Operation
4‐4
Part 7192568-03
E
2020 Nordson Corporation
Powder Level Sensor Operation
Hopper Operation
When the level of powder falls below the level sensor, a delay timer
(field-adjustable) is started. When the delay timer runs out, the virgin transfer
pump is turned on to refill the hopper. When the level sensor detects powder,
the virgin transfer pump is turned off. If the level sensor detects no powder for
greater than 3 minutes (field-adjustable), the low powder alarm is turned on.
Silencing the Low Powder Alarm
Touch the alarm silence icon on the touch screen.
Startup
1. Ensure that the system is safe to start.
2. Using the front door panel on the isolator, turn on the system components
in the following sequence:
S
Booth Control Panel
S
After Filter Control Panel
S
Spectrum HD Generation II Feed Center
3. Ensure the emergency stop buttons are pulled out on the booth, feed
center, and after filter panels.
4. Make sure compressed air is being supplied to the feed center at 6.5 bar
(95 psi) and that air pressures are adjusted properly.