Nordyne Air Conditioner / Heat Pump Air Handler Owner'S Manual & Installation Instructions Download Page 6

6

CIRCULATING AIR REQUIREMENTS

 WARNING:

All return ducts must be secured to the furnace 
with sheet metal screws. All return ducts must be 
adequately sealed. When return air is provided 
through the bottom of the unit, the joint between 
the furnace and the return air plenum must be 
air tight.

Return air and circulating air ducts must not be 
connected to any other heat producing device 
such as a fi replace insert, stove, etc. This may 
result in fi re, explosion, carbon monoxide 
poisoning, personal injury, or property damage.

Plenums & Air Ducts

This unit is designed only for use with a supply and return 
duct. Air ducts should be installed in accordance with the 
standards of the National Fire Protection Association 
Standard for Installation of Air Conditioning Systems 
(NFPA 90A), Standard for Installation of Residence Type 
Warm Air Heating and Air Conditioning Systems (NFPA 
90B), and all applicable local codes. NFPA publications 
are available by writing to: National Fire Protection 
Association, Batterymarch Park, Quincy, ME 02269 or visit 
www.NFPA.org on the web.

•  Plenums and air ducts must be installed in accordance 

with the Standard for the Installation of Air Conditioning 
and Ventilating Systems (NFPA No. 90A) or the 
Standard for the Installation of Warm Air Heating and 
Air Conditioning Systems (NFPA No. 90B).

•  Design the air ducts according to methods described 

by the Air Conditioning Contractors of America (ACCA).

•  Air ducts must be aluminum, tin plate, galvanized sheet 

steel, or other approved materials for outlet or return air 
ducts.

•  Snap-Lock or Pittsburgh-Lock seams are preferred. All 

other types of seams must be made tight to prevent 
leakage.

•  It is good practice to seal all connections and joints 

with industrial grade sealing tape or liquid sealant. 
Requirements for sealing ducts vary from region to 
region. Consult with local codes for requirements specifi c 
to your area.

•  Gas piping must not run in or through any of the air duct 

system.

•  Applicable installation codes may limit the furnace to 

installation in a single-story residence only. Furnace 
installations other than closet or alcove require ducted 
return air systems.

Return Air Connections

Air return to the furnace must have a minimum free area 
opening (see Table 1). A return air grille for closet or alcove 
installations is available. Acceptable closet installations 
with return air entering through an opening in the fl oor 
or ceiling of a closet, must meet all of the following 
requirements:

•  The return air opening, regardless of its location in the 

closet, must not be smaller than size specifi ed on unit 
data label. If located in the fl oor, the opening must be 
provided with a means of preventing its inadvertent 
closure by fl at object(s) placed over the opening.

•  A return air grille must be used when furnace is installed 

in a closet or alcove:

  Alcove installations: use return air grille & frame assembly 

P/N 902989 or equivalent. See Figure 2, page.

  Closet installations: use wall mount return air grilled 

P/N 902999 or equivalent. 

NOTE:

 For 5 ton A.C. or H.P. 

system, 155 in

2

 (1,000 cm

2

 ) must be added.

  Downfl ow alcove installations: the grille (with frame 

provided) may be attached to the top of the furnace and all 
paneling and trim fl ushed to it. This installation provides 
an access door for future installation of NORDYNE air 
conditioning or heat pump coils on top of the furnace.

•  Materials located in return air duct system must have 

a fl ame-spread classifi cation of 200 or less.

•  Noncombustible pans having 1” upturned fl anges must 

be located beneath openings in a fl oor-return duct 
system.

•  Wiring materials located in return duct system must 

conform to NEC Article 300-22(c).

•  If return air opening is located below top of furnace, a 

minimum clearance must be provided between opening 
and furnace. See Table 1 (page 5).

Supply Air Connections
•  Supply duct system must be designed for proper air 

distribution. Static pressure measured externally to 
furnace shall not exceed static pressure rating listed 
on furnace nameplate.

•  Duct system must be designed so that no supply registers 

are located in duct system directly below the furnace.

Acoustical Ducts

Certain installations may require the use of acoustical 
lining inside the supply duct work.

•  Acoustical insulation must be in accordance with the 

current revision of the Sheet Metal and Air Conditioning 
Contractors National Association (SMACNA) application 
standard for duct liners.

•  Duct lining must be UL classifi ed batts or blankets with 

a fi re hazard classifi cation of FHC-25/50 or less.

•  Fiber duct work may be used in place of internal duct 

liners if the fi ber duct work is in accordance with the 
current revision of the SMACNA construction standard 
on fi brous glass ducts. Fibrous duct work and internal 
acoustical lining must be NFPA Class 1 air ducts when 
tested per UL Standard 181 for Class 1 ducts.

Summary of Contents for Air Conditioner / Heat Pump Air Handler

Page 1: ...a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor The Installation Instructions are primarily in...

Page 2: ...t Connector Installation 11 Alcove Installations 11 Closet Installations 11 Downflow Furnaces 11 Upflow Furnaces 12 Over the Floor Return Air Non Ducted 12 Through the Floor Return Air Ducted 13 ELECT...

Page 3: ...urer s User manual for detailed programming instructions NOTE Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting After the desi...

Page 4: ...require additional maintenance Coil Filters If a cooling coil is installed on your unit the furnace filter is not used Remove coil filters wash and allow to dry Re install coil filters to their origin...

Page 5: ...inorormoderate injury or property damage INSTALLER INFORMATION Minimum Installation Clearances Access for positioning and servicing the unit must be considered when locating unit The need to provide c...

Page 6: ...e closet installations with return air entering through an opening in the floor or ceiling of a closet must meet all of the following requirements The return air opening regardless of its location in...

Page 7: ...y additional external static pressure produced from the chosen filtering method Without optional coil housing Install a filter with a minimum unrestricted medium area of 324 in2 in the duct above the...

Page 8: ...mensions for this furnace are shown in Figure 21 page 18 If an upflow stand will be used see Figure 22 for component dimensions The unit must be leveled at installation and attached to a properly inst...

Page 9: ...OR CUT OUT 14 1 4 DIAMETER FOR UPFLOW FURNACES WITH ROUND DUCT CONNECTORS C L STANDARD DUCT CONNECTOR ROUND DUCT CONNECTOR Locating Cutting Floor Openings Floor cut outs must be carefully located to a...

Page 10: ...ector Installed Figure 10 Narrow Air Duct Openings OPTION 1 OPTION 2 Supply Air Duct Fold Flap Here Fold Flap Here Remove this Flap Remove this Flap C u t H e r e C u t H e r e C u t H e r e C u t H e...

Page 11: ...n air grill installed in the door or a partially louvered door across the opening For clearances 6 or greater the closet must have an open free area of 235 in2 minimum For special clearances between 1...

Page 12: ...ructions supplied with accessory equipment Over the Floor Return Air System Non Ducted 1 If floor underneath furnace is made of combustible material locate a pan fabricated of non combustible material...

Page 13: ...onnect all electrical power to furnace When servicing controls label all wires prior todisconnecting Reconnectwirescorrectly Verify proper operation after servicing WARNING Electrical connections must...

Page 14: ...rth ground to operate properly Acceptablemethodsincludeelectrical wire or conduit approved for ground service Do not use gas piping as an electrical ground Thermostat Low Voltage Connections The furna...

Page 15: ...ptacle Position Pin1 Pin2 Pin3 Pin4 Pin5 4 Speed Blower Low Med LO Med Hi High Control Box Blower Lead Red Yellow Blue Black Blower Installation 1 Turn off all electrical supply circuits to the furnac...

Page 16: ...t up Procedures 1 Reinstall control box cover s 2 Switch circuit breaker s to the ON position 3 Replace outer furnace door 4 Check all duct connections and tape for air leakage Figure 19 E3EB Thermost...

Page 17: ...Wheel Blower Wheel Strap Capacitor Motor Control Door Right Side Control Door Left Side Circuit Breaker Circuit Adapter 012 Models Only Contactor Limit Switch Element Grounding Lug Blower Relay Transf...

Page 18: ...ckout 4 1 4 X 3 3 4 FRONT VIEW TOP VIEW LEFT SIDE BOTTOM VIEW RIGHT SIDE VentilAire Knockout 1 1 2 X 5 VentilAire Knockout 1 1 8 X 4 1 2 Optional Electric 1 Optional Electric 5 8 Tie Down Tab TOP VIEW...

Page 19: ...oling Available with factory installed blower 2 0 4 0 Ton See Note 3 2 0 5 0 Ton Optional Heat Pump Available with factory installed blower 2 0 4 0 Ton Air Filter Standard 16 x 20 x 1 nominal Furnace...

Page 20: ...08 Dual A 44 6 60 56 Dual B 41 7 60 52 023H Single 93 8 125 117 Dual A 45 5 60 57 Dual B 48 0 60 60 Model Number E3EX Supply Circuit Total Amperes Maximum Over current Rating Minimum Circuit Ampacity...

Page 21: ...installation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on...

Page 22: ...tallation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on syst...

Page 23: ...nstallation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on sy...

Page 24: ...furnace and or relay box installation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...sandanyotherspecialnoteshighlightedinthemanual Improper installation service or maintenance of the furnace or failure to follow safety warnings could result in serious injury death or property damage...

Reviews: