3 Options
BU 0200 GB
Subject to technical alterations
103
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
21 GND
22
Reference potential
for digital signals
As for terminal 15
-
23 24V
24
external 24V supply
As for terminal 11
-
25 DIN2
Digital input 2
(I/O DeviceNet DIN2)
P174
26 DIN4
Digital input 4
(I/O DeviceNet DIN4)
Low 0V ... 5V
High 15V ... 30V
R
i
= 8.1k
Ω
Input capacitance 10nF
Scan rate 1ms
Each digital input has a reaction
time of 1ms
Inputs compliant with
EN 61131-2,
Type 1
P174
27 GND
28
Reference potential
for digital signals
As for terminal 15
-
29 24V
30
external 24V supply
As for terminal 11
-
Potential separation
31 24V
o
external 24V supply
of the DOs
24VDC -/+20%
up to 1A, according to
load
protected against reverse
polarity
External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to
24V
terminal
-
32 GND
o
Reference potential
for digital signals
External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to
GND
terminal
-
33 DO1
Digital output 1
(I/O DeviceNet DO1)
P175
34 DO2
Digital output 2
(I/O DeviceNet DO2)
Low = 0V
High: 24V
Rated current: 500mA
each
The digital outputs should be used
with a separate 24V supply.
P175
35 GND
o
36
Reference potential
for digital signals
External supply voltage for digital
outputs (DO1 and DO2)
If necessary, bridge to
GND
terminal
-
Detailed information about operation via DeviceNet can be found in the relevant supplementary manual
BU0280.
-
www.nord.com
-
Summary of Contents for SK 200E Series
Page 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Page 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Page 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Page 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Page 263: ...10 Keyword index BU 0200 GB 263...
Page 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Page 265: ...The Nordac SK 200E is available to order from www inverterdrive com...