background image

8

e.  If the roof jack crown is covered or blocked with 

snow, the furnace will not operate properly. If 
the home is located in regions where snow 
accumulation exceeds 7” (HUD snowload 
zones) use an external roof jack extension 
p/n 901937.

f.  M1 furnaces may be used with roof jacks 

as tall as 170” (except M1M 056 & M1B 066 
models, which are limited to 120”). An internal 
roof jack extension (p/n 901935 - 10”, p/n 
903107 - 18”) can be used to increase roof 
jack height. All connections inside the home 
must be made below the ceiling.

These extensions are available as optional ac-
cessories and may be purchased through your 
NORDYNE distributor.

10. DUCT CONNECTOR 
SELECTION PLATINUM SERIES

a. For Platinum ready construction use 

the 14” round duct connector, p/n: 
903896.

NON-PLATINUM SERIES

a. Determine depth of fl oor cavity from 

surface of fl oor to top of supply air duct 
(See Figure  9).

h.  Gas piping is not run in or through the return 

duct system.

i.  Test the negative pressure in the closet with 

the air-circulating fan operating at high speed 
and the closet closed. The negative

    pressure is to be no more negative than minus 

0.05 inch water column.

j.  Air conditioning systems may require more 

duct register and open louver area to ob-
tain necessary airfl ow. Use NORDYNE’s 
certiduct program to determine proper duct 
size for A/C.

8. AIR DISTRIBUTION SYSTEMS

For proper air distribution, the supply duct system 
must be designed so that the static pressure 
measured external to the furnace does not 
exceed the listed static pressure rating shown 
on the furnace rating plate.

Location, size, and number of registers should 
be selected on the basis of best air distribution 
and fl oor plan of the home.

 CAUTION:

HAZARD OF ASPHYXIATION: Do not 
cover or restrict return air opening.

9. ROOF JACK SELECTION

Note: Install only Roof Jack Assemblies listed 
in Table 5 on this heating appliance.

a.  Determine depth of ceiling cavity from center 

of roof opening to center of ceiling opening. 
(See Dimension “A” in Figure 6.)

b.  Determine ceiling height and subtract height 

of furnace. (See Dimension “B” in Figure 6.)

c. Add dimensions A + B (and X from Table 6 

and Figure 7 if slant deck fl ashing is used). 
The total length of (A + B + X) must be within 
the minimum and maximum range of one of 
the Roof Jacks listed in Table 5.

APPLICATION NOTES:

a. FAW, FAWT, SAW and SAWT Series Roof 

Jacks with a 5” diameter inner vent pipe may 
be used with all models of M1 Series gas and 
oil furnaces.

b.  F=Flat Flashing; fl exes from 0/12 to 1/12 roof 

slope.

c. S=Slant Flashing. 2.5/12 Slope fl exes from 

1/12 to 4/12 roof slope, 4/12 fl exes from 3/12 
to 5/12.

d. Stainless steel roof jacks are available.

Table 6. Slant Deck Flashings

Table 7. Floor Cavity Sizes

Optional Deck Flashings for Flat and 2.5/12 Pitch 

Roof Jacks.

(4/12 Pitch Roof Jacks not applicable.)

IF ROOF PITCH IS:

USE SLANT DECK

FLASHING NO.

“X” FACTOR IS:

“F Series Roof Jack

2” in 12”

903893 (2.5/12)

2-1/8”

2-1/2” in 12”

903893 (2.5/12)

2-1/2”

3” in 12”

903894 (3/12)

2-7/8”

3-1/2” in 12”

903894 (3/12)

3-1/4”

4” in 12”

903895 (4/12)

3-5/8”

“S” Series Roof Jack (2.5/12 Pitch only)

4-1/2” in 12”

903895 (2.5/12)

2-1/8”

5” in 12”

903895 (2.5/12)

2-1/2”

5-1/2” in 12”

903894 (3/12)

2-7/8”

6” in 12”

903894 (3/12)

3-1/4”

6-1/2” in 12”

903895 (4/12)

3-5/8”

If “X” (Floor Cavity) is:

Use Duct Connector

Model Part Number:

English

Metric (mm)

Finger Tab

Screw Down

7/8”

22

901987

904008

2”

51

901988

904009

4-1/4”

108

901989

904010

6-1/4”

159

901990

904011

8-1/4”

210

901991

904012

10-1/4”

260

901992

904013

12-1/4”

311

901993

904014

Summary of Contents for M1B

Page 1: ...one Followthe gas supplier s instructions If you cannot reach your gas sup plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas...

Page 2: ...E GUIDE 25 18 MAINTENANCE 30 19 OPTIONAL ACCESSORIES 31 20 WIRING DIAGRAMS 34 39 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 40 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Page 3: ...living area of the home now a standard for the manufactured home industry NORDYNEengineersdevelopedthefirstcentral heatingsystemandthefirstcentralairconditioner for manufactured homes NORDYNE is dedi...

Page 4: ...M1 Furnace Specifications Furnace Input Output Orifice No E S P Pilot Ignitor Comb Motor A C Ready Model No MBtu h MBtu h Nat LP In WC Burner Direct Blower Hp Tons M1GH 056 56 45 29 45 0 3 x 1 8 2 M1G...

Page 5: ...501C forallrecreationalvehicleinstal lations Table 3 Field Installation Blower Assemblies Figure 1 Overall Dimensions A 56 23 3 4 B 76 19 3 4 A Model w o Coil Cabinet B Model w Coil Cabinet Removable...

Page 6: ...d so the burners and the source of the ignition are located no less than 18 inches above the floor and protected from physical damage by vehicles 6 MINIMUM CLEARANCES This heating appliance must be in...

Page 7: ...ification of 200 or less This includes a closet door if the furnace is in a closet f Noncombustible pans having 1 upturned flanges are located beneath openings in a floor duct system g Wiring material...

Page 8: ...stribution and floor plan of the home CAUTION HAZARD OF ASPHYXIATION Do not cover or restrict return air opening 9 ROOF JACK SELECTION Note Install only Roof Jack Assemblies listed in Table 5 on this...

Page 9: ...AIR DUCT FLOOR CAVITY depth equal to X in Figure 11 and Table 7 Figure 11 X SEE TABLE 7 REDUCER FELT SEAL SPACERS C OPENING TO DUCT WITH PLATE C REMOVED OPENING BECOMES 13 1 4 x 13 1 4 INDICATES FINGE...

Page 10: ...C E I L I N G C U T O U T F O R F L U E A N D R O O F J A C K S e e F i g 1 2 C L C L C L C L 24 23 1 4 21 3 4 14 1 2 2 1 4 2 3 4 20 14 1 2 13 1 2 FURNACE OUTLINE FLOOR CUT OUT FOR OPTIONAL COOLING C...

Page 11: ...8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DONOTALLOWDEBRISTOFALLINTOTHE FURNACE THIS COULD CAUSE UNSAFE OPERATION AND VOIDS THE FURNACE WARRANTY Use the top cap that comes with the furna...

Page 12: ...connector is designed for use on ducts 12 in width When using the connec tor on 12 wide ducts there may be insufficient clearance to bend the tabs on two sides of the duct connector In such cases the...

Page 13: ...he combustion air pipe to the furnace be made before the flashing is secured to the roof to maintain alignment of roof jack and furnace connections NOTE For replacement furnaces be sure the inner flue...

Page 14: ...er pipe Secure in place using three 3 10 1 2 sheet metal screws removed in step a Do not use the same holes which secured the rain cap in place c Venting system warning tags to be removed and discarde...

Page 15: ...ng jurisdiction CONNECT POWER SUPPLY WIRES a Remove the furnace control panel cover b Insert 115 volt wires through the strain relief on the left side of the furnace control box see Figure 25 c Connec...

Page 16: ...nlet pressure Pressure is reduced Five conductorthermostatwireisrecommended for 24 volt low voltage circuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems For Plat...

Page 17: ...satisfied where they apply for an approved installation Use a tank capacity suitable for the applica tion with a weatherproof capped fill opening and a shielded vent to let in air as fuel is used The...

Page 18: ...nk 8 ft Shut off Valve Optional Fuel Filter Alternate Fuel Line Entry Optional Return Pressure Gauge Port Nozzle Port Inlet Port Air Bleed Valve Return Port Internal By Pass Optional Inlet Control Pan...

Page 19: ...e level with the bottom of the duplex bushing Form the tube into an inverted U to serve as a vent How to Eliminate Air Leaks Toeliminateproblemscausedbyairintheoilline allconnectionsintheoilsupplyline...

Page 20: ...ust be lit by hand follow these instructions exactly c BEFORE LIGHTING smell all around the furnace for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on t...

Page 21: ...s broken it may allow productsofcombustionintotheliving space by the furnace blower resulting in possible asphyxiation In the event of any flashback or explosion immediately shut off the furnace and c...

Page 22: ...N section If you do not smell gas go to the next step g Set the On Off switch to the ON position h Honeywell turn knob on gas control counter clockwise to ON Robertshaw push the gas control lever to O...

Page 23: ...G Should overheating occur or the gas supply fail to shut off shut off the manualgasvalvetothefurnacebefore shutting off the electrically supply AVERTISSEMENT En case de temp rature excessive ou sail...

Page 24: ...If you then smell gas STOP and follow the safety information on the preceding page If you don t smell gas go to the next step 7 Set the On Off switch to the ON position 8 Honeywell turnknobongascontro...

Page 25: ...ycle The control uses a light sensing transducer to determineiffuelignitionhasbeensuccessfully attained If ignition is not attained by the end of the safety ignition timing period the control shuts th...

Page 26: ...11 for 66 000 BTUH furnaces and 12 13 for 86 000 BTUH furnaces The Smoke should be N0 0 on the Bacharach Scale and 0 to 0 02 negative draft over fire Electrode Setting Oil Gun Only Poor ignition of th...

Page 27: ...nto the converter top to protect the threads i Reassemble the burner assembly into the furnace j Reconnect the gas piping and electrical wires to the gas valve k Open the manual shut off valve and fol...

Page 28: ...electromagnet may be defective Replace the gas valve if necessary e Be sure the pilot shield is in place f Check for gas leaks in the pilot line or the pilot assembly g Check the flue assembly to make...

Page 29: ...and M1G 077 090 Models check air tube and electri cal connections c Burner in purge mode allow 75 seconds for flame establishing period d Check for proper electrical connections at purge timer contro...

Page 30: ...starts check thermostat or limit wiring connections b If burner does not start turn off power Check all wiring connections c If burner does not start replace primary control Burner starts and then lo...

Page 31: ...eantheairfilters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During ex tr...

Page 32: ...eries Only Rc RH W G Y Red White Green Yellow Red White Green Grey Thermostat M1 A C Ready Furnace Route Thermostat wire to intended Platinum Series AC HP location Coil and secure extra six feet of wi...

Page 33: ...l air conditioning systems There is a split system or package air conditioner designed for your total comfort needs Whether splitsystemorsinglepackage anenergy saving NORDYNE unit is available that ha...

Page 34: ...ACE ELECTRICAL BOX BLACK 3A FUSE BLOWER MOTOR HEATING ONLY 6 5 4 3 2 1 C R W GRAY RED BLUE CONNECTOR HOUSING CAP COMMON FOR OPTIONAL ACCESSORY KITS BLACK BLACK LEGENDS 115V FIELD 115V 24V FIELD 24V RE...

Page 35: ...OUND SCREW FURNACE ELECTRICAL BOX 3A FUSE BUSHING RED C R W ON OFF SWITCH CONNECTOR HOUSING CAP BLACK BLACK LEGENDS 115V FIELD 115V 24V FIELD 24V GRAY RED WHITE BLACK BLACK BLACK TRANSFORMER BLOWER MO...

Page 36: ...115V 24V FIELD 24V NOTES 1 Incoming power must be polarized Observe color coding See furnace data label for electrical information 2 If any of the original wires as supplied with the appliance must b...

Page 37: ...V HEATING COOLING 6 5 4 3 2 1 RED LOW BLACK HIGH BLUE MED HI ORANGE MED LO WHITE BLOWER MOTOR 4 SPEED CONNECTOR HOUSING CAP SUPPLIED BY INSTALLER Jumper Wire M1GB 090 Units Only Otherwise Hi Speed Con...

Page 38: ...verting to a multispeed blower Jumper is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 11 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHIT...

Page 39: ...USHING LINE CORD ITEM 12 TERMINAL BUSHING BUSHING BUSHING BUSHING W C ITEM 10 TYP 5 IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CON...

Page 40: ...AT GAS 24 25 26 27 27 28 28 29 29 30 M1M G 070 ORIFICE SIZE LP 42 42 43 43 43 44 44 45 46 47 OUTPUT MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28...

Reviews: