26
– Operation with
timer controlled capacity limitation
:
Select “
Power Limit
” in the settings menu, then press the
<Set>
key.
Select “
Timer
”, then press the
<Set>
key. In the upcoming modification dialogue activate the timer
function and confirm the setting with the
<Set>
key.
If the timer is activated, up to eight switching points (events 1 - 8) with different capacity limits
can be defined. Each switching point is defined by a weekday or weekday range, the switching
point and the capacity limit.
Configuration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings. Therefore, make sure your
settings make sense.
– the On/Off timer (see chapter 4.6.5) overrides the capacity limit timer.
Power Limit
Power Limit :50%rH
Timer :Off
Esc
Set
Timer
Off
On
On
Esc
Set
Power Limit
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc
Set
Event 2
Time :18:00
Power Limit :100%
Weekday :Mo-Fr
Esc
Set
Power Limit
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc
Set
Weekday
Off
Mo-Fr
Mo-Sa
Mo-Fr
Mo-So
Esc
Set
Event 2
Time :18:00
Power Limit :100%
Weekday :Mo-Fr
Esc
Set
Event 2
Time :18:00
Power Limit :100%
Weekday :Mo-Fr
Esc
Set
Power Limit
100 %
100 %
Esc
Set
Time
18:00
18:00
Esc
Set
Settings
Controls :Set
Power Limit :100%
On/Off Timer :Set
Language :English
GFCI-Mode :On
Esc
Set