
17
GB
6. Assembly
Important! It is very important that installation in-
structions are read carefully and followed closely in
order to ensure optimal functioning of the product.
Important! Failure to follow the guidelines for drying
can cause the elements to crack.
The air vent control is turned to the right to increase
the air supply to Salzburg. The vent is working in
two modes.
A.
When you turn the vent maximally to the right it is in
ignition mode.
B.
If you turn the vent to the left ingnition air is diminish.
When you felt a click then ignition air is closed and there
is maximum secondary air provided. Futher turning to
the left decraese amount of secondary air.
Combustion pace
An accumulating fireplace is designed to absorb thermal
energy during a relatively short period of relatively
intense heat. When the period of intensive combustion
is completed, the product will deliver the accumulated
heat over a longer period of time.
Important! Combustion beyond the recommended
pace (see table with Technical Information) will
result in a higher surface temperatures, which
can lead to discoloration of the paint. It can also
result in higher than intended temperatures against
combustible walls.
Follow the values in the table to find the correct load
size and what loading interval is right for your product.
When the last load has passed into the ember phase
with few embers left, the air vent and damper is closed
to prevent heat escaping through the chimney.
Remember to open the damper before making a fire in
the fireplace.
The ignition mode should only be open during when
necessary for short periods (10-15 minutes) at the time
a fire is lit, and at new loads, in order to prevent smoke
or ash escaping into the room. Persistent combustion
with an open ignition mode can result in exceeding the
maximum allowed chimney temperature.
Due to the length of the smoke gas ducts, the
fireplace is heated up somewhat unevenly. After
lighting a fire, the front above the door and one of
the sides will heat up first. The heat will then be
evened out after a few hours of burning and when
all the ducts have been warmed up.
+
-
A
B
Summary of Contents for FP-SAL05-200
Page 46: ...46 FIG 9 FIG 8 21 30001 510 x4 3 mm IS SAL04 040 x2 21 40005 525 x2 22 SAL04 170 x2 3 mm...
Page 49: ...49 FIG 14 CO SAL05 03L 1 2 A cryl CO SAL05 03R FIG 15...
Page 57: ...57 FIG 26 LA SAL04 01L FIG 27 FIG 28 LA SAL04 01A LA SAL04 01R...
Page 59: ...59 IS SAL04 070 FIG 31 FIG 32 LA SAL04 020 FIG 33 LA SAL04 03L...
Page 60: ...60 FIG 34 LA SAL04 040 FIG 35 1 2 3 4 LA SAL04 03L...
Page 61: ...61 3 mm 2 1 FIG 36 B C A...
Page 63: ...63 FIG 38 CO SAL05 050 FIG 39 30 mm O8...
Page 65: ...65 FIG 41 a 22 SAL05 070 FIG 41 1 CO SAL05 040...
Page 68: ...68 FIG 42 PI SAL01 13B CO SAL05 050 FIG 43...