The installation site of the Nordmann Omega Pro depends largely on the location of the steam distributor
(see
). To
ensure
proper functioning
of the steam humidifier and to
obtain an optimal
efficiency
, the following points must be considered and observed when choosing the location for the
steam humidifier:
– Install the steam humidifier so that:
– the
length of the steam
line is kept as short as possible (
max. 4 m
),
– the
minimum bend radius for steam hoses (R= 300 mm)
and for
solid steam pipes (5 x
internal diameter)
and the minimum
upslope
and
downslope (min. 15 %/8.5°)
of the steam
lines is maintained (see
).
– The Nordmann Omega Pro is designed for wall-mounting in protected interiors. Make sure that the
construction (wall, pillar, floor-mounted console, etc.) to which the humidifier is to be mounted, of-
fers a
sufficiently high load-bearing capacity
(take notice of the weight information found in the
dimensions and weights table), and is suitable for the installation.
CAUTION!
Do
not
mount the steam humidifier directly to the ventilation duct (insufficient stability).
– The back panel of the Nordmann Omega Pro retains heat during operation (max. surface temperature
of the metal housing approx. 60 - 70 °C). Make sure, therefore, that the construction (wall, pillar,
etc.) to which the unit is to be mounted, does not consist of heat-sensitive material.
– Install the Nordmann Omega Pro in such a manner that it is
freely accessible
with sufficient space
available for maintenance purposes. The
minimum distances
shown in
must be maintained
.
– In order to use the cables supplied with double units, the individual units must be mounted on the same
height, with a maximum distance between the units of 50 mm and in the order shown in
– The Nordmann Omega Pro is protected according to
IP21
. Make sure the unit is installed in a drip-
proof location and the admissible ambient conditions are complied with.
– Do
not
mount the Nordmann Omega Pro to hot or very cold walls or near vibrating components.
– The steam humidifier Nordmann Omega Pro must only be installed in rooms with a floor drain.
CAUTION!
If for some reason the Nordmann Omega Pro must be installed in a location without floor drain, it
is mandatory to provide a leakage monitoring device to safely interrupt the water supply in case
of leakage.
– When mounting the Nordmann Omega Pro use
only the mounting materials supplied with the
unit
. If mounting with the materials supplied is not possible in your particular case, select a method
of mounting that is of similar stability.
– The Nordmann Omega Pro is designed for installation and operation within buildings (admissible
temperature range 5...40 °C). For outdoor operation the Nordmann Omega Pro must be placed in
a weather protective housing. If ambient temperatures near or below the freezing point have to be
expected, the protective housing must equipped with a thermostat controlled heating of sufficient
capacity. The water supply pipe must be equipped with a trace-heating and must be insulated up to
the protective housing. The installation of a normally open valve inside the building envelope that
will drain water in case of power failure is highly recommended.