background image

To Shut Down Unit 

20.  OPERATING INSTRUCTIONS  

Set the thermostat to the lowest possible setting. 

Before Lighting 

Set the manual switch (if installed) in the Electrical 
Power Supply Line to "OFF". 

Open all supply and return air registers and grilles. 

Open all valves in oil pipes. 

 

Turn on electric power supply. 

 

To Light Unit 

Set the thermostat above room temperature to call for 
heat. The burner should start. NOTE: It may be 
necessary to press the RESET button on the primary 
combustion control relay. 

 

NOTE:  IF THE FURNACE IS TO BE SHUT DOWN 
FOR AN EXTENDED PERIOD OF TIME, CLOSE THE 
OIL SUPPLY VALVE TO THE BURNER. 

There will be a fan on time delay before the circulating 
fan is energized. The 

United Technologies 1158-120

 

has an adjustable fan on time that is set by selecting 
the dipswitch combination displayed in Chart 1. This 
fan on delay can be set at 30, 60, 90 or 120. 

 

 

Set the thermostat below room temperature. The oil 
burner should stop. 

The air circulation blower will continue to run until the 
time off setting selected on the electronic fan timer 
control times out. The 

United Technologies 1158-120 

have an adjustable fan off time of 2, 3, 4, & 6 minutes. 
The fan timer control adjustments may be altered if the 
air at the room registers is uncomfortably high upon 
blower start up or shutdown.  

DO NOT ATTEMPT TO START THE BURNER 
WHEN EXCESS OIL HAS ACCUMULATED, 
WHEN THE FURNACE IS FULL OF VAPOUR, OR 
WHEN THE COMBUSTION CHAMBER IS VERY 
HOT. NEVER BURN GARBAGE OR PAPER IN 
THE FURNACE, AND NEVER LEAVE PAPER OR 
RAGS AROUND THE UNIT. 

 

 

The necessary adjustments to the fan control settings 
should be determined by measuring the temperature of 
the air in the supply air take-off, or within the first few 
inches of the supply air trunk. The side mid point of the 
transition is usually ideal, providing that the 
thermometer probe is beyond the "line of sight" 
wherein false readings from radiant heat could be 
observed. The system temperature rise is 

the 

difference in temperature between the supply air and 
return air

 

 

 

 

 

 

 

To check the operation of the limit switch, shut off 
power to the furnace. Temporarily remove the neutral 
wire from the direct drive blower motor. Restore the 
electrical power to the furnace and set the thermostat 
above room temperature. 

 

 

 

 

After three or four minutes of burner operation, the limit 
control should turn the burner off. When the limit 
function test is complete, shut off electrical power to 
the furnace, replace the neutral wire to the blower fan 
motor, and then restore power. The blower fan will 
start up immediately. Once the temperature has 
dropped and the limit control has reset, the fan will 
operate until the fan off time is achieved. The oil burner 
will then resume operation and continue until the 
thermostat is satisfied. Restore the thermostat setting 
to a comfortable temperature. 

 

 

 

 

 

 

 

 

 

 

 

9

Summary of Contents for O5LD-091A-12-R

Page 1: ...flammable liquids or vapors in the vicinity of this or any other appliance ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL NORDYNE INC Read...

Page 2: ...NNECTIONS 5 10 HUMIDIFIER 6 11 PIPING INSTALLATION 6 12 OIL FILTER 6 13 OIL BURNER NOZZLES 6 14 OIL BURNER ADJUSTMENT 6 15 BURNER ELECTRODES 6 16 BURNER PRIMARY SAFETY CONTROL 7 17 COMBUSTION CHAMBER...

Page 3: ...n doubt please consult your local authorities Location Clearance to Combustibles Top 1 Bottom 0 S A Plenum 1 Rear 6 Sides 1 Front 1 Flue Pipe 4 in measured horizontally or below flue pipe 8 in measure...

Page 4: ...utlet should be at least two feet above the highest point of a peaked roof All unused chimney openings should be closed Chimneys must conform to local provincial or state codes or in the absence of lo...

Page 5: ...f 30 On Off 60 Off On 90 On On 120 Off Off 2 On Off 3 Off On 4 On On 6 9 ELECTRICAL CONNECTIONS The furnace is listed by the Canadian Standards Association under the NRTL North American Standard It is...

Page 6: ...ms should include an oil filter between the fuel oil storage tank and the oil burner When using an oil burner nozzle smaller than 0 65 U S Gallons Per Hour install an additional 7 to 10 micron filter...

Page 7: ...duct systems were not designed to provide static pressure They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts This system may require modificatio...

Page 8: ...O THE FURNACE and remove the burner Using a stiff brush with a wire handle brush off scale and soot from inside the drum and flue pipe To clean the radiator remove the clean out caps screws and remove...

Page 9: ...T TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOUR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT NEVER BURN GARBAGE OR PAPER IN THE FURNACE AND NEVER LEAVE PAPER OR...

Page 10: ...ckett AF Burner Electrode gap 5 32 inch Distance above horizontal centerline 5 16 inch Older instruction sheets specify 7 16 inch The current specification is 5 16 inch Distance ahead of nozzle 1 16 i...

Page 11: ...mounting plate as shown in Figure 2 The draft should be adjusted to 0 02 inches w c In the United States the Beckett AF Burner may be equipped with Beckett s Inlet Air Shut Off to increase efficiency...

Page 12: ...DD Med Low 1 2 HP Med Low 1 2 HP 3 1 2 HP 700 1600 O5LD 105A 12 R 10 10T DD Med Low 1 2 HP Med High 1 2 HP 3 1 2 HP 700 1600 Table A 6 Direct Drive Blower Characteristics CFM External Static Pressure...

Page 13: ...ENUM OPENINGS FLUE WIDTH A LENGTH B HEIGHT C SUPPLY D X E RETURN F X G DIAM HEIGHT H FILTER PERM SHIP WEIGHT LBS O5LD 091A 12 R 22 51 32 20 x 19 20 x 18 5 26 25 20 x 20 x 1 240 Table A 9 General Dimen...

Page 14: ...Chimney Vent Burner Wiring Diagram O5LD 091A 12 R APPENDIX B WIRING DIAGRAMS 14...

Page 15: ...The fan adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remov...

Page 16: ...and Y terminals are de energized Cooling contactor is de energized immediately Circulator fan turns off immediately Thermostat begins call for fan G terminal is energized Circulator fan is energized i...

Page 17: ...17 FIGURE 2 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD O5LD 019A 12 R...

Page 18: ...and burner motor reset button if equipped Check the limit switches to ensure that the switch contacts are closed Check the electrode gap and position Check the contacts between the oil primary contro...

Page 19: ...ive Check fuel oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks Any oil leak is a potential source of air or contaminants Furnace wil...

Page 20: ...ombustion air band and draft regulator to gain the highest practical CO2 or lowest practical O2 content in the flue gases See Burner Set Up Too much smoke Heat exchanger partially clogged Check for so...

Page 21: ...uct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary FINAL CHECK OUT 3 Where the oil shut off valve from the oil storage tank is located ENSURE THAT ALL SAFE...

Page 22: ...al No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No If different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Fuel Oil Suppli...

Page 23: ...le 30152 14 Clean out Gasket Retainer 2 per unit 29161 Clean out Gasket 2 per unit 29163 15 Oil Burner Mounting Plate Assembly 109007674 Inspection Door Gasket 29871 16 Pouch Gasket 2080175 17 Flue Pi...

Page 24: ...Firing Rate Baffle Nozzle 0 50 80 A 29880 25521101 29389 29 Blower Assembly Complete Direct Drive hp 4 Speed 29668 Blower Housing and Wheel 100 10T DD 30626 Blower Motor hp 4 Speed 102000131 Motor Mou...

Page 25: ...25...

Page 26: ...26...

Page 27: ...NOTES 27...

Page 28: ...28 NOTES Nordyne Inc 8000 Phoenix Parkway O Fallon Missouri 63368...

Reviews: