Nordyne Air Conditioner / Heat Pump Air Handler Owner'S Manual & Installation Instructions Download Page 11

11

Narrow

Duct

Narrow

Duct

Duct connector tabs

Staples or sheet metal screws 

Duct 
Flap

Narrow  

Duct

Duct Connector

Sheet metal 

screws 

Figure 11. Narrow Ducts

Figure 12. Round Duct Connector Installed

Screws

Mounting

Plate

Round Duct

Connector

14” Supply

Connection

7.  Seal all connections with industrial grade sealing tape 

or liquid sealant.

NOTE: 

Requirements for sealing ductwork vary 

from region to region. Consult with local codes for 
requirements specifi c to your area.

Round Duct Connector Installation

The 14” round duct connector is designed to connect 
directly to a 14” fl exible duct. 

NOTE: 

Flexible ducts must 

have a minimum temperature rating of 200° F and meet 
all applicable codes and standards.

1.  Apply a bead of caulking, mastic, or other approved 

sealant around bottom side of connector.

2.  Install and center the duct connector in the fl oor 

opening.

3.  Install the mounting plate under the back side of the 

duct connector. See Figure 12. 

NOTE:

 Align the screw 

holes in both components.

4.  Secure the duct connector and the mounting plate to 

the wood fl oor with appropriate size screws.

5.  Connect the round supply duct to the underside of the 

duct connector and secure them with fi eld supplied 
sheet metal screws.

6.  Seal all connections with industrial grade sealing tape 

or liquid sealant.

NOTE: 

Requirements for sealing ductwork vary 

from region to region. Consult with local codes for 
requirements specifi c to your area.

Alcove Installation

1.  Cut alcove rough openings to minimum dimensions 

shown in Figure 13 (page 12).

2.  Attach frame assembly with four fasteners (provided or 

equivalent) into pre-punched holes on top of furnace. 
See Figure 2 (page 7). 

NOTE:

 If additional securing 

is required, attach each side of frame assembly to 
alcove opening using holes provided.

3.  Attach return air grille to frame assembly by hooking 

grille over fl ange on top of frame and into channel on 
bottom.

Closet Installation

For proper air circulation, closet installations require a 
return air grill installed in the door or a partially louvered 
door across the opening. For clearances 6” or greater, the 
closet must have an open free area of 235 in

2

 minimum. 

For special clearances between 1” - 5”, requirements are 
a louvered door with a minimum of 250 in

2

 (1613 cm

2

) free 

area. A fully louvered closet door is strongly recommended 
for both installation types. For closet installations, the return 
air grille mounting frame is not used since the furnace is 
located inside the closet. For examples of both types of 
installations, see Figure 14 (page 12).

1.  Cut return air opening in desired position in door or 

wall, preferably above top of furnace. Refer to Table 
1 for return air opening requirements.

2.  Insert four fasteners, securing grille to door or wall.

Downfl ow Furnaces

For typical unducted return air downfl ow applications, 
an air-conditioner or heat-pump coil can be installed by 
mounting the coil directly on top of the furnace without 
adding sheet metal cavities or cutting and trimming wood 
panels. Unducted return air systems may be used for 
closet or alcove installations.

The steps below describe installation procedures for 
an under-the-fl oor supply duct system with a ducted 
or unducted return air system. Duct connectors are 
recommended for this application. See Table 2 (page 10).

1.  Route 240V supply circuit(s) and 24V wiring to closet 

or alcove. See Figure 21 (page 18) for locations.

2.  Remove refrigerant line knockouts in furnace only 

when installing indoor coil of an air conditioner or heat 
pump system, or for hook-up of a VentilAire accessory 
when the furnace is used in the upfl ow position. Refer 
to instructions supplied with accessory equipment.

3.  Remove unit front door and slide back until bottom 

slots in rear of unit engage with both tabs of optional 
rear mounting plate. If mounting plate is not used, an 
equivalent method of securing the rear of the unit may 
be used as long as it prevents displacement during 
transport if used in a manufactured home.

NOTE:

 The furnace does not need to be positoned 

against the rear mounting plate. The tabs will engage 
into the slots and allow approximately 1/2” of furnace 
adjustment front to back and side to side.

Summary of Contents for Air Conditioner / Heat Pump Air Handler

Page 1: ...a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor The Installation Instructions are primarily in...

Page 2: ...t Connector Installation 11 Alcove Installations 11 Closet Installations 11 Downflow Furnaces 11 Upflow Furnaces 12 Over the Floor Return Air Non Ducted 12 Through the Floor Return Air Ducted 13 ELECT...

Page 3: ...urer s User manual for detailed programming instructions NOTE Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting After the desi...

Page 4: ...require additional maintenance Coil Filters If a cooling coil is installed on your unit the furnace filter is not used Remove coil filters wash and allow to dry Re install coil filters to their origin...

Page 5: ...inorormoderate injury or property damage INSTALLER INFORMATION Minimum Installation Clearances Access for positioning and servicing the unit must be considered when locating unit The need to provide c...

Page 6: ...e closet installations with return air entering through an opening in the floor or ceiling of a closet must meet all of the following requirements The return air opening regardless of its location in...

Page 7: ...y additional external static pressure produced from the chosen filtering method Without optional coil housing Install a filter with a minimum unrestricted medium area of 324 in2 in the duct above the...

Page 8: ...mensions for this furnace are shown in Figure 21 page 18 If an upflow stand will be used see Figure 22 for component dimensions The unit must be leveled at installation and attached to a properly inst...

Page 9: ...OR CUT OUT 14 1 4 DIAMETER FOR UPFLOW FURNACES WITH ROUND DUCT CONNECTORS C L STANDARD DUCT CONNECTOR ROUND DUCT CONNECTOR Locating Cutting Floor Openings Floor cut outs must be carefully located to a...

Page 10: ...ector Installed Figure 10 Narrow Air Duct Openings OPTION 1 OPTION 2 Supply Air Duct Fold Flap Here Fold Flap Here Remove this Flap Remove this Flap C u t H e r e C u t H e r e C u t H e r e C u t H e...

Page 11: ...n air grill installed in the door or a partially louvered door across the opening For clearances 6 or greater the closet must have an open free area of 235 in2 minimum For special clearances between 1...

Page 12: ...ructions supplied with accessory equipment Over the Floor Return Air System Non Ducted 1 If floor underneath furnace is made of combustible material locate a pan fabricated of non combustible material...

Page 13: ...onnect all electrical power to furnace When servicing controls label all wires prior todisconnecting Reconnectwirescorrectly Verify proper operation after servicing WARNING Electrical connections must...

Page 14: ...rth ground to operate properly Acceptablemethodsincludeelectrical wire or conduit approved for ground service Do not use gas piping as an electrical ground Thermostat Low Voltage Connections The furna...

Page 15: ...ptacle Position Pin1 Pin2 Pin3 Pin4 Pin5 4 Speed Blower Low Med LO Med Hi High Control Box Blower Lead Red Yellow Blue Black Blower Installation 1 Turn off all electrical supply circuits to the furnac...

Page 16: ...t up Procedures 1 Reinstall control box cover s 2 Switch circuit breaker s to the ON position 3 Replace outer furnace door 4 Check all duct connections and tape for air leakage Figure 19 E3EB Thermost...

Page 17: ...Wheel Blower Wheel Strap Capacitor Motor Control Door Right Side Control Door Left Side Circuit Breaker Circuit Adapter 012 Models Only Contactor Limit Switch Element Grounding Lug Blower Relay Transf...

Page 18: ...ckout 4 1 4 X 3 3 4 FRONT VIEW TOP VIEW LEFT SIDE BOTTOM VIEW RIGHT SIDE VentilAire Knockout 1 1 2 X 5 VentilAire Knockout 1 1 8 X 4 1 2 Optional Electric 1 Optional Electric 5 8 Tie Down Tab TOP VIEW...

Page 19: ...oling Available with factory installed blower 2 0 4 0 Ton See Note 3 2 0 5 0 Ton Optional Heat Pump Available with factory installed blower 2 0 4 0 Ton Air Filter Standard 16 x 20 x 1 nominal Furnace...

Page 20: ...08 Dual A 44 6 60 56 Dual B 41 7 60 52 023H Single 93 8 125 117 Dual A 45 5 60 57 Dual B 48 0 60 60 Model Number E3EX Supply Circuit Total Amperes Maximum Over current Rating Minimum Circuit Ampacity...

Page 21: ...installation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on...

Page 22: ...tallation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on syst...

Page 23: ...nstallation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6 Not suitable for use on sy...

Page 24: ...furnace and or relay box installation instructions for thermostat connections 5 If any wire in this unit is to be replaced it must be replaced with 105 C thermoplastic copper wire of the same gauge 6...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...sandanyotherspecialnoteshighlightedinthemanual Improper installation service or maintenance of the furnace or failure to follow safety warnings could result in serious injury death or property damage...

Reviews: