through 3 until the 
system is correctly charged.

reFrigerant cHarging

 Warning:

these split system air conditioners leave the 
factory with a nitrogen holding charge. Follow 
these charging instructions for maximum 
unit performance and efficiency. Some local 
codes require licensed installation/service 
personnel to service this type of equipment. 
refrigerant charging must be done by qualified 
personnel familiar with safe and environmentally 
responsible refrigerant handling procedures. 
Under no circumstances should the owner 
attempt to install and/or service this equipment. 
Failure to comply with this warning could result 
in property damage, personal injury, or death.

After refrigerant line connections are completed, it is 
required that you properly leak check and evacuate the 
outdoor and indoor units and all line connections (using 
proper methods) before finalizing the full system refrigerant 
charge.

1. Removal of the outdoor section factory nitrogen 

charge can be used to purge non-condensables out 
of the system prior to conducting your leak check.  
Use standard industry practices for leak checking 
prior to evacuating the system.  When system is ready 
for evacuation, make sure the system is capable of 

Summary of Contents for S5BMX-018E

Page 1: ...ct and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to...

Page 2: ...an be obtained with the thermostat system mode set in any position including OFF Turning the Air conditioner Off Change the thermostat s system mode to OFF and the fan mode to AUTO See Figure 1 NOTE T...

Page 3: ...lower 9 Anti Short Cycle Timer Protection 9 System Cooling 9 System Heating 9 Air Conditioner Maintenance 10 Component Functions 10 Figures Tables 11 Figure 3 Unit Dimensions 11 Table 2 Unit Dimension...

Page 4: ...amage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructio...

Page 5: ...or mounting the outdoor unit Overhead obstructions Figure 2 poorly ventilated areas and areas subject to accumulation of debris should be avoided Sufficientclearanceforunobstructedairflowthroughthe ou...

Page 6: ...G WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical...

Page 7: ...connections are listed in Table 1 page 8 Thethermostatshouldbemountedabout5feet 1 52m above the floor on an inside wall DO NOT install the thermostat on an outside wall or any other location whereits...

Page 8: ...of new or reclaimed R 22 refrigerant Refer to the unit Rating Label or Table 2 Page 11 of this manual for the correct amount of charge that matches your specific system and connecting line lengths Ch...

Page 9: ...lter unit wiring A n t i S h o r t C y c l e T i m e r P r o t e c t i o n Single Phase Models Only 1 Set the thermostat system mode to COOL Note the temperaturesettingofthethermostatandgraduallyraise...

Page 10: ...5 minute short cycling delay before the outdoor unit will energize Air conditioner MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit...

Page 11: ...Metering Device Inches I D 0 052 0 056 0 065 0 070 0 070 0 072 0 082 0 090 0 092 R 22 Refrigerant charge Kg Ounces Outdoor unit Matched Indoor Unit 4 6M 15 Ft Line Set 4 2 41 85 2 61 92 2 87 101 3 01...

Page 12: ...ercurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 curcuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Sho...

Page 13: ...supply wire ampacities and overcurrent protection see unit rating plate 5 Connect to 24 VAC class 2 curcuit See furnace air handler installation instructions for control circuit and optional relay tra...

Page 14: ...specified on the unit rating label Theserefrigerantchargingchartsarevalidfor awidevarietyof indoorreturnair conditions temperature and airflow and are most influenced by the outdoor ambient temperatu...

Page 15: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 7 Charging Chart for 2 Ton Units 024E Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207...

Page 16: ...60 140 63 145 66 150 2758 400 C F Figure 10 Charging Chart for 3 Ton Units 036G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207 175 1379 200...

Page 17: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 11 Charging Chart for 3 5 Ton Units 042G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 120...

Page 18: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 14 Charging Chart for 5 Ton Units 060G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207...

Page 19: ...19...

Page 20: ...cable Avg Volts ______________________________ VOLTS If Applicable Max deviation of voltage from avg volts ____________________________________ VOLTS Volt imbalance _________________________________ V...

Reviews: