background image

12

Figure 16. Installation of Duct Connector

d. Cut out duct opening 1/4” larger than area 

marked.

INSTALL FURNACE MOUNTING PLATE
a. Place mounting plate (supplied within duct 

connector) at rear of the fl oor opening (See 
Figure 15).

INSTALLING PLATINUM SERIES 14” ROUND 
DUCT CONNECTOR
a.  Place duct connector through the fl oor open-

ing. (See Figure 15).

b.  Secure duct connector to fl oor.

INSTALLING SCREW DOWN DUCT CON-
NECTOR
a. Apply a bead of caulking, mastic, or other 

approved sealant around bottom side of 1/2” 
fl ange and restrictor plate, when applicable.

b. Locate the duct connector over duct and 

carefully lower screw down duct connector 
into place.

c. Once duct connector is located on duct, 

temporarily hold in place while fastening duct 
connector to the fl oor using fl at head screws 
or nails. Be sure fl anges of duct connector 
stay in contact with the duct.

d. Screw plenum to duct making sure a seal is 

made between the duct and the duct con-
nector. Additional screws may be added if 
required.

e.  Cut away duct along edge of fl ange allowing 

the center to drop into the duct. Remove 
section of duct with caution, as edges will be 
sharp.

INSTALLING FINGER TABBED DUCT CON-
NECTORS
a.  Place duct connector through the fl oor opening 

with bottom tabs extending through the duct 
opening. (See Figure 15)

b.  Secure duct connector to fl oor.
c.  Bend bottom tabs under and up tightly against 

the supply air duct (See Figure 16).

NOTE: The duct connector is designed for use 
on ducts 12” in width. When using the connec-
tor on 12” wide ducts, there may be insuffi cient 
clearance to bend the tabs on two sides of the 
duct connector. In such cases the tabs may be 
attached to the sides of the duct by using sheet 
metal screws or other suitable fasteners. (See 
Figure 17).

If sealant, mastic, or tape is used to provide a 
better seal, it should be approved by applicable 
national or local codes.

ALTERNATE ATTACHMENT METHODS

This procedure may also be used to install a 
furnace duct connector to narrow metal ductwork 
where insuffi cient clearance prevents bending 
of the duct connector tabs at the side(s) of the 
duct. (See Figure 18).
1. Score and cut the top of the metal duct as 

indicated in Step 1 or Step 2. With Step 1 
choice, also cut out the metal from the shaded 
area “A”.

2. Fold the duct fl ap “B” up, (See Step 3).
3. At the front-to-back of duct run (Area “A”), 

bend the duct tabs and secure them directly 
to the duct.

4. At Area “B”, bend the duct tabs up and 

back over, around the duct connector, (See 
Step 3).

5.  Fold/form the duct fl ap against the side of the 

duct connector and attach as shown, (See 
Step 4). Use three (3) staples (minimum) on 
each duct fl ap OR, if a 2X block/joist is not 
provided, use two (2) sheet metal screws 
(minimum) on each duct fl ap. An alternate 
attachment method is acceptable, as long 
as the duct connector is securely attached.

6. Tape the duct fl ap edges with an approved 

tape for a leak-free joint.

Duct

Duct Connector

Narrow Duct

Figure 17.

TABS

TABS

DUCT

DUCT

1.  INSERT DUCT CONNECTOR INTO
     DUCT CUT-OUT.

2.  BEND BOTTOM TABS OVER
     AND ONTO THE UNDERNEATH
     DUCT SERVICE.

Summary of Contents for M1B

Page 1: ...one Followthe gas supplier s instructions If you cannot reach your gas sup plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas...

Page 2: ...E GUIDE 25 18 MAINTENANCE 30 19 OPTIONAL ACCESSORIES 31 20 WIRING DIAGRAMS 34 39 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 40 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Page 3: ...living area of the home now a standard for the manufactured home industry NORDYNEengineersdevelopedthefirstcentral heatingsystemandthefirstcentralairconditioner for manufactured homes NORDYNE is dedi...

Page 4: ...M1 Furnace Specifications Furnace Input Output Orifice No E S P Pilot Ignitor Comb Motor A C Ready Model No MBtu h MBtu h Nat LP In WC Burner Direct Blower Hp Tons M1GH 056 56 45 29 45 0 3 x 1 8 2 M1G...

Page 5: ...501C forallrecreationalvehicleinstal lations Table 3 Field Installation Blower Assemblies Figure 1 Overall Dimensions A 56 23 3 4 B 76 19 3 4 A Model w o Coil Cabinet B Model w Coil Cabinet Removable...

Page 6: ...d so the burners and the source of the ignition are located no less than 18 inches above the floor and protected from physical damage by vehicles 6 MINIMUM CLEARANCES This heating appliance must be in...

Page 7: ...ification of 200 or less This includes a closet door if the furnace is in a closet f Noncombustible pans having 1 upturned flanges are located beneath openings in a floor duct system g Wiring material...

Page 8: ...stribution and floor plan of the home CAUTION HAZARD OF ASPHYXIATION Do not cover or restrict return air opening 9 ROOF JACK SELECTION Note Install only Roof Jack Assemblies listed in Table 5 on this...

Page 9: ...AIR DUCT FLOOR CAVITY depth equal to X in Figure 11 and Table 7 Figure 11 X SEE TABLE 7 REDUCER FELT SEAL SPACERS C OPENING TO DUCT WITH PLATE C REMOVED OPENING BECOMES 13 1 4 x 13 1 4 INDICATES FINGE...

Page 10: ...C E I L I N G C U T O U T F O R F L U E A N D R O O F J A C K S e e F i g 1 2 C L C L C L C L 24 23 1 4 21 3 4 14 1 2 2 1 4 2 3 4 20 14 1 2 13 1 2 FURNACE OUTLINE FLOOR CUT OUT FOR OPTIONAL COOLING C...

Page 11: ...8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DONOTALLOWDEBRISTOFALLINTOTHE FURNACE THIS COULD CAUSE UNSAFE OPERATION AND VOIDS THE FURNACE WARRANTY Use the top cap that comes with the furna...

Page 12: ...connector is designed for use on ducts 12 in width When using the connec tor on 12 wide ducts there may be insufficient clearance to bend the tabs on two sides of the duct connector In such cases the...

Page 13: ...he combustion air pipe to the furnace be made before the flashing is secured to the roof to maintain alignment of roof jack and furnace connections NOTE For replacement furnaces be sure the inner flue...

Page 14: ...er pipe Secure in place using three 3 10 1 2 sheet metal screws removed in step a Do not use the same holes which secured the rain cap in place c Venting system warning tags to be removed and discarde...

Page 15: ...ng jurisdiction CONNECT POWER SUPPLY WIRES a Remove the furnace control panel cover b Insert 115 volt wires through the strain relief on the left side of the furnace control box see Figure 25 c Connec...

Page 16: ...nlet pressure Pressure is reduced Five conductorthermostatwireisrecommended for 24 volt low voltage circuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems For Plat...

Page 17: ...satisfied where they apply for an approved installation Use a tank capacity suitable for the applica tion with a weatherproof capped fill opening and a shielded vent to let in air as fuel is used The...

Page 18: ...nk 8 ft Shut off Valve Optional Fuel Filter Alternate Fuel Line Entry Optional Return Pressure Gauge Port Nozzle Port Inlet Port Air Bleed Valve Return Port Internal By Pass Optional Inlet Control Pan...

Page 19: ...e level with the bottom of the duplex bushing Form the tube into an inverted U to serve as a vent How to Eliminate Air Leaks Toeliminateproblemscausedbyairintheoilline allconnectionsintheoilsupplyline...

Page 20: ...ust be lit by hand follow these instructions exactly c BEFORE LIGHTING smell all around the furnace for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on t...

Page 21: ...s broken it may allow productsofcombustionintotheliving space by the furnace blower resulting in possible asphyxiation In the event of any flashback or explosion immediately shut off the furnace and c...

Page 22: ...N section If you do not smell gas go to the next step g Set the On Off switch to the ON position h Honeywell turn knob on gas control counter clockwise to ON Robertshaw push the gas control lever to O...

Page 23: ...G Should overheating occur or the gas supply fail to shut off shut off the manualgasvalvetothefurnacebefore shutting off the electrically supply AVERTISSEMENT En case de temp rature excessive ou sail...

Page 24: ...If you then smell gas STOP and follow the safety information on the preceding page If you don t smell gas go to the next step 7 Set the On Off switch to the ON position 8 Honeywell turnknobongascontro...

Page 25: ...ycle The control uses a light sensing transducer to determineiffuelignitionhasbeensuccessfully attained If ignition is not attained by the end of the safety ignition timing period the control shuts th...

Page 26: ...11 for 66 000 BTUH furnaces and 12 13 for 86 000 BTUH furnaces The Smoke should be N0 0 on the Bacharach Scale and 0 to 0 02 negative draft over fire Electrode Setting Oil Gun Only Poor ignition of th...

Page 27: ...nto the converter top to protect the threads i Reassemble the burner assembly into the furnace j Reconnect the gas piping and electrical wires to the gas valve k Open the manual shut off valve and fol...

Page 28: ...electromagnet may be defective Replace the gas valve if necessary e Be sure the pilot shield is in place f Check for gas leaks in the pilot line or the pilot assembly g Check the flue assembly to make...

Page 29: ...and M1G 077 090 Models check air tube and electri cal connections c Burner in purge mode allow 75 seconds for flame establishing period d Check for proper electrical connections at purge timer contro...

Page 30: ...starts check thermostat or limit wiring connections b If burner does not start turn off power Check all wiring connections c If burner does not start replace primary control Burner starts and then lo...

Page 31: ...eantheairfilters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During ex tr...

Page 32: ...eries Only Rc RH W G Y Red White Green Yellow Red White Green Grey Thermostat M1 A C Ready Furnace Route Thermostat wire to intended Platinum Series AC HP location Coil and secure extra six feet of wi...

Page 33: ...l air conditioning systems There is a split system or package air conditioner designed for your total comfort needs Whether splitsystemorsinglepackage anenergy saving NORDYNE unit is available that ha...

Page 34: ...ACE ELECTRICAL BOX BLACK 3A FUSE BLOWER MOTOR HEATING ONLY 6 5 4 3 2 1 C R W GRAY RED BLUE CONNECTOR HOUSING CAP COMMON FOR OPTIONAL ACCESSORY KITS BLACK BLACK LEGENDS 115V FIELD 115V 24V FIELD 24V RE...

Page 35: ...OUND SCREW FURNACE ELECTRICAL BOX 3A FUSE BUSHING RED C R W ON OFF SWITCH CONNECTOR HOUSING CAP BLACK BLACK LEGENDS 115V FIELD 115V 24V FIELD 24V GRAY RED WHITE BLACK BLACK BLACK TRANSFORMER BLOWER MO...

Page 36: ...115V 24V FIELD 24V NOTES 1 Incoming power must be polarized Observe color coding See furnace data label for electrical information 2 If any of the original wires as supplied with the appliance must b...

Page 37: ...V HEATING COOLING 6 5 4 3 2 1 RED LOW BLACK HIGH BLUE MED HI ORANGE MED LO WHITE BLOWER MOTOR 4 SPEED CONNECTOR HOUSING CAP SUPPLIED BY INSTALLER Jumper Wire M1GB 090 Units Only Otherwise Hi Speed Con...

Page 38: ...verting to a multispeed blower Jumper is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 11 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHIT...

Page 39: ...USHING LINE CORD ITEM 12 TERMINAL BUSHING BUSHING BUSHING BUSHING W C ITEM 10 TYP 5 IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CON...

Page 40: ...AT GAS 24 25 26 27 27 28 28 29 29 30 M1M G 070 ORIFICE SIZE LP 42 42 43 43 43 44 44 45 46 47 OUTPUT MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28...

Reviews: