FigUreS & tableS
model number -
018e
024e
030e
036e
036g
042g
048g
054g
060g
Electrical Data: Volts-Cycles-Phase
220/240-1-50 (1a)
380/420-3-50 (1b) 3-Phase w/ Neutral
Unit Dimensions
cm (in.)
Height
59.7
(23.5)
59.7
(23.5)
80.0
(31.5)
90.2
(35.5)
69.8
(27.5)
80.0
(31.5)
80.0
(31.5)
80.0
(31.5)
80.0
(31.5)
Width
57.8
(22.75)
57.8
(22.75)
57.8
(22.75)
57.8
(22.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
Depth
57.8
(22.75)
57.8
(22.75)
57.8
(22.75)
57.8
(22.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
78.1
(30.75)
refrigerant suction line:
Length - M (Ft.) / O.D. - mm (in)
liquid line:
All lengths - 9mm (3/8 in.) O.D.
0-7.6 M
(0-25 Ft.)
19
(3/4)
19
(3/4)
19
(3/4)
22
(7/8)
22
(7/8)
22
(7/8)
22
(7/8)
22
(7/8)
22
(7/8)
7.9-11.9 M
(26-39 Ft.)
19
(3/4)
19
(3/4)
22
(7/8)
(2)
22
(7/8)
22
(7/8)
22
(7/8)
22
(7/8)
22
(7/8)
28.6
(1-1/8)
(3)
12.2-22.9 M
(40-75 Ft.)
19
(3/4)
19
(3/4)
22
(7/8)
(2)
22
(7/8)
22
(7/8)
29
(1-1/8)
(3)
29
(1-1/8)
(3)
29
(1-1/8)
(3)
29
(1-1/8)
(3)
Refrigerant Metering Device - (Inches) I.D.
0.052
0.056
0.065
0.070
0.070
0.072
0.082
0.090
0.092
r-22 refrigerant charge: Kg (ounces):
(Outdoor unit, Matched Indoor Unit, &
4.6M (15 Ft.) Line Set)
(4)
2.41
(85)
2.61
(92)
2.87
(101)
3.01
(106)
3.38
(119)
3.92
(138)
4.2
(148)
3.1
(110)
3.1
(109)
approximate Weight: Kg (lbs.)
Net
45
(100)
45
(100)
58
(128)
63
(139)
74
(164)
79
(173)
79
(173)
81
(179)
81
(179)
noteS:
1a. Operating Voltage Range: 198v min. — 264v max.
1b. Operating Voltage Range: 342v min. — 462v max.
2. Requires a 19mm to 22mm (3/4 in. to 7/8 in.) reducer from lineset to unit.
3. Requires a 22mm to 29 mm (7/8 in. to 1-1/8 in.) to reducer from lineset to unit.
4. Additional refrigerant charge for line sets above original 15 Ft. lineset total system charge.
Values based on suction line size as follows with 3/8 in. (9mm) liquid line.
a. 19mm (3/4 in.) = 0.6 oz. per additional foot
b. 22mm (7/8 in.) = 0.7 oz. per additional foot
c. 29mm (1-1/8 in.) = 0.8 oz. per additional foot
Figure 3. Unit dimensions
D
W
H
DO NOT OBSTRUCT TOP OF UNIT
Allow adequate clearance for airflow
table 2. Unit dimensional data
note: Unit style may appear
different depending on model.
Summary of Contents for S5BMX-018E